Plan Review Notes
Plan Review Notes For Permit 07060501
Permit Number 07060501
Review Stop P
Sequence Number 2
Notes
Date Text
2007-11-03 10:33:20DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****SUBMITTED & REVIEWED AS SHELL ONLY WITH FUTURE 2ND
 FLOOR PIPING****
  
 ****FROM PREVIOUS REVIEW. COMMENT NUMBER SHALL BE THE
 SAME TO AVOID CONFUSION:
  
 1. SURVEY SHEET 1 OF 1 SHALL BE SIGNED, SEALED & DATED.
 SECTION 106.1.--THE LICENSE STATUS AS SHOWN ON THE
 FLORIDA STATE DBPR WEBSITE IS DELINQUENT. (SEE ATTACHED
 SHEET). PLEASE UPDATE STATUS PRIOR TO RESUBMITTING FOR
 REVIEW.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. ALL SHEETS WITH SOUTHEAST ARCHITECT SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 WEBSITE AND/OR THE TITLE BLOCK PRIOR TO RESUBMITTING
 FOR REVIEW.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. SHTS L-1 & L-2THE FIRM ADDRESS IS REQUIRED IN THE
 TITLE BLOCK PER FAC 61G1-16.004(1) & FS 481.2055.--
 THE ORIGINAL LEGAL SIGNATURE IS REQUIRED. IT APPEARS
 THAT INITIALS HAVE BEEN USED TO SIGN THE DOCUMENT.
 PLEASE SUBMIT A SIGNED, SEALED, DATED, NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(5) & FS 481.2055.--SHEETS
 SHALL BE SEALED PER SECTION 106.1.1 & 106.1.2. ****NO
 RESPONSE, NOT ADDRESSED. NOW SHT IR-1 ADDED AND THE
 SAME COMMENT APPLIES.
  
 4. PLANS SHALL INDICATE ALL CODES ADOPTED AND UNDER
 WHICH THE PLANS WERE DESIGNED. SECTION 106.1.1. ****NO
 RESPONSE, NOT ADDRESSED.
  
 5. PLEASE INDICATE THE PROPOSED OCCUPANCY OF THE
 BUILDING. 106.3.5.1.1(2).
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SHT A-2 SUBMIT CALCULATIONS FOR THE GUTTERS PER
 TABLE 1106.6 & DOWNSPOUTS PER TABLE 1106.2. SHOW THE
 TOTAL SQUARE FOOTAGE AREA OF THE ROOF AND SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS INCLUDED IN
 THE CALCULATIONS.--SHOW THE TOTAL SQUARE FOOT AREA
 BEING DRAINED BY EACH DOWNSPOUT.--INDICATE THE
 SLOPE OF EACH GUTTER AND INDICATE THE HIGH POINT OF THE
 GUTTER SLOPING TO THE DOWNSPOUTS.SECTIONS 106.1.1&
 106.1.2.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE SUBMITTED.
 THE SQUARE FOOTAGE BEING DRAINED BY EACH DOWNSPOUT CAN
 NOT BE DETERMINED UNTIL THE HIGH POINT IS ESTABLISHED.
 IT APPEARS THAT THE SQUARE FOOTAGE DRAINING INTO EACH
 DOWNSPOUT WILL BE DIFFERENT BECAUSE OF THE FACT THAT
 THE DOWNSPOUTS ARE NOT EVENLY SPACED THROUGH THE
 GUTTER.
  
 7. SHT A-2 INDICATE THE SLOPE OF THE MAIN ROOF. SECTION
 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. N/A
  
 9. SHT A-4 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON
 THE ROOF PLAN. NO DOWNSPOUTS SHOWN. PLEASE CORRELATE
 INFORMATION SHOWN ON THE ELEVATION AND THE ROOF PLAN.
 SHOW ALL DOWNSPOUTS. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. OK
 11. OK
  
 **********NEW COMMENTS**********
  
 1B. SHT P-3 THE RISER DIAGRAM FOR UNIT/BAY-1 NOW
 INDICATES A GREASE INTERCEPTOR. THIS DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1. THE GREASE INTERCEPTOR
 IS NOT APPROVED FOR INSIDE THE BUILDING AND SHALL BE
 LOCATED OUTSIDE THE BUILDING. ALSO A NOTE ON THE RISER
 DIAGRAM STATES "TERMINATE AND CAP ABOVE THE CEILING FOR
 FUTURE USE". WILL THERE BE A RESTAURANT ON THE SECOND
 FLOOR? PLEASE CLARIFY.
  
 2B. ALL GREASE INTERCEPTORS SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRE-TREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561)
 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS,
 (561) 822-2284, E-MAIL [email protected]. THERE FAX
 NUMBER IS (561) 822-2287. A WRITTEN DETERMINATION FROM
 ENVIRONMENTAL COMPLIANCE WILL BE SUBMITTED WITH THE
 PLANS WHEN RESUBMITTING FOR REVIEW OF BLDG PERMIT.
  
 3B. NO VENTING FOR THE FIRST FLOOR IS INDICATED ON THE
 SANITARY RISER DIAGRAMS. PLEASE INDICATE HOW THE TENANT
 BUILD-OUTS WILL BE VENTED. SECTION 901.2.1.
  
 4B. SHT P-3 RISERS 4 & 5 DO NOT REFLECT THE FLOOR PLAN.
 RISER 4 INDICATES AN OFFSET AT THE TOP OF THE STACK
 THAT IS NOT INDICATED ON THE FLOOR PLAN, AND ON RISER 5
 AN OFFSET IS REQUIRED TO REFLECT THE FLOOR PLAN. TO
 CLEAR UP THE CONFUSION INDICATE THE RISER NUMBERS ON
 THE FLOOR PLANS OF THE FIRST AND SECOND FLOORS SHTS P-1
 & P-2. RISERS START OFF RISER 1 ON THE LEFT AND
 CONTINUE TO RISER 5 ON THE RIGHT. PLEASE
 CLARIFY.SECTION 106.1.1.
  
 5B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED. BY NOT ADDRESSING THE
 COMMENTS WITH A WRITTEN RESPONSE, REVIEW TIME TAKES
 LONGER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved