| 2007-07-24 18:49:09 | |
| | DENIED |
| | |
| | 1)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| | PRACTICE UNDER CHAPTER 481 OR 471 OF |
| | THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS |
| | PER 106.1 FBC PLEASE SIGN AND SEAL WIND LOAD |
| | CALCULATIONS. |
| | |
| | 2)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS. PLEASE NOTE THAT WINDOW SCHEDULE ON A/10 |
| | STATE COMPLIANCE WITH 2001 FBC |
| | |
| | 3)PROVIDE WIND DESIGN DATA ON DRAWINGS PER |
| | 1603.1.4 FBC |
| | |
| | 4)THE PERMIT APPLICATION SHALL INCLUDE TWO |
| | COPIES OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA |
| | STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT |
| | LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES. ALL |
| | CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 5)THE CITY OF WEST PALM BEACH REQUIRES THE |
| | FLORIDA STATE PRODUCT APPROVAL COVER |
| | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| | SUBMITTED APPLICATIONS WILL BE DENIED |
| | |
| | 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | |
| | 7)REMOVE ALL NON RELATED PAGES FROM THE PERMIT SETS |
| | SUCH AS SITE PLAN AND ROOF PLANAND INDICATE THE SCOPE |
| | OF WORK (WINDOW REPLACEMENT) IN THE TITLE BLOCK NOT |
| | CONDO CONVERSION. |
| | |
| | 8)PROVIDE CURRENT PRODUCT APPROVALS FOR THE |
| | STOREFRONT ASSEMBLIES THAT WILL BE USED. |
| | |
| | 9)THE PRODUCT APPROVAL FOR THE OUTSWING FRENCH DOORS |
| | HAS EXPIRED PLEASE SUBMIT CURRENT APPROVAL. |
| | |
| | 10)ALL MIAMI-DADE NOA'S FOR WINDOW UNITS AND SLIDING |
| | GLASS DOORS HAVE BEEN REVISED. |
| | |
| | 11)PROVIDE AN UPDATED WINDOW SCHEDULE WITH CORRECT |
| | PRODUCT APPROVAL NUMBERS, WIND PRESSURES, GLAZING |
| | TYPES, ETC. |
| | |
| | 12)IF METAL DOORS ON THE DOOR SCHEDULE ARE BEING |
| | CHANGED PROVIDE PRODUCT APPROVALS IF NOT PROVIDE NOTE |
| | THAT EXISTING TO REMAIN. |
| | |
| | 13)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |