Text |
| 2008-02-11 08:42:54 | ** DENIED** |
| | |
| | ** PLEASE SEE THE NOTES BELOW. IF ALL OTHER TRADES PASS |
| | THEIR REVIEWS PLEASE CONTACT THIS REVIEWER. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. PLEASE |
| | SEE FOR EXAMPLE INTERIOR FIXTURES ON PLANS CALL FOR |
| | 11-100 WATT FIXTURES, YET THE INPUT DATA REPORT SHOWS |
| | 9. |
| | PLEASE SEE THE CERTIFICATION SHEET PAGE #3 NEEDS TO |
| | CONTAIN THE SIGNATURE, DATE AND SEAL FROM THE ENGINEER |
| | MR. BUCHANAN. THE SEAL WAS PLACED ON COVER SHEET WHICH |
| | IS OK, HOWEVER THIS NEEDS TO BE ON THE CERTIFICATION |
| | SHEET AS STATED. |
| | 13-103.1.1.1, FAC 61G15-23.002, FS 471.025 |
| | PLEASE COMPLETE THE FIXTURE LEGENDS WITH THE TYPE OF |
| | FIXTURES WITH MORE DETAIL THAN ONLY STATING IT IS A |
| | 100W FIXTURE OR SIMPLY A 75 WATT FIXTURE. PLEASE BE |
| | SURE TO CORRELATE WITH THE IDR. |
| | |
| | 2) NOTE: PLEASE SUBMIT LIGHTING CONTROL DETAIL FOR THE |
| | OCCUPANCY SENSORS IN SPACE. COULD NOT LOCATE ANY RELAY |
| | DETAIL FOR POWER PACKS, WIRING METHODS ETC. WILL THESE |
| | BE LOW VOLTAGE TO POWER PACKS? WILL THESE BE 120V UNITS |
| | HARDWIRED? THIS IS THE SAME FOR THE TYPE OF DEVICE |
| | WHICH IS SHOWN IN SYMBOL LEGEND AS SM FOR WALL |
| | CONTROL. |
| | 13-415.1.ABC.1.1, .1.2 |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 3) NOTE: PLEASE SEE THE VA LOAD SHOWN ON PANEL SCHEDULE |
| | FOR HS-5 SHOWS 720 VA YET THE REVISED LOADS ON FIXTURES |
| | FOR OUTSIDE WALKWAYS ADDS UP TO A LOAD OF 900VA. |
| | IT IS VERY WELL THE SERVICE AND PANEL IS SIZED OK FOR |
| | LOAD, HOWEVER THIS NEEDS TO BE REVISED TO COORDINATE. |
| | NEC 220, |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | ** PLEASE KNOW SOME OF THE ABOVE ITEMS MAY BE ABLE TO |
| | BE SET UP AS A *PROVISO*, HOWEVER THERE ARE FEW ITEMS |
| | WHICH MUST BE ADDRESSED AT THIS TIME. IF*ALL *OTHER |
| | REVIEWS PASS REVIEWS, PLEASE CONTACT THIS REVIEWER TO |
| | GO OVER WHAT WILL BE NEEDED FOR PERMIT ISSUANCE AND |
| | OTHER ITEMS CAN BE PART OF A *PROVISO*. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER DIRECTLY AT THE INFORMATION |
| | PROVIDED BELOW. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |