Date Text
2007-08-10 13:49:43*****DENIED*****
  
  
 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALLCOMPLY WITH NFPA 241.
  
 03.THE REMOVAL, THE STOCKING OF BUILDING MATERIALS &
 SUPPLIES, AND/OR ANY OTHER ASSOCIATED OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING
 STREETS, ALLEYS, FIRE LANES).
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 PALM BEACH LAKES BOULEVARD, POST THE NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, THE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
 06.PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE
 TO AN EXIT.
  
 07.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND ALL
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 08.MORE EXIT LIGHTS NEEDED IN WEST BUILDING CORRIDORS
 (FLOORS 2 THRU 5) TO DIRECT PERSON(S) TO THE EXITS. NEW
 SIGN PLACEMENT SHALL BE THAT NO SUCH POINT IN AN EXIT
 ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING
 DISTANCE OR 30 FEET, WHICHEVER IS LESS, FROM THE
 NEAREST SIGN.
  
 09.PLEASE EXPLAIN LACK OF EMERGENCY LIGHTS IN WEST
 BUILDING CORRIDORS (FLOORS 2 THRU 5).
  
 10.NO SMOKE ALARMS SHOWN IN THE DWELLING UNITS.IN
 NEW CONSTRUCTION, WHERE TWO OR MORE SMOKE ALARMS ARE
 WITHIN A DWELLING UNIT, THEY SHALL BE ARRANGED SO THAT
 OPERATION OF ANY SMOKE ALARM SHALL CAUSE THE OTHER
 SMOKE ALARMS WITHIN THE DWELLING UNIT TO SOUND.SMOKE
 ALARMS SHALL SOUND ONLY WITHIN AN INDIVIDUAL DWELLING
 UNIT AND SHALL NOT ACTIVATE THE FIRE ALARM SYSTEM.
  
 11.NO EMERGENCY LIGHTNG SHOWN IN EAST BUILDING SOUTH
 STAIRWELL (FLOORS 2 THRU 5).
  
 12.ON SHEET E-12, ONCE EXITING FROM THE DOOR AT THE
 SOUTH END OF THE CORRIDOR IS ACCOMPLISHED, WHERE DO
 PERSON(S) GO FROM THERE IN CONTINUATION OF THE EXITING
 PROCESS.
  
 13.ON SHEET FA-7, UNDER FIRE ALARM SPECIFICATIONS,
 INSERT THE WORD 'LAKES' BETWEEN BEACH AND BOULEVARD IN
 ADDRESS LOCATION.
  
 14.ON SHEET FA-7, EXPLAIN HOW CHAPTER 38 OF NFPA 101
 (NEW BUSINESS OCCUPANCIES) PERTAINS TO THE OCCUPANCY
 TYPE PROPOSED IN THE SUBMITTED PLANS.
  
 15.ON SHEET FA-7 SEQUENCE OF OPERATION FOR THE FIRE
 ALARM SYSTEM, AMEND ACTIVATION OF DUCT DETECTOR TO
 REFLECT THAT THE ACTIVATION OF A DUCT DETECTOR SHALL
 INITIATE A GENERALFIRE ALARM.
  
 16.ON SHEET FA-4, EXPLAIN THE LACK OF A DUCT DETECTOR
 IN AHU-2.
  
 17.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM.
  
 18.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDE THAT THE CRITERIA AS PER NFPA
 101 7.2.1.6.2 ARE MET.
  
 19.PROVIDE THE PRESCRIPTIVE STRENGTH FOR THE NEW
 BALCONEY'S GUARDRAILS.
  
 20.SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER AND/OR FIRE ALARM SYSTEM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722