Plan Review Notes
Plan Review Notes For Permit 07060501
Permit Number 07060501
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-01 11:57:01 
  
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004
 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE
 SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER
 AND NO COST TO CONTRACTOR.
 PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY
 THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE.
  
 3) NOTE:PLEASE SUBMIT ONLY COMPLETED SIGNED, DATED
 AND SEALED SETS COMPLETELY BOUND TOGETHER.
 PLEASE DO NOT SUBMIT COPIES OF PLANS.
 PLEASE DO NOT ATTACHED PRODUCT APPROVALS, ENERGY
 CALCULATIONS AND OTHER SUPPORTING DOCUMENTS ATTACHED
 DOWN THE LEFT HAND SIDE OF PLANS. PLEASE SUBMIT THESE
 IN FOLDERS/SPIRAL NOTE BOOKS OR SOME FASHION WHICH WILL
 BE SEPARATE FROM PLANS AND EACH SET.
 FBC 106.1
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ALL TRADES ARE
 TO BE COMPLETE WITH ALL INFORMATION AS REQUIRED PER FAC
 61G1-16.004, 61G15-23.002 AND FLORIDA STATUTES 481.219
 AND 471.023.
 PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR
 LANDSCAPE ARCHITECT.
 PLEASE SEE THE PLANS SUBMITTED FOR LANDSCAPE SHEETS ARE
 IN FACT PHOTO-COPIES IN ALL SETS OF WHAT SHOULD BE
 SIGNED, DATED AND SEALED PLANS.
 FS 481.221.
  
 5) NOTE: PLEASE SEE FBC 2004 W/2006 REVISION FOR
 COMPLIANCE WITH CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING
 CONTROLS WHICH ARE MISSING FROM PLANS AT THIS TIME.
 PLEASE SEE THE DEVICE AS NOTED ON PLANS DO NOT SHOW UP
 IN THE SYMBOL LEGEND, SO THE DEVICES CAN NOT BE
 VERIFIED AT THIS TIME.
 PLEASE SUBMIT ALL INFORMATION IF A SYSTEM IS INSTALLED.
 IF ONLY OS TYPE DEVICES, PLEASE COMPLETE THE
 INFORMATION ON THESE.
 PLEASE BE SURE TO DETAIL THE WIRING OF ALL EMERGENCY
 AND EXIT LIGHTS AHEAD OF THESE DEVICES.
 PLEASE SUBMIT ANY TIMED SCHEDULING.
 PLEASE SUBMIT TIME ON DEVICES AND/OR OVER RIDE DEVICES.
 PLEASE SEE THE SECTIONS GIVEN FOR THE MAXIMUM TIMES
 PERMITTED.
 PLEASE SUBMIT COMPLETED FIXTURE LEGENDS FOR ALL
 FIXTURES WHICH ARE TO CONTAIN ALL INFORMATION ON THESE
 FIXTURES AND WILL NEED TO CORRELATE WITH LIGHTING
 PERFORMANCE CALCULATIONS FOR COMMON AREAS.
 PLEASE SEE NUMBER OF LUMINARIES, THE TYPE OF
 LUMINARIES, THE CONTROL OF LUMINARIES AS STATED ON THE
 ENERGY CALCULATIONS DO NOT CORRELATE WITH THE PLANS AS
 SUBMITTED.
 PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS PLEASE KNOW WHEN THE ENERGY CALCULATIONS
 ARE CORRECTED AND SUBMITTED THE OWNER AGENT IS REQUIRED
 TO BE SIGNED ON EACH. 13-103.1.1.1
 PLEASE SEE THE SHEET 3 FOR CERTIFICATIONS FROM ALL
 DESIGNER(S) IS THE SHEET WHICH IS REQUIRED TO BE
 SIGNED, DATED AND SEALED.
 13-415.1.AB.1.1, 13-415.1.C, 13-415.2.
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.1 OF THE FBC CHAPTER
 13. PLEASE SUBMIT WORST CASE SCENARIO FOR VOLTAGE DROP
 ON FEEDERS AND BRANCH CIRCUITS.
  
 7) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 EGRESS PATHS FROM UNITS WHICH ARE BEING NOTED ON PLANS
 AS FUTURE DWELLING UNITS UPSTAIRS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 FOR STAIRS.
 PLEASE SUBMIT AND INDICATE LEVELS UNDER NORMAL AND
 EMERGENCY.
 PLEASE SEE THERE IS NOT LIGHTING SHOWNFOR STAIRS
 PLEASE SEE 700.12F, 700.16
  
 PLEASE SEE NOT #5 ABOVE WITH RESPECT TO THE TYPE OF
 FIXTURES AND THE FIXTURE LEGEND TO BE COMPLETED.
  
 8) NOTE: PLEASE SEE AS PLANS ARE INCOMPLETE FOR ANY
 NOTES ON FUTURE UPSTAIRS UNITS ETC, THE ADDITIONAL
 SERVICE AS SHOWN ON PLANS AND RISER AS FUTURE IS NOT
 GRANTED AT THIS TIME.
 PLEASE COMPLETE PLANS WITH THE FUTURE INFORMATION AND
 INFORMATION TO DETERMINE WHETHER OR NOT THE ADDITIONAL
 SERVICE AS SHOWN MAY BE GRANTED. AT THIS TIME THIS IS
 NOT PERMITTED AS SHOWN ON PLANS AND RISER.
 230.2, 230.70, 220, ETC.
  
 9) NOTE: PLEASE VERIFY IF A CT WILL BE ON RISER FOR THE
 LINE SIDE OF THE 800A MDP.
 FBC 106.3.5.1.2 (FPL REQUIRED?)
  
 10) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM NOTES
 *STRUCTURAL STEEL*WHICH IS OK AND REQUIRED IF PRESENT
 PER 250.50 HOWEVER PLEASE CLARIFY IF THIS IS MEANT TO
 BE THE *FOOTER STEEL* ?
  
 11) NOTE: PLEASE KNOW IF THERE IS ANY FIRE SPRINKLER OR
 FIRE ALARM PLANS WHICH MAY BE REQUIRED UNDER A SEPARATE
 PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE
 MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND
 .3(4).
 PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING
 REQUIRED INFORMATION.
  
 12) NOTE: PLEASE SUBMIT/INDICATE ALL OF THE REQUIRED
 AIC RATINGS FOR SERVICE EQUIPMENT/MAINS AND BRANCH
 BREAKERS.
 110.9.
 FBC 106.1.2, 106.3.5.1.2
  
 13) NOTE: PLEASE SUBMIT WIND LOAD ENGINEERING FOR SITE
 LIGHT POLES.PLEASE KNOW THESE WILL BE REVIEWED BY
 BUILDING REVIEWER AND WILL BE REQUIRED TO MEET THE FBC
 140MPH MIN FOR 3-SEC GUST, 120 SUSTAINED OR ABOVE. FBC
 106.1.2
  
  
  
 *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES
 REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH
 ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENT SON
 THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]