| 2007-10-19 14:03:02 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: |
| | |
| | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). |
| | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR |
| | NOI. |
| | YOU CAN GET NOI INFO FROM |
| | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ |
| | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), |
| | EFFECTIVE MAY 1, 2003 |
| | 2. FIRST FLOOR ELEVATION=18', PLEASE SHOW IN YOUR WATER |
| | QUALITY CALS. THAT YOU CONSIDEREDCENTER LINE OF ROAD |
| | (CROWN OF THE ROAD), FLOOD ZONE AREA, & 5,10, 25, 100 |
| | YEAR FLOOD CRITERIATO DETERMINE THE FIRST FLOOR |
| | ELEVATION. FLOOR ELEVATION SHUOLD BE HIGHER THAN CROWN |
| | OF THE ROAD BY 1', PLEASE SHOW ALL THESE IN CALS & |
| | DRAWINGS. |
| | 3. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST |
| | MATCH WITH AREAS USED IN STORM WATER QUALITY |
| | CALCULATIONS. |
| | 4. ALSO PLEASE SHOW ALL STORM WATER CATCH BASINS |
| | NEAREST AROUND YOUR SITE. |
| | 5. PLEASE PROVIDE A COPY OF NPBID PERMIT, OR SFWMD |
| | PERMIT OR ENVOROMENTAL RESOURCE PERMIT , A COPY OF |
| | GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM |
| | WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH |
| | STREET. STORM WATER QUALITY CALS MUST BE APPROVED FROM |
| | 45TH STREET BEFORE WE ISSUE PERMIT. |
| | 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH |
| | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. |
| | |
| | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR |
| | PERMITTING PROCESS |
| | |
| | RASIK CHOKSHI805-6723 |