Plan Review Notes
Plan Review Notes For Permit 07060501
Permit Number 07060501
Review Stop B
Sequence Number 3
Notes
Date Text
2008-03-19 11:29:56SHELL 7204 S DIXIE HWY/ 07060501
 BUILDING PLAN REVIEW
 PERMIT: 07060501
 ADD: 7204 S DIXIE HWY
 CONT: BENCHMARK CUSTOM BUILDERS
 TEL: (954)802-0723
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) ADDITIONAL INFORMATION REQUIRED. THE PERMIT
 APPLICATION INDICATES A SHELL BUILDING WHILE THE PLANS
 INDICATE THIS TO BE A PHASED, PHASE I A COMMERCIAL
 FIRST FLOOR AND A PHASE II RESIDENTIAL
 SECOND FLOOR, ARE BOTH PHASES TO BE CONSIDERED WORK
 UNDER THIS PERMIT?
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. NOTE PLANS DO INDICATE 2004 FBC BUT NOT THE
 2006 AMENDMENTS, PLEASE CORRECT.
  
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3. COMPLIED.
  
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. PARTIALLY COMPLIED. PLANS INDICATE A TYPE
 III BUILDING BUT NO DESIGNATION AS A OR B. NOTE: TABLE
 503WILL ALLOW THIS BUILDING TO BE BUILT AS A TYPE V-B
 EVEN FOR PHASE II, SEE SECTION 302.3.2 AND TABLE
 302.3.2. IF TO BE DESIGNED AS EITHER A TYPE III A OR B
 SEE TABLE 602 THAT WILL REQUIRE A 2HR RATED WALL FOR
 THE SOUTH WALL LOCATED 5.5' FROM THE PROPERTY LINE .
 PLEASE PROVIDE WHAT TYPE OF CONSTRUCTION THIS STRUCTURE
 WILL BE DESIGNED TOO.
  
 D) THE OCCUPANT LOAD, SEE 1004. NOTE WORST CASE
 SCENARIO WILL BE TAKEN 5863 SQ /30= 196 OCCUPANT LOAD
  
 E-K) COMPLIED.
  
 4) SHEET S-1 NOTE# 19 INDICATES THERE SHALL BE A
 SPECIAL INSPECTOR FOR THE REINFORCED MASONARY SHALL BE
 PROVIDED. ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL: 561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR,
 CONTRACTOR AND ENGINEER.
  
 5)COMPLIED.
  
 6) PROVISO 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 7) PROVISO:109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 8)BOTH C1 - C4 HAVE TOTALLY DELETEDTHEJOBSITE
 LOCATION INTHE TITLE BLOCK.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS ANDTELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 XX - STATE PROJECT NAME AND LOCATION,IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE ANDDATED SEAL-
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
 9)SEMI-COMPLIED SHEET A-2 INDICATES A MECHANICAL
 EQUIPMENT STANDBUT THE PRODUCT APPROVALS REQUIRED BY
 RULE 9B-72 DO NOT CONTAIN THE REPORT OR ASSCIATED
 TECHNICAL SHEETS.
  
 10) COMPLIED.
  
 11)2ND REQUEST,PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
 12)2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
  
 A) STOREFRONT- NO REPORT WAS SUBMITTED
  
 B) OUTSWING DOOR & TRANSOM - NO REPORT WAS SUBMITTED
  
 C) EXTERIOR METAL CORE DOOR
  
 D) PRE-ENGINEERED A/C STANDS- ONLY THE FLORIDA
 COVERSHEET SUBMITTED, NEEDS THE BACK UP REPORT AND
 TECNICAL DRAWINGS.
  
 E) GLASS BLOCK- REVIEWED OK
  
 F) TRUSS ANCHORS OR BUCKETS- NO REPORT SUBMITTED
  
 G) ROOFING ASSEMBLIES- NO REPORT SUBMITTED
  
 13) SHEET A-9 DETAIL# 5 INDICATES 2'X8' WOOD JOIST @
 2'-0" O. C. PLANS NOW INDICATE THE BUCKET TYPE BUT THE
 LENGHT OF THEEMBEDMENT OF THE 3/8" EXSPANSION BOLT IS
 NOT PROVIDED.
 106.1.2* ADITIONAL INFORMATION REQUIRED.
  
 14) 2ND REQUEST, SHEET A-1 STORAGE ROOM# 2THE DOOR ON
 THE RIGHT SIDE IS MISSING THE REQUIRED 18" SEE :
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 16)ARCHITECTURAL BUSINESS SOUTHEAST ARCHITECT
 SERVICES INC DOES NOT SHOW UP ON THE STATES DBPR
 WEBSITE USING THE FIRMS NAME NOR LICENSE NUMBER AA-C
 001953PLEASE PROVIDE CONFRAMATION OF THE FIRMS BUSINESS
 LICENSE. 481.219 F.S.CERTIFICATE OF AUTHORIZATION.
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 17) PROVISO: HOLLOW CORE SLAB PLANKS TO SUBMITT SHOP
 DRAWINGS REVIEWED BY THE DESIGN TEAM WITH APPROVAL
 STAMP.
  
 18-25) COMPLIED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]