Plan Review Notes
Plan Review Notes For Permit 07060536
Permit Number 07060536
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-01 10:27:362007-07-01 10:27:36
  
 *** UNSAT ***
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004
 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE
 SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER
 AND NO COST TO CONTRACTOR.
 PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY
 THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE.
  
 3) NOTE: PLEASE SEE COMMENTS FROM BUILDING, FIRE
 MARSHAL AND OTHER TRADES WHICH WILL REQUIRE A SEPARATE
 PERMIT APPLICATION FOR EACH BUILDING. PLEASE ALSO SEE
 AN ADDRESSING STOP HAS BEEN ADDED AS EACH BUILDING WILL
 NOT CONTAIN THE SAME ADDRESS.
 PLEASE ADJUST TITLE BLOCKS FOR EACH BUILDING SET OF
 PLANS ONCE THE ADDRESS HAS BEEN CORRECTED.
 FAC 61G1-16.004,61G15-23.002
  
 4) NOTE: PLEASE SEE TITLE BLOCKS FOR THE ENGINEER DOES
 NOT CORRELATE WITH THE ADDRESS AS LISTED ON THE STATE
 WEBSITE FOR THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
 PLEASE ADJUST. FAC 61G1-16.004.
  
 5) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON
 THE TITLE BLOCKS FOR MEP SHEETS. PLEASE SEE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 FIRM. PLEASE SEE FAC 61G15-23.002 AND FLORIDA STATUTES
 471.023.
 ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 6) NOTE: PLEASE SEE FS 471.025. PLEASE SEE PLANS APPEAR
 TO BE SIGNED WITH *INITIALS*, IF THIS IS INDEED THE
 LEGAL SIGNATURE FOR EACH OF THE DESIGN PROFESSIONALS ON
 PLANS, PLEASE SUBMIT A LETTER FOR SIGNATURE
 VERIFICATION WHICH WILL BE REQUIRED TO BE SIGNED,
 DATED, SEALED AND NOTARIZED.
 THE LETTER MUST BE ORIGINAL AND CORRECTLY NOTARIZED AS
 REQUIRED UNDER FS 117.05.
 ** THESE LETTERS WILL GO INTO OUR SIGNATURE FILE FOR
 ANY FUTURE PROJECTS OR SIGNATURE VERIFICATION.
  
 7) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH SUBMITTED PANEL SCHEDULES. PLEASE SEE
 THERE ARE TOO NUMEROUS LOCATION MISSING TO IDENTIFY
 EACH IN NOTES.
 PLEASE SEE 700.12F FOR CIRCUITING OF ALL EMERGENCY AND
 EXIT LIGHTS.
 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE SEE FBC 2004 W/2006 REVISION FOR
 COMPLIANCE WITH CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING
 CONTROLS WHICH ARE MISSING FROM PLANS AT THIS TIME. NO
 REVIEW OF ANY OF THESE ITEMS CAN BE DONE AT THIS TIME.
 PLEASE SUBMIT ALL INFORMATION IF A SYSTEM IS
 INSTALLED.
 PLEASE SUBMIT ANY TIMED SCHEDULING.
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR LIGHTING.
 PLANS APPEAR TO SHOW SOME SORT OF LIGHTS HOWEVER NOT
 CLEAR THIS TIME.
 PLEASE SUBMIT TIME ON DEVICES AND/OR OVER RIDE DEVICES.
 PLEASE SEE THE SECTIONS GIVEN FOR THE MAXIMUM TIMES
 PERMITTED.
 PLEASE SUBMIT COMPLETED FIXTURE LEGENDS FOR ALL
 FIXTURES WHICH ARE TO CONTAIN ALL INFORMATION ON THESE
 FIXTURES AND WILL NEED TO CORRELATE WITH LIGHTING
 PERFORMANCE CALCULATIONS FOR COMMON AREAS.
 PLEASE SEE EGRESS PATHS AND CONTROLS PERMITTED IN THE
 FBC 1006.1.2, NFPA-101 7.8.1.2.2
 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING SWITCHES SHALL
 BE PERMITTED WITHIN THE MEANS OF EGRESS, PROVIDED THAT
 THE SWITCH CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE
 OPERATION, THE ILLUMINATION TIMERS ARE SET FOR MINIMUM
 15-MINUTE DURATION, AND THE MOTION SENSOR IS ACTIVATED
 BY ANY OCCUPANT MOVEMENT IN THE AREA SERVED BY THE
 LIGHTING UNITS.
  
 PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS BASED ON NEW AREAS OF COMMON USE. THE
 SHEETS SUBMITTED APPEAR TO BE FOR UNITS ONLY. PLEASE
 KNOW WHEN THE ENERGY CALCULATIONS ARE CORRECTED AND
 SUBMITTED THE OWNER AGENT IS REQUIRED TO BE SIGNED ON
 EACH. 13-103.1.1.1
 13-415.1.AB.1.1, 13-415.1.C, 13-415.2.
  
 9) NOTE: PLEASE SEE 620.22-620.24 AS THE DEDICATED
 CIRCUITS SHALL BE STATED ON PLANS AND COORDINATE WITH
 THE SUBMITTED PANEL SCHEDULE(S). PLEASE KNOW THESE
 REQUIRED DEDICATED CIRCUITS SHALL NOT FEED ANY OTHER
 AREAS AS THEY ARE SHOWN ON PLANS.
  
 10) NOTE: PLEASE SEE 13-413.1.ABC.1 OF THE FBC CHAPTER
 13. PLEASE SUBMIT WORST CASE SCENARIO FOR VOLTAGE DROP
 ON FEEDERS AND BRANCH CIRCUITS.
  
 11) NOTE: PLEASE SEE ALL DISCONNECTING MEANS SHALL BE
 GROUPED IN WEST BUILDING AND EAST BUILDING FOR EACH
 SERVICE GRANTED AND MEETS 230.2.
 PLEASE SEE THE LOCATION OF MAINS AND THE AMOUNT OF
 SERVICES BEING REQUESTED AND SHOWN IN EAST BUILDING
 DOES NOT MEET CODE AND WILL NOT BE GRANTED.
 PLEASE ADJUST THE SIZE OF SERVICES AND PLEASE KNOW ALL
 MAINS SHALL BE GROUPED AS REQUIRED PER 225.34 AND
 230.72.
 PLEASE SEE THE LOCATIONS OF SERVICE MAINS WILL ALSO BE
 REQUIRED IN A READILY ACCESSIBLE LOCATION FOR FIRE
 DEPARTMENT PERSONNEL. THIS HAS ALREADY BEEN CONFIRMED
 WITH THE FIRE MARSHAL?S OFFICE.
 PLEASE SEE THE LOCATION OF THE MAINS ON THE WEST
 BUILDING IS OK, HOWEVER PLEASE SEE THE NUMBER OF
 SERVICES IS NOT GRANTED.
 PLEASE SEE LOCATIONS OF DISCONNECTING MEANS, SERVICES
 AND MAIN LOCATIONS ON THE EAST BUILDING ARE NOT
 ACCEPTABLE TO THIS JURISDICTION.
 PLEASE SEE THE MAIN MAY NOT BE LOCATED ON THE SECOND
 FLOOR AS SHOWN. THIS AHJ DOES NOT HAVE AN ISSUE WITH
 MAINS LOCATED ON THE MEZZANINE LEVEL OR 2ND FLOOR AS
 LONG AS DIRECT ACCESS TO MAINS FROM THE OUTSIDE OF THE
 BUILDING IS DESIGNED. AS SHOWN ON PLANS THIS IS NOT
 DONE.
 230.70.230.71.230.72 ETC
 THE METER CENTERS MAY BE LOCATED IN ELECTRICAL ROOMS
 ABOVE THE FIRST FLOOR HOWEVER MAINS MUST BE GROUPED AND
 LOCATED ON FIRST FLOOR.
 ** AS THERE WILL BE SEVERAL DESIGN CHANGES TO THE
 ELECTRICAL SERVICE MANY OF THE COMMENTS WILL NOT APPLY
 HOWEVER COMMENTS ARE MADE BASED ON THE PLANS
 SUBMITTED.
  
 12) NOTE: PLEASE SEE THE LOCATIONS OF ELECTRICAL PANELS
 IN MANY UNITS DO NOT MEET 110.26, 408.7, 240.24. PLEASE
 SEE MANY OF THESE WILL BE REQUIRED TO BE MOVED. PLEASE
 ALSO SEE MANY SHEETS INDICATE A SHIFT OF SOME KIND
 WHICH PLACES SOME OF THESE PANELS IN LOCATIONS WHERE NO
 WALLS ETC ARE PRESENT.
  
 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE PROPOSED INSTA-HOT WATER HEATING UNITS.
 90.7,110.3
 FBC 106.1.2
  
 14) NOTE: PLEASE SEE THERE ARE MISSING EXIT SIGNS AND
 LIGHTING REQUIRED PER NFPA-101. 7.8 AND 7.9. PLEASE SEE
 FIRE MARSHAL OFFICE COMMENTS ALSO.
  
