| 2007-10-06 14:43:41 | |
| | *** DENIED2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED. |
| | ** PLEASE SEE COMMENTS FROM ORIGINAL PERMIT *PROVISO* |
| | ARE STILL PART OF THESE NOTES. |
| | ** PLEASE SEE COMMENT WITH RESPECT TO THE GENERATOR NOW |
| | BEING BI-FUEL WHICH WAS NOT PART OF THE ORIGINAL |
| | GENERATOR PERMIT APPLICATION PACKAGE. |
| | |
| | 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. CODES |
| | HAVE NOT CHANGED ON PLANS FOR NEW CODES AS APPLIED. ( |
| | THIS SHOULD NOT AFFECT INSTALLATION OF ELECTRICAL). |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW #4 AND ALSO THE |
| | ORIGINAL PERMIT NOTES AS PERMIT WAS ISSUED WITH A |
| | *PROVISO*. THIS CONDITION OF ISSUANCE OF PERMIT WAS AT |
| | CONTRACTORS OWN RISK AS THE INFORMATION SUBMITTED FOR |
| | EQUIPMENT DID MEET THE CODES ARE REFLECT ON REDLINED |
| | PLANS. |
| | PLEASE SEE THE INFORMATION STILL SUBMITTED FOR THIS |
| | PARALLEL SWITCHGEAR HAS NOT PROVED TO MEET 230.76 AND |
| | 230.79. |
| | 230.70, 230.71, 110.3, 90.7 ETC. |
| | IT IS CLEAR THIS IS *PARALLEL SWITCH GEAR* HOWEVER THE |
| | BREAKER(S) DOES NOT SHOW HOW IT MEETS THESE CODES WHEN |
| | THE BREAKERS DO NOT SHOW ANY MANUAL MEANS OF DISCONNECT |
| | REQUIRED FOR SERVICE MEANS OF DISCONNECT. |
| | THIS IS CLEARLY THE NEW SERVICE MAIN FOR BUILDING. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 ALSO AS THE |
| | ORIGINAL GENERATOR UNIT WAS DIESEL ONLY AND IS NOW A |
| | BI-FUEL UNIT. |
| | THE RESPONSE FROM THE ENGINEER MENTIONS TO SEE THE |
| | ATTACHED LISTING FOR THE GTI FUEL SYSTEM. THE PREVIOUS |
| | COMMENT WAS NOT FOR THE GTI FUEL SYSTEM. |
| | THE NOTE APPLIED TO HOW THE AFTERMARKET INSTALLATION OF |
| | THIS FUEL SYSTEM VOIDS THE EXISTING |
| | CERTIFICATION/LISTING FROM THE GENERATOR MANUFACTURE. |
| | THIS FUEL SYSTEM AND GAS CONNECTION WAS DONE WITHOUT |
| | ANY PERMIT FOR INSTALLATION OF ANY OF THE GAS SYSTEMS. |
| | PLEASE KNOW AS THE PERMIT WAS NEVER ISSUED FOR THE GAS |
| | INSTALLATION AND THIS WORK WAS ALREADY DONE, A 4X |
| | PERMIT FEE MAY STILL BE APPLIED TO THEGAS PERMIT AS |
| | APPLIED FOR SUB-PERMIT. |
| | ONLY ONE SUCH UNIT THIS OFFICE IS AWARE OF HAS BEEN |
| | RE-LISTED BEFORE LEAVING THE FACTORY WITH THE FUEL |
| | SYSTEM INSTALLED AT THE FACTORY. ALL DOCUMENTS FOR |
| | RE-LISTING UNIT WOULD BE REQUIRED FOR ANY SUCH |
| | PROCESS. |
| | ANY AFTERMARKET PRODUCTS INSTALLED ON ANY LISTING |
| | EQUIPMENT WILL REQUIRE THESE TO BE RE-LISTED/TESTED, |
| | FIELD EVALUATED ETC.110.3, 90.7 ETC. (THIS WOULD ALSO |
| | INCLUDE LISTING FOR POSSIBLE MECH/PLUMBING ETC). PLEASE |
| | PROVIDE DOCUMENTATION FOR LISTING OF THIS LISTED |
| | ASSEMBLY AS INSTALLED. |
| | PLEASE HAVE THE LISTING AGENCY CONTACT THIS OFFICE IF |
| | THERE ARE ANY QUESTIONS. |
| | ALL WORK MUST BE DONE BY A NRTL. |
| | |
| | 47) NOTE:*** PLEASE KNOW THE VALUE FOR THE COMPLETE |
| | SCOPE OF WORK WILL BE REQUIRED TO BE ADJUSTED AS THE |
| | SCOPE OF WORK FROM ORIGINAL APPLICATION HAS GREATLY |
| | INCREASED AND THE VALUE FOR ALL WORK AS SHOWN IS LOW. |
| | PLEASE SEE FBC 108.3. |
| | ALL LABOR, ALL MATERIALS, ALL EQUIPMENT, INSTALLAITON, |
| | DESIGN COST ETC SHALL BE INCLUDED WHETHER OR NOT ANY OF |
| | THESE ITEMS ARE OWNER SUPPLIED. THIS INCLUDE EQUIPMENT, |
| | GENERATOR ETC. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |