| Date |
Text |
| 2007-07-02 10:21:22 | |
| | *** UNSAT *** |
| | |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THIS PERMIT IS FOR COMPLETE ION OF |
| | WORK STARTED UNDER PERVIOUS PERMIT THEREFORE THE NEW |
| | ADOPTED CODES AS OF DECEMBER 8TH, 2006 DO NOT APPLY AT |
| | THIS TIME. |
| | PLEASE SEE PLANS NEED TO CONTAIN NOTES ACCORDINGLY. |
| | PLEASE SUBMIT TWO COMPLETE PACKAGES OF PLANS AND SPECS. |
| | PLEASE SEE NO SITE PLANS/SURVEYS SHOWING ALL EQUIPMENT |
| | SET-BACKS ETC WERE SUBMITTED. |
| | FBC 106.1 |
| | |
| | 2) NOTE: PLEASE BE SURE ALL PLANS AND SHEETS SIGNED, |
| | DATED AND SEALED BY THE ENGINEER CONTAINS TITLE BLOCKS |
| | AS REQUIRED PER FAC 61G15-23.002. |
| | |
| | 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE SPECIFIC TO |
| | INSTALL OF ELECTRICAL. PLANS INDICATE *AS-BUILT* |
| | HOWEVER STILL INDICATE EITHER/OR FOR CONDUCTORS ETC. |
| | PLEASE ADJUST PLANS FOR WHAT WAS INSTALLED. 310.16, |
| | 215.5, 240.4 ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 4) NOTE: PLEASE KNOW THE ORIGINAL PERMIT WAS ISSUED |
| | WITH CONDITIONS THAT THE EQUIPMENT INSTALLED MEETS THE |
| | NEC FOR SEVERAL SECTIONS. 230.70, 230.71, 230.76, |
| | 230.79 ETC. |
| | THIS WAS GIVEN AS NOTES AND REDLINED ON PLANS FOR |
| | INSPECTOR HOWEVER THIS HAS NOT YET BEEN VERIFIED TO |
| | THIS DATE. |
| | PLEASE SEE THIS EQUIPMENT IS THE FIRST MEANS OF |
| | DISCONNECT AS WELL AS THE SERVICE MEANS OF DISCONNECT. |
| | PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT SHEETS |
| | FOR ALL EQUIPMENT, GENERATOR, SUB BASE FUEL TANK ETC. |
| | PLEASE KNOW THIS PERMIT RECORD SET OF PLANS WILL NEED |
| | TO BE COMPLETE WITH ALL NEW INFORMATION. |
| | PLEASE SUBMIT INFORMATION AS THE GENERATOR IS NOW A |
| | BI-FUELED UNITS. PLEASE KNOW ANY LISTINGS FOR EQUIPMENT |
| | WILL STILL NEED TO BE MAINTAINED FOR MANUFACTURING |
| | STANDARDS. ANY MODIFICATION WHICH CHANGES THE LISTING |
| | FOR THE MANUFACTURING OF THE GENERATOR MAY REQUIRE A |
| | NEW ON-SITE LISTING FORM UL OR NRTL AS RECORD. PLEASE |
| | KNOW AS THE EQUIPMENT FOR THE SERVICE HAS NOT BEEN |
| | VERIFIED WITH THIS OFFICE NO COMMENTS CAN BE MADE AT |
| | THIS TIME. |
| | 90.7, 110.3 |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE NOTES AT THE EXISTING MDP1 AND |
| | MDP2 STATE THAT SIGNAGE WILL READ * OPTIONAL STAND-BY |
| | SYSTEM MAY BE PRESENT* OR WORDS TO THAT AFFECT. THIS |
| | WORDING WILL BE REQUIRED TO CHANGE AS THERE ARE MORE |
| | THAN ONE STAND-BY SYSTEMS AND SIGNS AND MAPPING OF |
| | THESE OTHER SYSTEMS MUST BE DETAILED AND NOTED AS BEING |
| | PRESENT, NOT *MAY*. |
| | 230.2, 702.8 700.8, 701.8 ETC. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2007-07-02 10:21:15 | |
| | PLANS REMOVED FROM INCOMING, PLANS RETURNED TO INCOMING |
| | WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS DONE. |