2007-07-17 11:23:30--------------DENIED---------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO INFORMATION WAS PROVIDED REGARDING VENTILATION
 REQUIREMENTS. PLEASE PROVIDE OCCUPANCY CLASSIFICATION,
 OCCUPANT LOAD AND OUTDOOR AIR CALCULATIONS BASED ON
 FBC,M 403.3.
  
 2. NO INFORMATION WAS INCLUDED IN ENERGY CALCULATIONS
 FOR AIR CONDITIONING OR OTHER FEATURES OF THE SPACE.
 NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED. FBC 13-101.1.6
  
 3. PG A-1: NOTE #1 INDICATES R-30 INSULATION IS TO BE
 PROVIDED LATER ABOVE A FUTURE DROP CEILING. ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE PANELS PER FBC 13-404.1.ABC.1.
  
 4. PG A-1: NOTE #3 INDICATES R-5 INSULATION ON EXTERIOR
 MASONRY WALLS, BUT ENERGY CALCULATIONS SHOW R-12.5.
 PLEASE COORDINATE PLANS WITH INFORMATION USED IN THE
 INPUT DATA REPORT. FBC 13-403.2.AB
  
 5. PLEASE INCLUDE EXTERIOR DOOR INFORMAION ON ENERGY
 CALCULATIONS/ INPUT DATA REPORT. FBC 13-403.2.AB
  
 6. PG A-2 SUPPORT DETAIL: PRE-ENGINEERED A/C STANDS ARE
 STRUCTURAL COMPONENTS AS DEFINED IN FAC RULE 9B-72 AND
 AS SUCH ARE SUBJECT TO THE FLORIDA PRODUCT APPROVAL
 SYSTEM. PLEASE PROVIDE NOA WITH INSTALLATION DETAILS.
 ALSO, DRAWING REFERS TO A DETAIL ON PAGE M-2, BUT THERE
 IS NO PG M-2 PROVIDED. PLEASE CLARIFY. FBC 106.1.1
  
 7. M-1: OUTSIDE AIR OPENINGS IN THE EXTERIOR WALLS
 SHALL BE LOCATED A MINIMUM OF 10' FROM ANY HAZARDOUS
 CONTAMINANT SUCH AS STREETS, ALLEYS, PARKING LOTS AND
 LOADING DOCKS PER FBC,M 401.5.1.
  
 8. M-1: WALL LEGEND ON A-1 SHOWS EXTERIOR BLOCK WALLS
 TO BE 1-HOUR RATED. HOW ARE OUTDOOR AIR AND EXHAUST
 OPENINGS TO BE PROTECTED IN ACCORDANCE WITH FBC,M
 401.6?
  