| 2007-07-25 19:22:34 | PROJECT: 300 PALM BEACH LAKES BLVD. |
| | |
| | PROJECT DESCRIPTION: CONDO CONVERSION/ ALTERATIONS |
| | |
| | REVIEW: 2004 FL. EXISTING BUILDING CODE W/ 2006 |
| | REVISIONS |
| | 2004 FL. BUILDING CODE W/ 2006 |
| | REVISIONS |
| | CITY OF WPB AMENDMENTS/2004 |
| | |
| | COMMENTS: |
| | |
| | A) PURSUANT TO THE FLORIDA STATUES, CHAPTER 471.003 |
| | QUALIFICATIONS FOR PRACTICE; EXEMPTIONS: THE FOLLOWING |
| | SHALL APPLY: |
| | |
| | |
| | (3)NOTWITHSTANDING THE PROVISIONS OF THIS CHAPTER OR |
| | OF ANY OTHER LAW, NO LICENSED ENGINEER WHOSE PRINCIPAL |
| | PRACTICE IS CIVIL OR STRUCTURAL ENGINEERING, OR |
| | EMPLOYEE OR SUBORDINATE UNDER THE RESPONSIBLE |
| | SUPERVISION OR CONTROL OF THE ENGINEER, IS PRECLUDED |
| | FROM PERFORMING ARCHITECTURAL SERVICES WHICH ARE PURELY |
| | INCIDENTAL TO HER OR HIS ENGINEERING PRACTICE, NOR IS |
| | ANY LICENSED ARCHITECT, OR EMPLOYEE OR SUBORDINATE |
| | UNDER THE RESPONSIBLE SUPERVISION OR CONTROL OF THE |
| | ARCHITECT, PRECLUDED FROM PERFORMING ENGINEERING |
| | SERVICES WHICH ARE PURELY INCIDENTAL TO HER OR HIS |
| | ARCHITECTURAL PRACTICE. HOWEVER, NO ENGINEER SHALL |
| | PRACTICE ARCHITECTURE OR USE THE DESIGNATION |
| | "ARCHITECT" OR ANY TERM DERIVED THEREFROM, AND NO |
| | ARCHITECT SHALL PRACTICE ENGINEERING OR USE THE |
| | DESIGNATION "ENGINEER" OR ANY TERM DERIVED THEREFROM. |
| | |
| | THEREFORE, A LICENSED ARCHITECT SHALL PREPARE THE |
| | ARCHITECTURAL PLANS SINCE THE DESIGNATED SCOPE OF WORK |
| | IS NOT INCIDENTAL TO THE STRUCTURAL SCOPE OF WORK. |
| | |
| | |
| | 1)PLEASE INDICATE LEVEL OF ALTERATION PURSUANT TO THE |
| | FEBC: |
| | |
| | 301.5 . A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION |
| | 303,304 & 305 OF THIS CODE. |
| | |
| | 2) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING |
| | DATA: |
| | |
| | A) BUILDING CONSTRUCTION TYPE |
| | B) OCCUPANCY LOAD: INCLUDING NEW DECK FOR ASSEMBLY |
| | OCCUPANCY. |
| | C) OCCUPANCY GROUP |
| | D) SPRINKLERED OR NON-SPRINKLERED. |
| | |
| | 3) NEW BALCONIES NOT SHOWN ON SCOPE OF WORK, SHT. A-0. |
| | |
| | 4) CHANGE CONSTRUCTION NOTES #1 TO REFLECT THE CURRENT |
| | BUILDING CODES. |
| | |
| | 5) INDICATETHE FIRE-RATED WALL PARTITIONS ON SHEETS |
| | A-6 THRU A-9. SHOW EXISTING DOOR FIRE RATINGS. |
| | |
| | 6) REQUIRE APPROVED FIRE-STOPPING DETAILS FOR |
| | FLOOR/CEILING/WALL PENETRATIONS: |
| | |
| | 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| | PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| | PENETRATED. |
| | |
| | 7) PLEASE SUBMIT A LIFE SAFETY PLAN. INDICATE TRAVEL |
| | DISTANCES, MEANS OF EGRESS, ETC. |
| | |
| | 8) THE PROPOSED CONSTRUCTION IS FOR A CONDO CONVERSION. |
| | THIS REPRESENTS A CHANGE OF OCCUPANCY CLASSIFICATION, |
| | SINCE THE EXISTING BUILDING WAS CLASSIFIED AS A R-2 |
| | (DORMITORY). THE OCCUPANCY CLASSIFICAITON FOR A |
| | CONDOMINIUM IS R-3. THE BUILDING SHALL MEET ALL OF THE |
| | REQUIREMENTS AS STATED WITHIN THE FLORIDA EXISTING |
| | BUILDING CODE: |
| | |
| | SECTION 812 |
| | CHANGE OF OCCUPANCY CLASSIFICATION |
| | 812.1COMPLIANCE WITH CHAPTER 7. |
| | THE OCCUPANCY CLASSIFICATION OF AN EXISTING BUILDING |
| | MAY BE CHANGED, PROVIDED THAT THE BUILDING MEETS ALL OF |
| | THE REQUIREMENTS OF CHAPTER 7 APPLIED THROUGHOUT THE |
| | BUILDING FOR THE NEW OCCUPANCY GROUP AND COMPLIES WITH |
| | THE REQUIREMENTS OF SECTIONS 802 THROUGH 812. |
| | |
| | 9) PLEASE INDICATE THE TYPE OF THE EXISTING ROOF |
| | SLAB/FLOOR SLABS. SHOW THICKNESS ANDTHE STRENGTH OF |
| | THE EXISTING CONCRETE. |
| | |
| | 10) PLEASE SUBMIT STRUCTURAL CALCULATIONS SHOWING THE |
| | ADDITONAL IMPOSED LOADS AND ALL OTHER APPLICABLE LOADS |
| | BY THE CONSTRUCTION OF THE ROOF RECREATIONAL DECK: |
| | |
| | 707.6ADDITIONAL LOADS. |
| | WHERE GRAVITY LOADING IS INCREASED ON THE ROOF OR FLOOR |
| | OF A BUILDING OR STRUCTURE, ALL STRUCTURAL MEMBERS |
| | AFFECTED BY SUCH INCREASE SHALL MEET THE GRAVITY LOAD |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | EXCEPTIONS: |
| | 1. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT INCREASED BY |
| | MORE THAN 5 PERCENT. |
| | 2. BUILDINGS OF GROUP R OCCUPANCY WITH NO MORE THAN |
| | FIVE DWELLING UNITS OR SLEEPING UNITS USED SOLELY FOR |
| | RESIDENTIAL PURPOSES THAT ARE ALTERED BASED ON THE |
| | CONVENTIONAL LIGHT-FRAME CONSTRUCTION METHODS AS |
| | DEFINED IN CHAPTER 2. |
| | |
| | 11)INDICATE CONSTRUCTION SPECIFICATIONS FOR THE |
| | JACUZZIS. SHOW LOAD CALCULATIONS. |
| | |
| | 12) MISSING BUILDING/FLOOR PLAN/BALCONY DIMENSIONS. |
| | |
| | 13) SUBMIT SHOP DRAWINGS FOR THE NEW BALCONY |
| | GUARDRAILING. |
| | |
| | 14) SHOW LOAD CALCULATIONS FOR NEW BALCONY SLABS. |
| | |
| | 15) SUBMIT SHOP DRAWINGS FOR THE PRE-FABRICATED METAL |
| | STAIRS SHOWN ON SHEET A-8. |
| | |
| | 16) SUBMIT SHOP DRAWINGS FOR PRE-FAB CONTINUOUS STUDDED |
| | METAL ANGLE. |
| | |
| | 17) PLEASE SHOW ALL APPLICABLE WORK/DETAILS INCIDENTAL |
| | TO ITEM #7/#8 ON SHEET A-0, UNDER |
| | SCOPE OF WORK. |
| | |
| | 18) SHOW THE TYPE OF EXISTING ROOF COVERING. THE ROOF |
| | COVERING SHALL BE MAINTAINED AS PER THE FOLLOWING |
| | SECTION: |
| | |
| | 1503.1 GENERAL. |
| | ROOF DECKS SHALL BE COVERED WITH APPROVED ROOF |
| | COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN |
| | ACCORDANCE |
| | WITH THE PROVISIONS OF THIS CHAPTER. ROOF COVERINGS |
| | SHALL BE DESIGNED, INSTALLED AND MAINTAINED IN |
| | ACCORDANCE WITH |
| | THIS CODE AND THE APPROVED MANUFACTURER?S INSTRUCTIONS |
| | SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT THE |
| | BUILDING OR STRUCTURE. |
| | |
| | PLEASE EXPLAIN HOW THE ROOF COVERING WILL BE MAINTAINED |
| | OR HOW A RE-ROOFING APPLICATION WOULD BE PERMITTED WITH |
| | THE |
| | WOOD DECK IN PLACE. |
| | |
| | 19) SHOW INTERIOR DEMOLITION IN THE SCOPE OF WORK AND |
| | ON FLOOR PLANS. |
| | |
| | 20) PLEASE BE ADVISED THAT THESE PLANS AND APPLICABLE |
| | INFORMATION ARE INCOMPLETE. THEREFORE, THIS REVIEWER |
| | COULD NOT PERFORM A COMPLETE BUILDING PLAN REVIEW.THE |
| | NOTED COMMENTS SHALL NOT BE CONSTRUED AS FINAL |
| | COMMENTS. PRIOR TO RE-SUBMITTING THESE PLANS, PLEASE |
| | ADDRESS AND REVIEW FOR COMPLETENESS. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |