| Plan Review Notes For Permit 07060501 |
| Permit Number |
07060501 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-31 15:55:22 | ***DENIED*** | | | | | | 1) BOUNDARY AND CIVIL DRAWINGS INDICATE NORTH DIXIE | | | HIGHWAY. PLEASE MAKE CORRECTION TO REFLECT SOUTH DIXIE | | | HIGHWAY. | | | | | | 2) IT APPEARS THAT BAY-2 ONLY HAS ONE (1) EXIT. PLEASE | | | VERIFY, AND IF SO DOES SPACE MEET REQUIREMENTS FOR | | | SINGLE EXIT? | | | | | | 3) ADDRESS IS REQUIRED ON BUILDING THAT MEETS THE | | | STANDARDS FOR THE CITY OF WEST PALM BEACH FOR | | | COMMERCIAL BUILDINGS. CITY CODE SEC. 78. | | | | | | 4) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 6) SHEET SP-1 ILLUSTRATES A RESTAURANT. MORE | | | INFORMATION WOULD BE REQUIRED SUCH AS PROPOSED | | | HOOD/SUPPRESSION EQUIPMENT, SEATING LAY OUT, OCCUPANT | | | LOAD ETC. | | | | | | 7) MORE INFORMATION WILL BE REQUIRED TO ADDRESS | | | CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF | | | THIS SCOPE OF WORK. | | | | | | 8) 2A-10B,C RATED FIRE EXTINGUISHERS REQUIRED TO MEET | | | MINIMUM 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|