| 2007-07-16 18:51:52 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING |
| | EXISTING. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL |
| | INDICATE MAXIMUM BTU LOAD AT 100%. |
| | |
| | B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS |
| | NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS |
| | REGULATORS. SECTION 106.1.2. |
| | |
| | D. NO SITE PLANSOR SURVEYSHAS BEEN SUBMITTED |
| | SHOWING SET BACKS. |
| | |
| | E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. FAC 61G15-23.002(2) & FS 471.025 |
| | |
| | REVIEW BY KEN STEVENS |