 15) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 EGRESS PATHS FORM CONDO UNITS. PLEASE SEE NFPA-101
 7.8.1.3, 7.9.2.2 FOR STAIRS. PLEASE SUBMIT AND INDICATE
 LEVELS UNDER NORMAL AND EMERGENCY.
 PLEASE SEE THE LIGHTING AS SHOWN IN STAIRS DOES NOT
 MEET THE LS 101 SECTIONS FOR MINIMUM REQUIREMENTS.
 PLEASE SEE MISSING LIGHTING IN GARAGE.
 PLEASE SEE THE FOLLOWING LOCATIONS WILL BE REQUIRED TO
 CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
 MAIN ELECTRICAL ROOMS, FIRE COMMAND ROOMS ,STAIRS ETC
 AS STATED.
 PLEASE ALSO SEE 700.16, 700.12F
  
  
 PLEASE SEE NOT #8 ABOVE WITH RESPECT TO THE TYPE OF
 FIXTURES AND THE FIXTURE LEGEND TO BE COMPLETED.
  
 16) NOTE: PLEASE PLANS INDICATE SMOKE DETECTORS AND NOT
 SMOKE ALARMS HOWEVER NO INFORMATION IS SHOWN FOR
 SOUNDING DEVICES OR SYSTEM IF THESE DEVICES ARE INDEED
 SMOKE DETECTORS.
 PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE DETECTORS AND
 SMOKE ALARMS.
 PLEASE ADJUST PLANS ACCORDINGLY AND CIRCUIT PLANS AS
 NEED.
 PLEASE SEE 115.1.1.1 AND 11.8.3.
  
 11) NOTE: PLEASE KNOW EVEN AS ANY FIRE SPRINKLER OR
 FIRE ALARM PLANS WILL BE REQUIRED UNDER A SEPARATE
 PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE
 MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND
 .3(4).
 PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING
 REQUIRED INFORMATION.
  
 12) NOTE: PLEASE INDICATE ALL THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS ON PANE SCHEDULE(S). PLEASE SEE THE
 NOTE LOCATED ON PLANS QUOTING THE CODE INSTEAD OF
 SHOWING THE REQUIRED DETAIL IS NOT ACCEPTABLE.
 FBC 106.3.5.1.2, 106.1.2, NEC 408.4, 210.12
  
 13) NOTE: PLEASE SEE THERE IS A SHIFT ON PLANS IN MANY
 LOCATIONS WHICH SEEMS TO MISPLACE CIRCUITING AND OTHER
 ITEMS FOR REVIEW.
 PLEASE BE SURE PLANS ARE CORRECTED.
 FBC 106.1
  
 14) NOTE: PLEASE SEE NEC 210.52B1, 210.11C1, 220.53 AS
 THE TWO MINIMUM SMALL APPLIANCE CIRCUITS COULD NOT BE
 LOCATED ON PLANS. PLEASE SEE VA SHALL MEET THE MINIMUM
 AS STATED IN THE NEC, NOT THE VA AS STATED ON PANEL
 SCHEDULE.
 PLEASE SEE SOME UNITS INDICATE SOME SORT OF
 DINING/BREAKFAST AREAS WHICH CIRCUITING IS REQUIRED TO
 MEET THE SAME CODE SECTIONS AS GIVEN.
  
 15) NOTE: PLEASE SEE MISSING THE *ENLARGED ROOM LAYOUT*
 FOR THE WEST ELECTRICAL ROOM.
 FBC 106.1, 106.1.2
  
 16) NOTE: PLEASE SEE LOAD CALCULATIONS FOR SERVICE(S)
 DO NOT CORRELATE WITH ALL LOADS AS STATED ON ELECTRICAL
 PANELS.
 PLEASE SEE THERE ARE SUBSTANTIAL LOADS MISSING FROM
 BUILDING LOAD CALCULATIONS ALL TOGETHER?
 PLEASE SEE THE LOADS ARE ALREADY SHOWN ON UNIT PANELS
 AT 70AMPS AND SOME LOADS ARE NOT SHOWN CORRECTLY AND
 NOT FIGURED AT ALL. PLEASE KNOW AS SHOWN EACH OF THESE
 UNITS WILL BE REQUIRED TO HAVE A LARGER FEEDER, SERVICE
 TO EACH UNIT. NO DESIGN HAS BEEN TAKEN FOR FUTURE
 LOADS. 90.8
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125% PLEASE SEE
 NEC 220
 FBC 106.3.5.1.2
  
 17) NOTE: PLEASE SEE THE PLANS SHALL ALL INDICATE A
 MINIMUM OF 1/8INCH SCALE. FBC ADMIN SECTION. 106.1
  
 18) NOTE: PLEASE SEE THERE ARE MULTIPLE VOLTAGES SHOWN
 ON THE SAME SERVICE EQUIPMENT?
 PLEASE CORRELATE.
 FBC 106.3.5.1.2, NEC 230, 240 ETC
  
 19) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS TO UNITS AS REQUIRED PER 250.24, 250.110,
 250.122.
 PLEASE BE SURE TO INDICATE ALL AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 20) NOTE: PLEASE CLARIFY COLD WATER AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50.
  
 21) NOTE: PLEASE SEE 210.52 AS SOME UNITS ARE MISSING
 REQUIRED RECEPTACLES FOR 2FT OR MORE OF WALL SPACE.
 PLEASE SEE THIS INCLUDES KITCHEN WALLS.
  
 22) NOTE: PLEASE SUBMIT/INDICATE ALL OF THE REQUIRED
 AIC RATINGS FOR SERVICE EQUIPMENT/MAINS AND BRANCH
 BREAKERS.
 110.9.
 FBC 106.1.2, 106.3.5.1.2
  
 23) NOTE: PLEASE SEE THE CIRCUITING FORWASHERS AND
 DRYERS CAN NOT BE CORRECT. PLEASE SEE SOME WASHERS
 INDICATE 240V CIRCUITS TO THEM AND THE DRYERS INDICATE
 120V CIRCUITS? PLEASE CORRELATE ALL OF THESE.
 FBC 106.1.2
  
 24) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI
 PROTECTION OF ALL RECEPTACLES LOCATED WITHIN 6FT OF
 LAUNDRY TUBS. THIS INCLUDES 15/20AMP 120V DEDICATED
 CIRCUITS. THIS IS NEW IN THE 2005 NEC>
  
 25) NOTE: PLEASE SEE PLANS INDICATE 310.15B6 FOR
 DE-RATING OF FEEDERS AND SERVICE CONDUCTORS. PLEASE SEE
 THE SECTION OF THE CODE DOES NOT APPLY TO THE SERVICE
 AS SHOWN.
 PLEASE ADJUST.
  
 26) NOTE: PLEASE SEE BUILDING REVIEW NOTES AND CLARIFY
 *BUILDING* SEPARATIONS. PLEASE SEE AT THIS TIME THIS IS
 BEING SHOWN AS TWO SEPARATE BUILDINGS AND BASED ON
 PLANS THE SEPARATION OF THESE BUILDINGS DOES NOT APPEAR
 TO GIVE IT THE DEFINITION OF TWO SEPARATE BUILDING
 BASED ON THE FBC.
 PLEASE SEE THIS WILL GREATLY AFFECT THE NOTE # 11
 ABOVE.
  
 27) NOTE: PLEASE SHOW LOCATIONS FOR ALL PANELS. WHERE
 ARE THE HOUSE PANELS ALL LOCATED?
  
 28) NOTE: PLEASE KNOW AS PER FPL GUIDELINES, NO
 ELECTRICAL FROM BUILDING MAY BE INSTALLED IN FPL
 VAULT/TRANSFORMER ROOMS.
 PLEASE ALSO SEE MINIMUM FIRE SEPARATION REQUIRED PER
 450.42
  
 29) NOTE: PLEASE SEE 680.41, 680.44 ETC AS THE LOCATION
 S SHOWN FOR THE ELECTRICAL FOR THE JACUZZIS ARE SHOWN
 TOO CLOSE. PLEASE ALSO INDICATE THE EPO LOCATIONS.
  
  
 *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES
 REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH
 ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENT SON
 THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-01 08:52:002007-07-01 08:52:00
 REVIEW IN PROGRESS, NOTES TO FOLLOW.
2007-06-29 20:01:492007-06-29 20:01:49
 REVIEW NOT COMPLETE. NOTES WILL FOLLOW.
2007-06-29 18:56:542007-06-29 18:56.54
 REVIEW IN PROGRESS
2007-06-29 07:32:262007-06-29 07:32:26
 RREMOVED FROM INCOMING, IN ELEC FOR REVIEW. WILL ROUTE
 BACK TO INCOMING ONCE REVIEW IS COMPLETE.