Plan Review Notes
Plan Review Notes For Permit 07060536
Permit Number 07060536
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-23 16:40:31----------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE THE LEVEL OF ALTERATION, OCCUPANCY
 CLASSIFICATION AND OCCUPANT LOAD. FBC 106.3.5.1
  
 2.. PROVIDE INFORMATION ON THE PREVIOUS EXISTING A/C
 SYSTEMS TO DETERMINE COMPLIANCE WITH FBC, EB 501.2, IF
 APPLICABLE.
  
 3. PLEASE PROVIDE SUBMITTALS FOR ALL NEW EQUIPMENT SUCH
 AS CLOTHES DRYERS, DAMPERS, GRILLS, LOUVERS, KITCHEN
 EXHAUST HOODS. FBC 106.1
  
 4. PRODUCT APPROVALS ARE REQUIRED FOR LOUVERS AND
 PRE-ENGINEERED A/C STANDS PER FAC 9B-72. FOR MORE
 INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM,
 PLEASE VISIT WWW.FLORIDABUILDING.ORG
  
 5. REGARDING THE NEW VENTILATION SYSTEM IN CORRIDORS,
 SHOW COMPLIANCE WITH FBC,M 401.4 AS FOLLOWS:
  
 EQUIPMENT AND DUCTWORK FOR EXIT ENCLOSURE VENTILATION
 SHALL COMPLY WITH ONE OF THE FOLLOWING ITEMS:
 1. SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED
 EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY
 CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK ENCLOSED IN
 CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING FOR SHAFTS.
 2. WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE EXIT ENCLOSURE, THE INTAKE AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE
 DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH AIR SHALL
 BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING FOR
 SHAFTS.
 3. WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT
 AND DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT,
 WITH CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING FOR SHAFTS.
 IN EACH CASE, OPENINGS INTO FIRE-RESISTANCE-RATED
 CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR
 MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY
 SELF-CLOSING FIRE-RESISTANCE-RATED DEVICES IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING FOR
 ENCLOSURE WALL OPENING PROTECTIVES.
 EXIT ENCLOSURE VENTILATION SYSTEMS SHALL BE INDEPENDENT
 OF OTHER BUILDING VENTILATION SYSTEMS.
  
 6. ARCHITECTURAL PLANS DO NOT INDICATE THE LOCATION OF
 FIRE RESISTANCE-RATED ELEMENTS OF THE BUILDING. PLEASE
 PROVIDE THIS INFORMATION ON PLANS, AS IT IS NEEDED TO
 FACILITATE A COMPLETE REVIEW OF THE MECHANICAL
 SYSTEMS.
  
 7. WHAT IS THE LOCATION OF CONDENSING UNITS 1,2 AND 3?
 THEY ARE NOT SHOWN ON PLANS. FBC 106.1.1
  
 8. PG M-8: AC EQUIPMENT SCHEDULE, THE LOCATION OF
 EQUIPMENT ON PLANS DOES NOT MATCH THE LOCATION SHOWN ON
 THE SCHEDULE. EXAMPLE: ACCORDING TO THE SCHEDULE, AHU 1
 IS ON THREE DIFFERENT FLOORS IN TWO DIFFERENT
 BUILDINGS. PLEASE CORRECT.
  
 9. PG M-8: DRYER EXHAUST DETAIL, ARE THE DRYER EXHAUST
 DUCTS PENETRATING A RATED CEILING? IF SO, PROVIDE
 DETAIL FOR OPENING PROTECTIVES PER FBC CH.7.
  
 10. PG M-8: CONDENSING UNIT DETAIL, IF PRE-ENGINEERED
 A/C STANDS ARE TO BE USED, STANDS ARE TO BE FASTENED TO
 STRUCTURE AND CONDENSERS ARE TO BE FASTENED TO STANDS
 PER MANUFACTURER'S INSTRUCTIONS.
  
 11. PLEASE SHOW MEANS AND LOCATION OF CONDENSATE
 DISPOSAL PER FBC,M 307.2.1. ALSO, SHOW MEANS OF
 AUXILIARY DRAIN PROTECTION PER FBC,M 307.2.3.
  