Plan Review Notes
Plan Review Notes For Permit 07060536
Permit Number 07060536
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-21 19:15:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SHT A-0 CONSTRUCTION NOTES: BUILDING CODE ADOPTED IS
 THE FBC-2004 W/2005 & 2006 AMENDMENTS NOT THE STANDARD
 CODE AS INDICATED. PLEASE CORRECT CODE REFERENCE.
 SECTION 106.1.1.
  
 2. ALL SHEETS THE ADDRESS FOR THE ENGINEER OF RECORD
 DOES NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA
 STATE DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR
 THE TITLE BLOCK INFORMATION. FAC 61G15-23.002(2) & FS
 471.025.
  
 3. SHT A-9 SUBMIT MORE INFORMATION ON THE JACUZZI'S.
 SUBMIT THE MANUF. SPECIFICATION SHEETS. SECTION 303.4.
  
 4. SHTS P-1 & P-14 HAVE NOT BEEN SUBMITTED, ALSO TWO
 DIFFERENT SHEETS DESIGNATED P-10 HAVE BEEN SUBMITTED.
 SINCE NO SHEET INDEX HAS BEEN SUBMITTED, I NEED A
 CLARIFICATION THAT NO P-1, P-14 AND TWO P-10 SHEETS ARE
 CORRECT. SECTION 106.1.1. PLEASE SUBMIT A SHEET INDEX
 TO VERIFY ALL SHEETS TO BE SUBMITTED ARE INDEED
 SUBMITTED.
  
 5.A GAS DEMO PERMIT IS REQUIRED.
  
 6. SHT P-8 IT APPEARS THAT A 2" CONDENSATE CONNECTS TO
 THE SANITARY BUILDING DRAIN IN THE WEST BUILDING. THIS
 IS NOT APPROVED. CONDENSATE SHALL DRAIN SEPARATELY FROM
 THE BUILDING AND SHALL CONNECT EITHER TO THE STORM
 DRAIN, A CATCH BASIN. OR DRAIN TO A PLANTED AREA.
 MUNICIPAL CODE SECTION 90-125(B)(5).
  
 7. SHT P-8 WEST PIPING STILL SHOWS BATHTUB WHEN CHANGED
 TO SHOWER. PLEASE CLARIFY. SECTION 106.1.1.
  
 8. SHT P-8 EAST BUILDING LEGEND #(6) INDICATES A 2"
 SANT. & VENT. PER SECTION 406.3 A MINIMUM 3" IS
 REQUIRED TO THE W/M.--INDICATE WHERE THE BRANCH
 LINES CONNECTS TO THE BUILDING DRAIN. SECTION 106.1.1.
  
 9. SHT P-8 EAST BUILDING. HOT WATER DESIGNATION, (A),
 NOT SHOWN TO KITCHEN SINK, LAVS OR SHOWERS. PLEASE
 INDICATE DESIGNATION FORALL HOT WATER LINES. SECTION
 106.1.1.
  
 10. SHT P-8 EAST BUILDING. A FLOOR DRAIN IS REQUIRED IN
 THE ROOMS CONTAINING AUTOMATIC CLOTHES WASHERS. SECTION
 412.4.
  
 11. SHT P-8 HOT WATER REQUIRED TO JANITOR SINK AND TO
 SINK IN THE CLEANING ROOM. SECTION 607.1.
  
 12. SHT P-8 SHOW THE EAST BUILDING DRAIN & ALL BRANCH
 LINES TO ALL BATHROOM GROUPS, KITCHEN SINK, MOP SINKS,
 CLEANING SINKS & WASH MACHINES. SECTION 106.1.1.
  
 13. SHT P-8 APTO 3-EAST SHOW A SHOWER ON THE FLOOR
 PLAN, BUT IS INDICATED AS A TUB. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 14. SHT P-8 SHOW UNDERGROUND SANITARY PIPING TO NEW
 PLUMBING FIXTURES. (W/M'S, JAN SINK, CLEANING SINKS
 ETC.). SECTION 106.3.5.1.3(4).--SHOW THE BUILDING
 DRAIN LINE, INDICATE WHERE IT EXITS THE BUILDING & SHOW
 WHERE & HOW ALL STACKS, FIXTURE GROUPS, NEW FIXTURES
 ETC. CONNECT TO THE BUILDING DRAIN. SECTION 704.
  
 15. SHT P-9 FLOOR DRAIN REQUIRED IN THE LAUNDRY ROOMS.
 SECTION 412.4.
  
 16. SHT P-9 NO #2 IN A SQUARE BOX IS INDICATED ON THE
 EAST BLDG. LEGEND & NOTES, BUT IS SHOWN AT AHU-1.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 17. SHT P-9 APTO 9-EAST SHOWS A SHOWER ON THE FLOOR
 PLAN, BUT IS INDICATED AS A TUB. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 18. SHT P-9 INDICATE USE OF SINK IN THE CLEANING ROOM.
 SER SECTION 607.1 IF THE SINK IS USED FOR CLEANSING OR
 BUILDING MAINTENANCE, HOT WATER IS REQUIRED. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 19. SHT P-9 FLOOR DRAINS ARE REQUIRED IN THE LAUNDRY
 ROOMS. IT APPEARS THAT THE FLOOR DRAIN IN THE WEST
 BUILDING HAS BEEN CHANGED TO A MOP SINK. SECTION
 412.4.
  
 20. SHT P-10 INDICATE USE OF SINK IN THE CLEANING ROOM.
 SER SECTION 607.1 IF THE SINK IS USED FOR CLEANSING OR
 BUILDING MAINTENANCE, HOT WATER IS REQUIRED. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 21. SHT P-10 FLOOR DRAINS ARE REQUIRED IN THE LAUNDRY
 ROOMS. IT APPEARS THAT THE FLOOR DRAIN IN THE WEST
 BUILDING HAS BEEN CHANGED TO A MOP SINK. SECTION
 412.4.
  
 22. SHT P-10 APTO 16 EAST SHOW A SHOWER ON THE FLOOR
 PLAN, BUT IS INDICATED AS A TUB. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 23. 2ND SHT P-10 INDICATES TYPICAL UNITS AT EAST
 BUILDING, BUT UNITS 1,7,14 & 21 EAST BUILDING UNITS ARE
 NOT TYPICAL OF THIS FLOOR PLAN. ALSO 5TH FLOOR SHOWS
 TUBS AND THE TYPICAL SHOWS SHOWERS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 24. 2ND SHT P-10 PLEASE IDENTIFY THE NEW SANITARY
 ISOMETRIC RISER DIAGRAMS. IS THE NEW 2" RISER(8FU) FOR
 THE KITCHEN IN THE WEST BUILDING? IF SO INDICATE ON THE
 FLOOR PLAN WHERE THE VENT IS RUN ON THE TYPICAL UNIT
 FLOOR PLAN. WHERE IS THE RISERS FOR THE NEW LAUNDRY
 ROOMS, (2 ON 1ST FLOOR), (EAST) & NEW CLEANING ROOMS,
 (EAST? PLEASE CLARIFY. SECTION 106.1.1.
  
 25. 2ND SHT P-10 ONE NEW SANITARY ISOMETRIC SHOWS A
 HORIZONTAL DRY VENT.PER SECTIONS 905.3 & 905.4 THIS
 IN NOT APPROVED.
  
 26. 2ND SHT P-10SUBMIT A SANT RISER ISOMETRIC AND A
 WATER RISER ISOMETRIC FOR NEW UNIT IN THE WEST
 BUILDING. SHOW ALL PIPE SIZES, TRAPS AND VENTS FOR THE
 SANT. AND ALL PIPE SIZES, VALVES, AND REQUIRED WATER
 HAMMER ARRESTORS FOR THE WATER ISOMETRIC RISER DIAGRAM.
 SECTION 106.3.5.1.3(3)(4)(6)(10)(13).
  
 27. 2ND SHT P-10 SUBMIT MANUF. SPECIFICATION SHEETS FOR
 THE TANKLESS WATER HEATERS. SHEETS SHALL SHOW LISTING.
 SECTION 303.4.
  
 28. SHT P-15 IDENTIFY ALL RISERS EITHER WITH A SANT.
 NUMBER DESIGNATION SUCH AS S-1, S-2, S-3 ETC, OR BY
 BUILDING & APARTMENT NUMBER SUCH AS TYPICAL OF WEST
 BLDG APT0 8 & 9,OR 3 & 4 ETC. AS SHOWN I AM UNABLE TO
 DETERMINE WHICH RISER IS FOR WHICH UNITS. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 29. SHT P-16 EXISTING SANITARY RISER EAST BUILDING NOT
 #1 INDICATES "REWORK ALL EXISTING STACKS". PLEASE
 INDICATE ALL REWORKED AREAS OF EACH STACK. IDENTIFY
 EACH RISER PER UNIT, (APTS) OR RISER DESIGNATION. S-1,
 S-2 ETC. INDICATE ON THE FLOOR PLAN THE RISER
 DESIGNATION IF USED. SECTION 106.1.1.
  
 30. SUBMIT NEW RISERS FOR ALL NEW FIXTURES AND SHOW THE
 CONNECTION OF THE RISERS TO THE BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM. SECTION 106.1.1.
  
 31. SHT P-17 IS INDICATED AS SHEET 16 OF 17. PLEASE
 CORRELATE SHEETS. SECTION 106.1.1.
  
 32. ONE SET OF PLANS HAS SHEET E-15AFTER SHEET P-17.
  
 33. INDICATE HOW THE JACUZZI TUBS ARE TO BE FILLED AND
 DRAINED. PLEASE INDICATE WHICH RISER DIAGRAMS THEY
 CONNECT TO. SECTION 106.1.1.
  
 34. PLANS SEEM TO BE INCOMPLETE AT THIS TIME AND MORE
 COMMENTS MAY BE FORTHCOMING AT NEXT REVIEW.
  