Plan Review Notes
Plan Review Notes For Permit 07060501
Permit Number 07060501
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2008-03-18 14:24:07*****DENIED*****
  
 THE FOLLOWINGS COMMENTS (NOT MARKED OK) TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.OK
  
 2.OK
  
 3.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY.
 AS PER WEST PALM BEACH CODE, THE ADDRESS NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.ADD TO PROJECT INFORMATION UNDER APPLICABLE
 CODES (COVER & TITLE SHEET)
  
 5.CONSTRUCTION, ALTERATION, AND DEMOLITION SHALL
 COMPLY WITH NFPA 241.ADD TO PROJECT INFORMATION UNDER
 APPLICABLE CODES (COVER & TITLE SHEET)
  
 6.OK
  
 7.MORE INFORMATION WILL BE REQUIRED TO ADDRESS
 CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF
 THIS SCOPE OF WORK.
  
 8.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATIFIY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 MIKE WENNERGREN,ASSISTANT FIRE MARSHAL
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 FIRE PLAN REVIEW
 FIRE PREVENTION 561-804-4756
 561-805-6722