| 2007-07-16 12:23:34 | DENIED |
| | REFERENCE: FBC-2004 W/2006 AMENDMENTS |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****SUBMITTED & REVIEWED AS SHELL ONLY WITH FUTURE 2ND |
| | FLOOR PIPING**** |
| | |
| | 1. SURVEY SHEET 1 OF 1 SHALL BE SIGNED, SEALED & DATED. |
| | SECTION 106.1.--THE LICENSE STATUS AS SHOWN ON THE |
| | FLORIDA STATE DBPR WEBSITE IS DELINQUENT. (SEE ATTACHED |
| | SHEET). PLEASE UPDATE STATUS PRIOR TO RESUBMITTING FOR |
| | REVIEW. |
| | |
| | 2. ALL SHEETS WITH SOUTHEAST ARCHITECT SERVICES INC. |
| | TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT |
| | REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR |
| | WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE |
| | WEBSITE AND/OR THE TITLE BLOCK PRIOR TO RESUBMITTING |
| | FOR REVIEW. |
| | |
| | 3. SHTS L-1 & L-2THE FIRM ADDRESS IS REQUIRED IN THE |
| | TITLE BLOCK PER FAC 61G1-16.004(1) & FS 481.2055.-- |
| | THE ORIGINAL LEGAL SIGNATURE IS REQUIRED. IT APPEARS |
| | THAT INITIALS HAVE BEEN USED TO SIGN THE DOCUMENT. |
| | PLEASE SUBMIT A SIGNED, SEALED, DATED, NOTORIZED LETTER |
| | INDICATING YOUR LEGAL SIGNATURE FOR OUR FILES. FAC |
| | 61G1-16.003, 61G1-16.004(5) & FS 481.2055.--SHEETS |
| | SHALL BE SEALED PER SECTION 106.1.1 & 106.1.2. |
| | |
| | 4. PLANS SHALL INDICATE ALL CODES ADOPTED AND UNDER |
| | WHICH THE PLANS WERE DESIGNED. SECTION 106.1.1. |
| | |
| | 5. PLEASE INDICATE THE PROPOSED OCCUPANCY OF THE |
| | BUILDING. 106.3.5.1.1(2). |
| | |
| | 6. SHT A-2 SUBMIT CALCULATIONS FOR THE GUTTERS PER |
| | TABLE 1106.6 & DOWNSPOUTS PER TABLE 1106.2. SHOW THE |
| | TOTAL SQUARE FOOTAGE AREA OF THE ROOF AND SHOW 1/2 AREA |
| | OF ALL VERTICAL WALLS INCLUDING PARAPETS INCLUDED IN |
| | THE CALCULATIONS.--SHOW THE TOTAL SQUARE FOOT AREA |
| | BEING DRAINED BY EACH DOWNSPOUT.--INDICATE THE |
| | SLOPE OF EACH GUTTER AND INDICATE THE HIGH POINT OF THE |
| | GUTTER SLOPING TO THE DOWNSPOUTS.SECTIONS 106.1.1& |
| | 106.1.2. |
| | |
| | 7. SHT A-2 INDICATE THE SLOPE OF THE MAIN ROOF. SECTION |
| | 106.1.1. |
| | |
| | 8. SHT A-3 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON |
| | THE ROOF PLAN. PLEASE CORRELATE. SECTION 106.1.1.-- |
| | NO DOWNSPOUTS ARE INDICATED ON THE ELEVATION. PLEASE |
| | SHOW THE LOCATION OF EACH DOWNSPOUT. SECTION 106.1.1. |
| | SHOW THE SIZE OF THE GUTTER AND THE DOWNSPOUTS. TABLES |
| | 1106.6 & 1106.2. |
| | |
| | 9. SHT A-4 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON |
| | THE ROOF PLAN. NO DOWNSPOUTS SHOWN. PLEASE CORRELATE |
| | INFORMATION SHOWN ON THE ELEVATION AND THE ROOF PLAN. |
| | SHOW ALL DOWNSPOUTS. SECTION 106.1.1. |
| | |
| | 10. SHT P-3 THE SANT RISER TO UNIT #1 SHOWS 2" TO ONE |
| | LAV, BUT THE FLOOR PLAN SHOWS 3".--RISER TO UNIT |
| | #3 SHOWS 3" TO LAVS AND 3" TO ONE LAV BUT SHOWS 2" ON |
| | THE FLOOR PLANS. --RISER TO UNIT #4 SHOWS 2" TO THE |
| | W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS SHOWN |
| | ON THE FLOOR PLAN. - 3" IS SHOWN TO TWO LAVS BUT SHOWN |
| | AS 2" ON THE FLOOR PLAN.--RISER TO UNIT #5 SHOWS 2" |
| | TO THE W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS |
| | SHOWN ON THE FLOOR PLAN. PLEASE CORRELAT INFORMATION |
| | BETWEEN THE FLOOR PLAN AND THE RISER DIAGRAMS. |
| | |
| | 11. SHT P-3 BAY 1 WATER RISER. PLEASE SHOW ALL PIPE |
| | SIZES.--BAY 2 WATER RISER IS SHOWN AS 1-1/4" |
| | METER/BACKFLOW BUT FLOOR PLAN SHOWS 2" METER/BACKFLOW. |
| | PLEASE CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND |
| | THE RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |