Plan Review Notes
Plan Review Notes For Permit 07060501
Permit Number 07060501
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-16 12:23:34DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****SUBMITTED & REVIEWED AS SHELL ONLY WITH FUTURE 2ND
 FLOOR PIPING****
  
 1. SURVEY SHEET 1 OF 1 SHALL BE SIGNED, SEALED & DATED.
 SECTION 106.1.--THE LICENSE STATUS AS SHOWN ON THE
 FLORIDA STATE DBPR WEBSITE IS DELINQUENT. (SEE ATTACHED
 SHEET). PLEASE UPDATE STATUS PRIOR TO RESUBMITTING FOR
 REVIEW.
  
 2. ALL SHEETS WITH SOUTHEAST ARCHITECT SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 WEBSITE AND/OR THE TITLE BLOCK PRIOR TO RESUBMITTING
 FOR REVIEW.
  
 3. SHTS L-1 & L-2THE FIRM ADDRESS IS REQUIRED IN THE
 TITLE BLOCK PER FAC 61G1-16.004(1) & FS 481.2055.--
 THE ORIGINAL LEGAL SIGNATURE IS REQUIRED. IT APPEARS
 THAT INITIALS HAVE BEEN USED TO SIGN THE DOCUMENT.
 PLEASE SUBMIT A SIGNED, SEALED, DATED, NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(5) & FS 481.2055.--SHEETS
 SHALL BE SEALED PER SECTION 106.1.1 & 106.1.2.
  
 4. PLANS SHALL INDICATE ALL CODES ADOPTED AND UNDER
 WHICH THE PLANS WERE DESIGNED. SECTION 106.1.1.
  
 5. PLEASE INDICATE THE PROPOSED OCCUPANCY OF THE
 BUILDING. 106.3.5.1.1(2).
  
 6. SHT A-2 SUBMIT CALCULATIONS FOR THE GUTTERS PER
 TABLE 1106.6 & DOWNSPOUTS PER TABLE 1106.2. SHOW THE
 TOTAL SQUARE FOOTAGE AREA OF THE ROOF AND SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS INCLUDED IN
 THE CALCULATIONS.--SHOW THE TOTAL SQUARE FOOT AREA
 BEING DRAINED BY EACH DOWNSPOUT.--INDICATE THE
 SLOPE OF EACH GUTTER AND INDICATE THE HIGH POINT OF THE
 GUTTER SLOPING TO THE DOWNSPOUTS.SECTIONS 106.1.1&
 106.1.2.
  
 7. SHT A-2 INDICATE THE SLOPE OF THE MAIN ROOF. SECTION
 106.1.1.
  
 8. SHT A-3 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON
 THE ROOF PLAN. PLEASE CORRELATE. SECTION 106.1.1.--
 NO DOWNSPOUTS ARE INDICATED ON THE ELEVATION. PLEASE
 SHOW THE LOCATION OF EACH DOWNSPOUT. SECTION 106.1.1.
 SHOW THE SIZE OF THE GUTTER AND THE DOWNSPOUTS. TABLES
 1106.6 & 1106.2.
  
 9. SHT A-4 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON
 THE ROOF PLAN. NO DOWNSPOUTS SHOWN. PLEASE CORRELATE
 INFORMATION SHOWN ON THE ELEVATION AND THE ROOF PLAN.
 SHOW ALL DOWNSPOUTS. SECTION 106.1.1.
  
 10. SHT P-3 THE SANT RISER TO UNIT #1 SHOWS 2" TO ONE
 LAV, BUT THE FLOOR PLAN SHOWS 3".--RISER TO UNIT
 #3 SHOWS 3" TO LAVS AND 3" TO ONE LAV BUT SHOWS 2" ON
 THE FLOOR PLANS. --RISER TO UNIT #4 SHOWS 2" TO THE
 W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS SHOWN
 ON THE FLOOR PLAN. - 3" IS SHOWN TO TWO LAVS BUT SHOWN
 AS 2" ON THE FLOOR PLAN.--RISER TO UNIT #5 SHOWS 2"
 TO THE W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELAT INFORMATION
 BETWEEN THE FLOOR PLAN AND THE RISER DIAGRAMS.
  
 11. SHT P-3 BAY 1 WATER RISER. PLEASE SHOW ALL PIPE
 SIZES.--BAY 2 WATER RISER IS SHOWN AS 1-1/4"
 METER/BACKFLOW BUT FLOOR PLAN SHOWS 2" METER/BACKFLOW.
 PLEASE CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND
 THE RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  