| Plan Review Notes For Permit 07060502 |
| Permit Number |
07060502 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-14 18:22:04 | DENIED | | | REFERENCE: FBC-2004 | | | CHAPTER 1 | | | CHAPTER 11 | | | | | | 1.SEE COMMENT #5 FROM THE BUILDING PLAN REVIEW AND | | | COMMENT #1 FROM THE ELECTRICAL PLAN REVIEW.IF THE | | | PLANS ARE TO BE REVIEWED BY ALL REVIEWERS THEN THE | | | FOLLOWING INFORMATION WILL BE REQUIRED TO BE SHOWN ON | | | THE PLANS. | | | | | | FOR THE TOILET ROOMS: | | | __FOR THE W.C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.19.6 DISPENSERS | | | | | | FOR THE LAVS: | | | A. 11-4.19.2 CLEARANCES | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | | | | A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1. | | | | | | BAR SINK SHALL SHOW COMPLIANCE WITH SECTION 11-4.24 | | | WITH ALL SUBSECTIONS. | | | | | | 2. THE FOLLOWING INFORMATION IS REQUIRED IN ANY CASE | | | FOR PLUMBING PERMIT: | | | | | | AN RPZV BACKFLOW IS REQUIRED PER SECTION 608.13.2. | | | | | | A SITE PLAN SHOWING THE SEWER LATERAL AND THE WATER | | | METER LOCATIONS. BACKFLOW SHALL BE AS CLOSE TO THE | | | METER BUT ON PRIVATE PROPERTY . | | | | | | SHOW THE WATER SERVICE AND THE SEWER LINES AND INDICATE | | | THEIR ROUTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|