| Plan Review Notes For Permit 07060548 |
| Permit Number |
07060548 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-18 16:17:22 | --------------DENIED---------------- | | | | | | 1. PLEASE SEE FUEL REVIEW FOR ADDITIONAL COMMENTS. | | | | | | 2. PLEASE SHOW GENERATOR EXHAUST TERMINATION LOCATION | | | TO BE MINIMUM 10' FROM ANY OPENINGS INTO ADJACENT | | | BUILDINGS SUCH AS DOORS, WINDOWS, SOFFIT VENTS OR AIR | | | INAKES PER FBC,M 401.5.1. | | | | | | 3. PLEASE SUBMIT FULL DOCUMENTATION FOR THIS PERMIT | | | APPLICATION PER FBC 106.1 INCLUDING GENERATOR SUBMITTAL | | | DATA. | | | | | | 4. PERMIT APPLICATION STATES A DIESEL GENERATOR IS | | | BEING INSTALLED, HOWEVER THE PLANS SHOW NATURAL GAS. IS | | | THIS GENERATOR BEING MODIFIED? | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|