| 2007-06-25 08:39:07 | BUILDING PLAN REVIEW |
| | PERMIT: 07060502 |
| | ADD: 2101 OKEECHOBEE BLVD |
| | CONT: PROENACK CORP. |
| | TEL: (561)691-2400 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)THE CALIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 3)THE WINDOW SCHEDULE UNIT 3 SHOWS WINDOW (A) AND |
| | (B), ARE THESE TWO WINDOWSBEING CHANGED TO IMPACT |
| | WINDOWS? IF SO, SUBMIT THE PRODUCT APPROVAL FOR WINDOW |
| | (A). DOOR SCHEDULE UNIT 2 HASTHE SAME PROBLEM, SO |
| | SUBMIT THE PRODUCT APPROVAL FOR THE EXTERIOR STEEL |
| | DOOR. |
| | |
| | 4)THE CONTRACTOR SHALL PRINT AND SIGN HIS/HER NAME ON |
| | THE PERMIT APPLICATION. ALL SIGNATURES MUST BE |
| | ORIGINAL. |
| | |
| | 5)THE DRAWINGS SUBMITTED ARE NOT ON THE STATE |
| | WEBSITE. THE STATE APPROVAL STAMP IS ALSO MISSING FROM |
| | THE PLANS. IF THESE PLANS WERE NOT APPROVED BY THE |
| | STATE, THEY WILL BE REVIEWED BY ALL THE TRADES OF THE |
| | BUILDING DEPARTMENT FOR CODE COMPLIANCE AND LIFESAFETY. |
| | THE PLANS ARE ALSO MISSING PAGES 3-5. |
| | |
| | 6)FL ENERGY EFFICIENCY CODE 400.ABCD.2 |
| | THE BUILDING'S OWNER, THE OWNER'S |
| | ARCHITECT, OR OTHER AUTHORIZED AGENT |
| | LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY TO THE BUILDING OFFICIAL THAT |
| | THE BUILDING IS IN COMPLIANCE WITH THE |
| | ENERGY EFFICIENTY CODE. |
| | |
| | 7)A COMPLETE EXTERIOR WALL DETAIL INDICATING ALL |
| | MATERIALS SHALL BE SUBMITTED. |
| | |
| | |
| | NOTE; THERE IS FLAG IN OUR COMPUTER SYSTEM REGUARDING |
| | THE FOUNDATION PERMIT AT THIS LOCATION WHICH WILL SOON |
| | BE EXPIRED, SHOW HOW THIS STRUCTURE WILL MEET THE |
| | REQUIRED FOUNDATION REQUIREMENTS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |