Plan Review Notes
Plan Review Notes For Permit 07060501
Permit Number 07060501
Review Stop ENG
Sequence Number 5
Notes
Date Text
2008-05-15 14:41:56PASSED, WITH FOLLOWING PROVISO:
 PLEASE MAKE SUREYOU CORRECT ITEM #1 & ITEM#3 OF
 MOCK-ROOS FOLLOWING LETTER
 RASIK CHOKSHI 805-6723
  
 MARTIN PILOTE, P.E.
 GLOBE ENGINEERING, INC.
 N. LAUDERDALE, FL
  
 HI MARTIN:
  
 THE FOLLOWING LETTER IS FROM OUR CONSULTANT MOCK-ROOS.
 THEY MADE SOME MINOR COMMENTS ON YOUR WATER QUALITY
 CALCULATIONS.THEREFORE, WE ASK YOU TO INCORPORATE
 THEIR ITEM #1 & ITEM # 3 STATED IN MOCK ROOS'S
 FOLLOWING LETTER FOR YOUR WATER CALCULATION PACKAGE AND
 YOUR DRAWINGS. HOWEVER, WE HAVE PROVISIONALLY APPROVED
 YOUR PLANS THAT YOU WILL CORRECT THE STORM WATER
 CALCULATIONS AND DRAWINGS SUGGESTED BY MOCK-ROOS AS
 SOON AS POSSIBLE.
 THANKS,
  
 RASIK
  
 MAY 6, 2008
 MR. EMERY FABIAN
 CITY OF WEST PALM BEACH
 ENGINEERING PROJECT COORDINATOR
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH, FL 33407
 REF. NO. W7700.16
 SUBJECT: FOREST POINT DRAINAGE REVIEW
 DEAR EMERY:
 WE HAVE COMPLETED OUR REVIEW OF THE PLANS AND
 CALCULATIONS PROVIDED FOR THE ABOVE REFERENCED
 PROJECT. OUR OBSERVATIONS ARE AS FOLLOWS:
 1. THE PROPOSED EXFILTRATION TRENCH DETAIL SPECIFIES
 ONLY 12 INCHES OF BACKFILL OVER THE TRENCH, RATHER
 THAN THE 18 INCHES THAT IS SPECIFIED BY THE SFWMD
 TYPICAL EXFILTRATION TRENCH DETAIL.
 2. NO GEOTECHNICAL REPORT WAS PROVIDED TO SUBSTANTIATE
 THE HYDRAULIC CONDUCTIVITY (K VALUE) OR THE
 GROUND WATER TABLE LEVEL. HOWEVER, THE K VALUE APPEARS
 TO BE CONSERVATIVE.
 3. THE CALCULATIONS INDICATE THAT THE PROPOSED SITE
 PROVIDES STORAGE FOR UP TO THE 10-YEAR/1-DAY
 RAINFALL EVENT. HOWEVER, THIS CALCULATION IS BASED ON
 AN EFFECTIVE HEAD VALUE OF 10.2? (INLET GRATE
 ELEVATION LESS THE GROUND WATER ELEVATION). IT IS MORE
 CONVENTIONALLY ACCEPTED THAT THIS VALUE
 SHOULD BE THE INLET GRATE ELEVATION LESS THE BOTTOM OF
 THE TRENCH, 16.25? ? 9.75 = 6.5?. USING THE
 LOWER VALUE, THE PROPOSED VOLUME OF THE TRENCH IS
 SUFFICIENT FOR THE 5-YEAR/1-HOUR, WHICH IS THE
 SFWMD CRITERION FOR PARKING AREAS, AND IT IS ALSO
 ENOUGH STORAGE VOLUME TO PROVIDE FOR THE
 RUNOFF FROM THE 5-YEAR/1-DAY; HOWEVER, IT IS NOT ENOUGH
 FOR THE 10-YEAR/1-DAY EVENT RUNOFF. ANY
 RUNOFF IN EXCESS OF THE 5-YEAR/1-DAY WILL LEAVE THE
 SITE. THE PLANS DO NOT INDICATE THE OFF-SITE FLOW
 PATTERN AND IT IS UNKNOWN IF THE DISCHARGE FLOWS TO THE
 CITY?S SYSTEM OR THAT OF FDOT.
 ALL THINGS CONSIDERED, THE PROPOSED DRAINAGE MEETS
 SFWMD WATER QUALITY CRITERIA, PROVIDES THE
 MINIMUM LEVEL OF PARKING PROTECTION AND WILL BE AN
 IMPROVEMENT OVER THE EXISTING CONDITIONS. WE
 RECOMMEND THAT THE CITY CONTINUE TO PROCESS THE
 PROPOSED SITE APPLICATION.
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT 683-3113,
 EXTENSION 231.
 SINCERELY,
 MOCK, ROOS & ASSOCIATES, INC.
 ALAN D. WERTEPNY, P.E.
 AC:JEH SENIOR PROJECT MANAGER