| Date |
Text |
| 2007-08-10 13:49:43 | *****DENIED***** |
| | |
| | |
| | 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALLCOMPLY WITH NFPA 241. |
| | |
| | 03.THE REMOVAL, THE STOCKING OF BUILDING MATERIALS & |
| | SUPPLIES, AND/OR ANY OTHER ASSOCIATED OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO |
| | THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING |
| | STREETS, ALLEYS, FIRE LANES). |
| | |
| | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | PALM BEACH LAKES BOULEVARD, POST THE NUMERICAL ADDRESS |
| | ON THE BUILDING.AS PER WEST PALM BEACH CODE, THE |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH. |
| | |
| | 06.PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE |
| | TO AN EXIT. |
| | |
| | 07.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND ALL |
| | OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 08.MORE EXIT LIGHTS NEEDED IN WEST BUILDING CORRIDORS |
| | (FLOORS 2 THRU 5) TO DIRECT PERSON(S) TO THE EXITS. NEW |
| | SIGN PLACEMENT SHALL BE THAT NO SUCH POINT IN AN EXIT |
| | ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING |
| | DISTANCE OR 30 FEET, WHICHEVER IS LESS, FROM THE |
| | NEAREST SIGN. |
| | |
| | 09.PLEASE EXPLAIN LACK OF EMERGENCY LIGHTS IN WEST |
| | BUILDING CORRIDORS (FLOORS 2 THRU 5). |
| | |
| | 10.NO SMOKE ALARMS SHOWN IN THE DWELLING UNITS.IN |
| | NEW CONSTRUCTION, WHERE TWO OR MORE SMOKE ALARMS ARE |
| | WITHIN A DWELLING UNIT, THEY SHALL BE ARRANGED SO THAT |
| | OPERATION OF ANY SMOKE ALARM SHALL CAUSE THE OTHER |
| | SMOKE ALARMS WITHIN THE DWELLING UNIT TO SOUND.SMOKE |
| | ALARMS SHALL SOUND ONLY WITHIN AN INDIVIDUAL DWELLING |
| | UNIT AND SHALL NOT ACTIVATE THE FIRE ALARM SYSTEM. |
| | |
| | 11.NO EMERGENCY LIGHTNG SHOWN IN EAST BUILDING SOUTH |
| | STAIRWELL (FLOORS 2 THRU 5). |
| | |
| | 12.ON SHEET E-12, ONCE EXITING FROM THE DOOR AT THE |
| | SOUTH END OF THE CORRIDOR IS ACCOMPLISHED, WHERE DO |
| | PERSON(S) GO FROM THERE IN CONTINUATION OF THE EXITING |
| | PROCESS. |
| | |
| | 13.ON SHEET FA-7, UNDER FIRE ALARM SPECIFICATIONS, |
| | INSERT THE WORD 'LAKES' BETWEEN BEACH AND BOULEVARD IN |
| | ADDRESS LOCATION. |
| | |
| | 14.ON SHEET FA-7, EXPLAIN HOW CHAPTER 38 OF NFPA 101 |
| | (NEW BUSINESS OCCUPANCIES) PERTAINS TO THE OCCUPANCY |
| | TYPE PROPOSED IN THE SUBMITTED PLANS. |
| | |
| | 15.ON SHEET FA-7 SEQUENCE OF OPERATION FOR THE FIRE |
| | ALARM SYSTEM, AMEND ACTIVATION OF DUCT DETECTOR TO |
| | REFLECT THAT THE ACTIVATION OF A DUCT DETECTOR SHALL |
| | INITIATE A GENERALFIRE ALARM. |
| | |
| | 16.ON SHEET FA-4, EXPLAIN THE LACK OF A DUCT DETECTOR |
| | IN AHU-2. |
| | |
| | 17.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM. |
| | |
| | 18.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO |
| | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS |
| | CONTROL SYSTEM PROVIDE THAT THE CRITERIA AS PER NFPA |
| | 101 7.2.1.6.2 ARE MET. |
| | |
| | 19.PROVIDE THE PRESCRIPTIVE STRENGTH FOR THE NEW |
| | BALCONEY'S GUARDRAILS. |
| | |
| | 20.SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE |
| | SPRINKLER AND/OR FIRE ALARM SYSTEM REMODEL. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |