| 2007-10-24 14:48:57 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, |
| | WEST PALM BEACH, FLORIDA33401 |
| | TEL:561-805-6713FAX:561-805-6731 |
| | |
| | JAMES JOHNSTON, |
| | E-MAIL:JJOHNSTON @WPB.ORG |
| | BUILDING PLAN EXAMINER II |
| | |
| | PERMIT NO 07060501 |
| | ADDRESS7204 S. DIXIE HIGHWAY |
| | PROJECT FOREST POINT 1ST STORY |
| | |
| | DATE NOVEMBER 5, 2007 |
| | |
| | BUILDINGPLANREVIEWFLORIDA BUILDING CODES |
| | 2004 |
| | |
| | THE FOLOWING COMMENTS ADDRESS THE PREVIOUS |
| | CRITQUE COMPLETED ON 7/29/07 BY JIM WHITMER |
| | |
| | 1. COMPLIED |
| | |
| | 2. COMPLIED |
| | |
| | 3. COMPLIED |
| | |
| | 4. |
| | NOT IN COMPLIANCE2ND REQUEST |
| | |
| | FBCBUILDING 104.3 EXAMINATION |
| | OF DOCUMENTS |
| | 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL |
| | EXAMINE OR |
| | CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND |
| | THE |
| | ACCOMPANYING DOCUMENTS, CONSISTING OF DRAWINGS, |
| | SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL DATA, AND |
| | SHALL |
| | ASCERTAIN BY SUCH EXAMINATIONS WHETHER THE |
| | CONSTRUCTION |
| | INDICATED AND DESCRIBED IS IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF THE TECHNICAL CODES AND ALL OTHER |
| | PERTINENT |
| | LAWS OR ORDINANCES. |
| | |
| | COMMENT- PLEASE FURNISH THE THE FOLLOWING |
| | INFORMATION |
| | |
| | ON THE COVER SHEET |
| | PROJECT INFORMATION |
| | FBC2004 BUILDING W/ 2005 AND 6 REVISIONS |
| | FBC2004 ACCESSIBILITYCHAPTER 11 |
| | TYPE OF CONSTRUCTION |
| | SPRINKLED / UN-SPRINKLED |
| | BASIC WIND SPEED - MPH |
| | WIND EXPOSURE |
| | WIND IMPORTANCE FACTOR & BUILDING CATEGORY INTERNAL |
| | PRESSURE COEFFICIENT |
| | TYPE OF OCCUPANCY |
| | OCCUPANT LOAD-GROSS - NET |
| | 5 |
| | NOT IN COMPLIANCE2ND REQUEST |
| | |
| | FBC BUILDING1802.6 SOIL REPORTS. |
| | THE SOIL CLASSIFICATION AND DESIGN LOAD-BEARING |
| | CAPACITY |
| | SHALL BE SHOWN ON THE CONSTRUCTION DOCUMENT. |
| | WHERE REQUIRED BY THE BUILDING OFFICIAL, A WRITTEN |
| | REPORT |
| | OF THE INVESTIGATION SHALL BE SUBMITTED THAT INCLUDES, |
| | |
| | BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION: |
| | |
| | 1.A PLOT SHOWING THE LOCATION OF TEST BORINGS |
| | AND/OR |
| | EXCAVATIONS. |
| | 2. A COMPLETE RECORD OF THE SOIL SAMPLES. |
| | 3. A RECORD OF THE SOIL PROFILE. |
| | 4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. 5. |
| | RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN |
| | CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING |
| | CAPACITY |
| | OF NATURAL OR COMPACTED SOIL; PROVISIONS TO |
| | MITIGATE |
| | THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF |
| | THE EFFECTS |
| | OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT AND |
| | VARYING SOIL |
| | STRENGTH; AND THE EFFECTS OF ADJACENT LOADS. 6. |
| | EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. 7. PILE |
| | AND PIER FOUNDATION INFORMATION IN ACCORDANCE |
| | WITH SECTION 1808.2.2 . |
| | 8. SPECIAL DESIGN AND CONSTRUCTION PROVISIONS FOR |
| | FOOTINGS |
| | OR FOUNDATIONS FOUNDED ON EXPANSIVE SOILS, AS |
| | NECESSARY. |
| | |
| | COMMENT-PLEASE SUBMIT THE SOIL TEST REPORT FOR |
| | THIS |
| | PROJECT BY QUESTENGINEERING AS NOTED ON THE |
| | STRUCTURAL |
| | SHEETS-1. |
| | |
| | |
| | 6 |
| | COMPLIED |
| | |
| | |
| | 7 |
| | COMPLIED |
| | |
| | |
| | 8 |
| | COMPLIED |
| | |
| | |
| | 9 |
| | COMPLIED |
| | |
| | 10 |
| | COMPLIED |
| | |
| | 11 |
| | NOT IN COMPLIANCE2ND REQUEST |
| | |
| | PRODUCT APPROVALS REQUIRED |
| | FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 |
| | REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS |
| | SUBMIT TWO COPIES OF EACH APPROVAL |
| | ( 3 COPIES IF A THRESHOLD BUILDING ) WITH FLORIDA |
| | PRODUCT |
| | APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S |
| | SIGNATURE AS APPLICABLE, STATING |
| | ?TO THE BEST OF THEIR KNOWLEDGE THE PRODUCT APPROVAL |
| | COMPLIES WITH THE PLANS AND SPECIFICATIONS. |
| | |
| | COMMENT-IN ADDITION TO THE MIAMI-DADE NOA |
| | PLEASE PROVIDE FLORIDA PRODUCT APPROVALS FOR ALL |
| | PRODUCTS |
| | REQUIRED TO BE SUBMITTED.SEE INFORMATION SUBMITTED |
| | ABOVE. |
| | THE DELTA DOOR COMPANY DOES NOT HAVE FLORIDA PRODUCT |
| | APPROVAL. |
| | |
| | 11A |
| | FLORIDA ADMINISTRATIVE CODE9B-72.030 EXCEPTIONS. |
| | LOCAL PRODUCT APPROVAL GENERALLY |
| | PRODUCTS LISTED IN RULE 9B-72.005, F.A.C., SHALL BE |
| | APPROVED |
| | ACCORDING TO THE PROVISIONS OF THIS RULE. |
| | (1) PRESCRIPTIVE.PRODUCTS THAT HAVE PRESCRIPTIVE |
| | SPECIFICATION STANDARDS AND ARE MANUFACTURED UNDER |
| | QUALITY ASSURANCE PROCEDURES AS SPECIFIED IN THE CODE |
| | WILL BE DEEMED APPROVED. |
| | SUCH PRODUCTS SHALL INCLUDE BUT NOT BE LIMITED TO THE |
| | FOLLOWING: |
| | (A) STRUCTURAL COMPONENTS COVERED BY UNITED STATES |
| | DEPARTMENT OF COMMERCE PRODUCT STANDARDS; |
| | (B) STRUCTURAL COMPONENTS COMPRISED OF PRODUCTS THAT |
| | ARE ASSEMBLED OR PLACED IN THE FIELD AND ARE SUBJECT |
| | TO |
| | |
| | STANDARDIZED FIELD TESTING PROCEDURES CONTAINED WITHIN |
| | |
| | NATIONALLY RECOGNIZED STANDARDS ADOPTED WITHIN THE |
| | CODE |
| | |
| | MAY DEMONSTRATE COMPLIANCE BY A BATCH TICKET OR BILL |
| | OF |
| | LADING MADE AVAILABLE AT THE SITE OF ASSEMBLY OR |
| | PLACEMENT; |
| | (C) CUSTOM (ONE OF A KIND) PRE-ENGINEERED BUILDINGS. |
| | (2) PERFORMANCE. PRODUCTS, METHODS AND SYSTEMS OF |
| | CONSTRUCTION SPECIFICALLY ADDRESSED IN THE CODE |
| | THROUGH |
| | |
| | PERFORMANCE CRITERIA SHALL DEMONSTRATE COMPLIANCE |
| | PURSUANT TO RULE 9B-72.070, F.A.C., AND SHALL BE |
| | APPROVED |
| | PURSUANT TO RULE 9B-72.090, F.A.C. |
| | |
| | COMMENT-FOR DELTA DOOR |
| | |
| | |
| | 11B |
| | FLORIDA ADMINISTRATIVE CODE9B-72.050 |
| | PRODUCT APPROVAL BY LOCAL JURISDICTION |
| | AND ACCEPTANCE |
| | (1) APPROVAL OF A PRODUCT FOR LOCAL USE SHALL BE |
| | PERFORMED |
| | BY THE BUILDING CODE OFFICIAL OR HIS/HER DESIGNEE BY |
| | VERIFYING THAT THE PRODUCT COMPLIES WITH THE CODE IN |
| | ACCORDANCE WITH RULE 9B-72.040, F.A.C. |
| | (A) THE AUTHORITY HAVING JURISDICTION OR BUILDING |
| | OFFICIAL |
| | SHALL VALIDATE THE METHOD OF COMPLIANCE PURSUANT TO |
| | RULE 9B-72.040, F.A.C. |
| | (B) UPON ACCEPTANCE OF REQUIRED DOCUMENTATION PURSUANT |
| | TO SUBSECTION 9B-72.040(5), F.A.C., THE AUTHORITY |
| | HAVING JURISDICTION OR BUILDING OFFICIAL MAY |
| | |
| | DEEM THE PRODUCT APPROVED FOR USE IN ACCORDANCE WITH |
| | ITS APPROVAL AND LIMITATION OF USE. |
| | (C) APPROVAL SHALL BE VALID UNTIL SUCH TIME AS THE |
| | PRODUCT |
| | CHANGES DECREASING THE PRODUCT?S PERFORMANCE, |
| | THE STANDARDS OF THE CODE CHANGE, OR THE APPROVAL IS |
| | OTHERWISE SUSPENDED OR REVOKED. |
| | CHANGES TO THE CODE SHALL NOT BE CONSTRUED AS VOIDING |
| | THE APPROVAL OF PRODUCTS PREVIOUSLY INSTALLED IN |
| | EXISTING |
| | BUILDINGS PROVIDED SUCH PRODUCTS MET BUILDING CODE |
| | REQUIREMENTS AT THE TIME THE PRODUCT WAS INSTALLED. (D) |
| | MANUFACTURER SHALL NOTIFY THE AUTHORITY HAVING |
| | JURISDICTION OR THE BUILDING OFFICIAL WHEN THE QUALITY |
| | |
| | ASSURANCE REQUIREMENTS OF SUBSECTION 9B-72.040(4), |
| | F.A.C., |
| | ARE NO LONGER IN PLACE. |
| | (2) ACCEPTANCE OF A PRODUCT, MATERIAL OR SYSTEM OF |
| | CONSTRUCTION IS SPECIFIC TO A PROJECT AND REQUIRES |
| | APPROVAL BY A LOCAL JURISDICTION PURSUANT TO RULE |
| | 9B-72.050, F.A.C., OR STATEWIDE APPROVAL BY THE |
| | COMMISSION PURSUANT TO RULE 9B-72.090, F.A.C., |
| | AND VERIFICATION THAT THE PRODUCT IS BEING USED |
| | CONSISTENT WITH THE APPROVED EVALUATION AND |
| | LIMITATIONS |
| | |
| | OF USE ESTABLISHED BY THE APPROVED EVALUATION AS |
| | REQUIRED BY THE DESIGN SPECIFICATIONS. |
| | |
| | COMMENT-USE FLORIDA ADMINISTRATIVE CODES 9B-72.050 |
| | AND9B-72.030FOR DELTA DOOR CO. |
| | PLEASE FIND THE CITY OF WEST PALM BEACH |
| | ?SITE SPECIFIC? ?LOCAL PRODUCT APPROVAL? ATTACHED |
| | FORMS. |
| | SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT APPROVAL |
| | COVER PAGE FOR THE FOLLOWING |
| | COMPONENTS THAT ARE APPLICABLE |
| | FIXED GLASS |
| | MULLION TUBES |
| | STORE FRONT GLAZING SYSTEM |
| | ALUMINUM OUT -SWING DOORS |
| | EXTERIOR HOLLOW METAL DOORS |
| | EXTERIOR GLAZED DOORS |
| | ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION, |
| | UNDERLAYMENT,ROOF TILE,ROOF SYSTEM |
| | PREENGINEERED AC STAND |
| | GLASS BLOCK |
| | TRUSS ANCHORS |
| | |
| | |
| | 12 |
| | NOT IN COMPLIANCE2ND REQUEST |
| | |
| | FBCBUILDING 1609.1.3COMPONENTS & CLADDING ANCHORAGE |
| | AGAINST OVERTURNING, UPLIFT AND SLIDING. STRUCTURAL |
| | MEMBERS AND SYSTEMS AND COMPONENTS |
| | AND CLADDING IN A BUILDING OR STRUCTURE SHALL BE |
| | ANCHORED |
| | TO RESIST WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING |
| | AND |
| | TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO |
| | THE |
| | FOUNDATION. |
| | WHERE A PORTION OF THE RESISTANCE TO THESE FORCES IS |
| | PROVIDED BY DEAD LOAD, THE DEAD LOAD, INCLUDING THE |
| | WEIGHT |
| | OF SOILS AND FOUNDATIONS, SHALL BE TAKEN AS THE |
| | MINIMUM |
| | |
| | DEAD LOAD LIKELY TO BE IN PLACE DURING A DESIGN WIND |
| | EVENT. |
| | |
| | COMMENT |
| | SEE ITEM 11 |
| | |
| | |
| | |
| | |
| | FLORIDA ADMINISTRATIVE CODE61G15-23.002 SEAL, |
| | SIGNATURE AND DATE SHALL BE AFFIXED. |
| | (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND |
| | AFFIX |
| | HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, FINAL |
| | BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER?S |
| | REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR ISSUED |
| | BY SAID REGISTRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED AS |
| | PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, |
| | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS |
| | IMMEDIATELY |
| | |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. (2) |
| | EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED |
| | |
| | UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE |
| | SEALED, |
| | SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR |
| | NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF |
| | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING |
| | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME |
| | AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND |
| | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND |
| | LICENSE NUMBER OF THE ENGINEER, |
| | AND THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER OF THE ENGINEERING BUSINESS WILL SATISFY THIS |
| | REQUIREMENT. |
| | |
| | COMMENT-CARMAN VERDE AND ASSOCIATE?S LICENSE |
| | IS LISTED WITH THE DBPR AS ?DELINQUENT, ACTIVE. |
| | |
| | PLEASE SUBMIT THE CORRECT SURVEY FOR |
| | THIS PROJECT |
| | SHEET 1 OF 1 - BOUNDARY AND TOPOGRAPHIC SURVEY SHALL |
| | BE-SIGNED, SEALED, PRINTED NAME AND INCLUDE THE |
| | COMPANY CERTIFICATE OF AUTHORIZATION. |
| | |
| | |
| | |
| | |
| | 13 |
| | COMPLIED |
| | |
| | |
| | 14 |
| | COMPLIED |
| | |
| | 15 |
| | NOTED FOR COMPLIANCE |
| | THE FOLLOWING COMMENTS ARE THE RESULTS OF ADDITIONAL |
| | INFORMATION WHICH WAS REQUESTED |
| | BY THE PREVIOUS PLAN REVIEWER |
| | |
| | 16 |
| | ARCHITECTURAL |
| | FLORIDA ADMINISTRATIVE CODE61G1-16.002 |
| | ARCHITECTDESCRIPTION OF SEAL |
| | (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE |
| | ARCHITECT |
| | OR INTERIOR DESIGNER AND THE REGISTRATION NUMBER; THE |
| | SEAL OF THE ARCHITECT SHALL BE CIRCULAR, AND THE SEAL |
| | OF |
| | THE INTERIOR DESIGNER SHALL BE HEXAGONAL. |
| | BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL SEAL, |
| | APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR LINES |
| | BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE |
| | WORDS |
| | ?STATE OF FLORIDA? AND AT THE BOTTOM THE WORDS ? |
| | REGISTERED ARCHITECT? OR ?LICENSED INTERIOR DESIGNER,? |
| | |
| | WHICHEVER IS APPLICABLE. |
| | (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT |
| | AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH |
| | CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN |
| | REGISTRATION NUMBERS, IN SUCH A MANNER: |
| | |
| | COMMENT-SOUTHEAST ARCHITECT SERVICES, INC. PLEASE |
| | VERIFY YOUR SEAL IS IN COMPLIANCE WITH RULE |
| | 61G1-16.002 |
| | |
| | |
| | 17 |
| | FBC BUILDING 104.3 EXAMINATION OF DOCUMENTS 104.3.1 |
| | PLAN REVIEW. THE BUILDING OFFICIAL SHALL EXAMINE OR |
| | CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND |
| | THE ACCOMPANYING DOCUMENTS, CONSISTING OF DRAWINGS, |
| | SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL DATA, AND |
| | SHALL |
| | ASCERTAIN BY SUCH EXAMINATIONS WHETHER THE |
| | CONSTRUCTION |
| | INDICATED AND DESCRIBED IS IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF THE TECHNICAL CODES AND ALL OTHER |
| | PERTINENT |
| | LAWS OR ORDINANCES. |
| | |
| | COMMENT- PLEASE FURNISH THE HOLLOW CORE SLAB |
| | ENGINEERING DOCUMENTS. |
| | HAVE THE ARCHITECT OF RECORD NOTE ACCEPTANCE OF THIS |
| | PRODUCT |
| | |
| | |
| | |
| | CHAPTER11 ACCESSIBILITY |
| | |
| | 18 |
| | FBC BUILDING 11-4.3ACCESSIBLE ROUTE |
| | (1)AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY |
| | OF THE SITE SHALL BE PROVIDED FROM PUBLIC |
| | TRANSPORTATION |
| | STOPS, ACCESSIBLE PARKING, AND ACCESSIBLE PASSENGER |
| | LOADING ZONES, AND PUBLIC STREETS OR SIDEWALKS TO THE |
| | ACCESSIBLE BUILDING ENTRANCE THEY SERVE. |
| | THE ACCESSIBLE ROUTE SHALL, TO THE MAXIMUM EXTENT |
| | FEASIBLE, |
| | COINCIDE WITH THE ROUTE FOR THE GENERAL PUBLIC. (2) AT |
| | LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE |
| | BUILDINGS, FACILITIES, ELEMENTS, AND SPACES THAT ARE ON |
| | THE |
| | SAME SITE. |
| | (3)AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT |
| | ACCESSIBLE BUILDINGS OR FACILITY ENTRANCES WITH ALL |
| | ACCESSIBLE SPACES AND ELEMENTS AND WITH ALL ACCESSIBLE |
| | |
| | DWELLING UNITS WITHIN THE BUILDING OR FACILITY. (4) AND |
| | ACCESSIBLE ROUTE SHALL CONNECT AT LEAST ONE ACCESSIBLE |
| | ENTRANCE OF EACH ACCESSIBLE DWELLING UNIT. |
| | |
| | COMMENTDEFINETHE TRANSITION FROM THE BOUNDARY |
| | WALKWAY ACROSS THE DRIVEWAY ENTRANCES TO THE PUBLIC |
| | SIDEWALK WITHOUT A CHANGE IN ELEVATION |
| | |
| | |
| | 18 B |
| | FBC BUILDING 11-4.1.3 ACCESSIBLE BUILDINGS: |
| | NEW CONSTRUCTION |
| | (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| | SECTION |
| | 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR FACILITY |
| | ENTRANCES |
| | WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE |
| | BUILDING |
| | OR FACILITY. |
| | |
| | COMMENT THE SIDEWALK ALONG THE FRONT OF THE BUILDING |
| | DOES NOT CONTINUE TO THE SIDEWALK LOCATED AT THE |
| | NORTH. |
| | |
| | SHOW ALL CONNECTIONS FOR VERIFICATION OF ELEVATION. |
| | |
| | 19 |
| | FBC BUILDING 1816.1 TERMITE PROTECTION. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| | BAITING |
| | SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR OTHER |
| | APPROVED |
| | METHODS OF TERMITE PROTECTION LABELED FOR USE AS A |
| | PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. |
| | |
| | COMMENTFURNISH THIS INFORMATION ON SHEET S-1 |
| | OR WHERE APPLICABLE |
| | |
| | |
| | 20 |
| | FBC1905.1.1 CONCRETE STRENGTH. |
| | CONCRETE SHALL BE PROPORTIONED TO PROVIDE AN AVERAGE |
| | COMPRESSIVE STRENGTH AS PRESCRIBED IN SECTION 1905.3 , |
| | |
| | AND SHALL SATISFY THE DURABILITY CRITERIA OF SECTION |
| | 1904 . |
| | |
| | COMMENT- |
| | SHEET-SP-2 PROVIDE THE CONCRETE DESIGN MIX FOR THE |
| | DUMPSTER SLAB. |
| | SHEET - S-1 PROVIDE THE DESIGN MIX FOR THE SLAB. |
| | ?FOUNDATION NOTES? STATE THAT A SAFE BEARING CAPACITY |
| | IS |
| | 2,500 LBS.SPECIFY IF THIS IS THE INTENDED DESIGN |
| | MIX. |
| | |
| | |
| | |
| | 21 |
| | WPB ADMENDMENT106.1.1.2 FOR ROOF ASSEMBLIES REQUIRED |
| | BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL |
| | ILLUSTRATE, DESCRIBE, AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE INSTALLED. |
| | |
| | |
| | |
| | 21A |
| | FBC BUILDING 1507.10.1 SLOPE. |
| | BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF A MINIMUM |
| | OF ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR |
| | BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF A |
| | MINIMUM |
| | ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | |
| | COMMENT-DEFINE THE ROOF SLOPE FOR DRAINAGE ON SHEET |
| | A-2. |
| | INDICATE THE ROOF SURFACE ELEVATION AT THE EAST AND |
| | WEST. |
| | COORDINATE THE ARCHITECTURALWITH THE STRUCTURAL |
| | DETAILS |
| | REFERENCING THE TIE BEAM ELEVATION |
| | |
| | |
| | |
| | 22 |
| | FBC BUILDING 13-404.1.ABC.1 ROOF/CEILING THERMAL |
| | ENVELOPES. |
| | THE ROOF OR CEILING WHICH FUNCTIONS AS THE BUILDING?S |
| | THERMAL ENVELOPE SHALL BE INSULATED TO AN R -VALUE OF |
| | AT LEAST R-10. ROOF INSULATION SHALL NOT BE INSTALLED |
| | ON A |
| | SUSPENDED CEILING WITH REMOVABLE CEILING PANELS. |
| | |
| | COMMENT-ROOF INSULATION CANNOT BE USED IN THE |
| | SUSPENDED CEILING. |
| | PLEASE PROVIDE THE ROOF INSULATION MINIMUM OF R-10 AS |
| | NOTED FBC 13-404.1 ABOVE. |
| | |
| | |
| | 23 |
| | FBC BUILDINGTABLE 601 |
| | |
| | COMMENT-DEFINE FIRE RESISTANT RATING FOR STEEL TUBE |
| | COLUMNS |
| | |
| | |
| | 24 |
| | FBC BUILDING TABLE 2304.7(3) |
| | |
| | COMMENTS IDENTIFY STRUCTURAL PANEL SHEATHING BY ITS |
| | RATING AND THIS TABLE FOR USE ON THIS PROJECT |
| | |
| | |
| | 25 |
| | FBC BUILDING 2121.2.5.1 PARAPET WALLS. |
| | MASONRY PARAPET WALLS SHALL BE NOT LESS THAN 8 INCHES |
| | THICK, SHALL BE REINFORCED WITH MINIMUMTIE COLUMNS |
| | AND SHALL BE COPED WITH A CONCRETE BEAM NOT LESS THAN |
| | 64 SQUARE INCHES (.04 M 2 ) IN CROSS- SECTION, |
| | REINFORCED WITH TWO #4 REINFORCING BARS. |
| | |
| | COMMENTS- PROVIDE DETAILS FOR ANCHORING THE PARAPET |
| | WALL TO THE BUILDING STRUCTURE |