| 2007-07-01 11:57:01 | |
| | |
| | *** UNSAT *** |
| | |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC |
| | AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004 |
| | FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE |
| | SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL |
| | INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST |
| | ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER |
| | AND NO COST TO CONTRACTOR. |
| | PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY |
| | THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE. |
| | |
| | 3) NOTE:PLEASE SUBMIT ONLY COMPLETED SIGNED, DATED |
| | AND SEALED SETS COMPLETELY BOUND TOGETHER. |
| | PLEASE DO NOT SUBMIT COPIES OF PLANS. |
| | PLEASE DO NOT ATTACHED PRODUCT APPROVALS, ENERGY |
| | CALCULATIONS AND OTHER SUPPORTING DOCUMENTS ATTACHED |
| | DOWN THE LEFT HAND SIDE OF PLANS. PLEASE SUBMIT THESE |
| | IN FOLDERS/SPIRAL NOTE BOOKS OR SOME FASHION WHICH WILL |
| | BE SEPARATE FROM PLANS AND EACH SET. |
| | FBC 106.1 |
| | |
| | 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ALL TRADES ARE |
| | TO BE COMPLETE WITH ALL INFORMATION AS REQUIRED PER FAC |
| | 61G1-16.004, 61G15-23.002 AND FLORIDA STATUTES 481.219 |
| | AND 471.023. |
| | PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR |
| | LANDSCAPE ARCHITECT. |
| | PLEASE SEE THE PLANS SUBMITTED FOR LANDSCAPE SHEETS ARE |
| | IN FACT PHOTO-COPIES IN ALL SETS OF WHAT SHOULD BE |
| | SIGNED, DATED AND SEALED PLANS. |
| | FS 481.221. |
| | |
| | 5) NOTE: PLEASE SEE FBC 2004 W/2006 REVISION FOR |
| | COMPLIANCE WITH CHAPTER 13. PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING |
| | CONTROLS WHICH ARE MISSING FROM PLANS AT THIS TIME. |
| | PLEASE SEE THE DEVICE AS NOTED ON PLANS DO NOT SHOW UP |
| | IN THE SYMBOL LEGEND, SO THE DEVICES CAN NOT BE |
| | VERIFIED AT THIS TIME. |
| | PLEASE SUBMIT ALL INFORMATION IF A SYSTEM IS INSTALLED. |
| | IF ONLY OS TYPE DEVICES, PLEASE COMPLETE THE |
| | INFORMATION ON THESE. |
| | PLEASE BE SURE TO DETAIL THE WIRING OF ALL EMERGENCY |
| | AND EXIT LIGHTS AHEAD OF THESE DEVICES. |
| | PLEASE SUBMIT ANY TIMED SCHEDULING. |
| | PLEASE SUBMIT TIME ON DEVICES AND/OR OVER RIDE DEVICES. |
| | PLEASE SEE THE SECTIONS GIVEN FOR THE MAXIMUM TIMES |
| | PERMITTED. |
| | PLEASE SUBMIT COMPLETED FIXTURE LEGENDS FOR ALL |
| | FIXTURES WHICH ARE TO CONTAIN ALL INFORMATION ON THESE |
| | FIXTURES AND WILL NEED TO CORRELATE WITH LIGHTING |
| | PERFORMANCE CALCULATIONS FOR COMMON AREAS. |
| | PLEASE SEE NUMBER OF LUMINARIES, THE TYPE OF |
| | LUMINARIES, THE CONTROL OF LUMINARIES AS STATED ON THE |
| | ENERGY CALCULATIONS DO NOT CORRELATE WITH THE PLANS AS |
| | SUBMITTED. |
| | PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS PLEASE KNOW WHEN THE ENERGY CALCULATIONS |
| | ARE CORRECTED AND SUBMITTED THE OWNER AGENT IS REQUIRED |
| | TO BE SIGNED ON EACH. 13-103.1.1.1 |
| | PLEASE SEE THE SHEET 3 FOR CERTIFICATIONS FROM ALL |
| | DESIGNER(S) IS THE SHEET WHICH IS REQUIRED TO BE |
| | SIGNED, DATED AND SEALED. |
| | 13-415.1.AB.1.1, 13-415.1.C, 13-415.2. |
| | |
| | 6) NOTE: PLEASE SEE 13-413.1.ABC.1 OF THE FBC CHAPTER |
| | 13. PLEASE SUBMIT WORST CASE SCENARIO FOR VOLTAGE DROP |
| | ON FEEDERS AND BRANCH CIRCUITS. |
| | |
| | 7) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL |
| | EGRESS PATHS FROM UNITS WHICH ARE BEING NOTED ON PLANS |
| | AS FUTURE DWELLING UNITS UPSTAIRS. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 FOR STAIRS. |
| | PLEASE SUBMIT AND INDICATE LEVELS UNDER NORMAL AND |
| | EMERGENCY. |
| | PLEASE SEE THERE IS NOT LIGHTING SHOWNFOR STAIRS |
| | PLEASE SEE 700.12F, 700.16 |
| | |
| | PLEASE SEE NOT #5 ABOVE WITH RESPECT TO THE TYPE OF |
| | FIXTURES AND THE FIXTURE LEGEND TO BE COMPLETED. |
| | |
| | 8) NOTE: PLEASE SEE AS PLANS ARE INCOMPLETE FOR ANY |
| | NOTES ON FUTURE UPSTAIRS UNITS ETC, THE ADDITIONAL |
| | SERVICE AS SHOWN ON PLANS AND RISER AS FUTURE IS NOT |
| | GRANTED AT THIS TIME. |
| | PLEASE COMPLETE PLANS WITH THE FUTURE INFORMATION AND |
| | INFORMATION TO DETERMINE WHETHER OR NOT THE ADDITIONAL |
| | SERVICE AS SHOWN MAY BE GRANTED. AT THIS TIME THIS IS |
| | NOT PERMITTED AS SHOWN ON PLANS AND RISER. |
| | 230.2, 230.70, 220, ETC. |
| | |
| | 9) NOTE: PLEASE VERIFY IF A CT WILL BE ON RISER FOR THE |
| | LINE SIDE OF THE 800A MDP. |
| | FBC 106.3.5.1.2 (FPL REQUIRED?) |
| | |
| | 10) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM NOTES |
| | *STRUCTURAL STEEL*WHICH IS OK AND REQUIRED IF PRESENT |
| | PER 250.50 HOWEVER PLEASE CLARIFY IF THIS IS MEANT TO |
| | BE THE *FOOTER STEEL* ? |
| | |
| | 11) NOTE: PLEASE KNOW IF THERE IS ANY FIRE SPRINKLER OR |
| | FIRE ALARM PLANS WHICH MAY BE REQUIRED UNDER A SEPARATE |
| | PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE |
| | MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND |
| | .3(4). |
| | PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING |
| | REQUIRED INFORMATION. |
| | |
| | 12) NOTE: PLEASE SUBMIT/INDICATE ALL OF THE REQUIRED |
| | AIC RATINGS FOR SERVICE EQUIPMENT/MAINS AND BRANCH |
| | BREAKERS. |
| | 110.9. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 13) NOTE: PLEASE SUBMIT WIND LOAD ENGINEERING FOR SITE |
| | LIGHT POLES.PLEASE KNOW THESE WILL BE REVIEWED BY |
| | BUILDING REVIEWER AND WILL BE REQUIRED TO MEET THE FBC |
| | 140MPH MIN FOR 3-SEC GUST, 120 SUSTAINED OR ABOVE. FBC |
| | 106.1.2 |
| | |
| | |
| | |
| | *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES |
| | REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH |
| | ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENT SON |
| | THE FOLLOWING REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |