| 2007-07-29 22:08:12 | SHELL 7204 S DIXIE HWY/ 07060501 |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07060501 |
| | ADD: 7204 S DIXIE HWY |
| | CONT: BENCHMARK CUSTOM BUILDERS |
| | TEL: (954)802-0723 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) ADDITIONAL INFORMATION REQUIRED. THE PERMIT |
| | APPLICATION INDICATES A SHELL BUILDING WHILE THE PLANS |
| | INDICATE THIS TO BE A PHASED, PHASE I A COMMERCIAL |
| | FIRST FLOOR AND A PHASE II RESIDENTIAL |
| | SECOND FLOOR, ARE BOTH PHASES TO BE CONSIDERED WORK |
| | UNDER THIS PERMIT? |
| | |
| | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT |
| | H) NUMBER OF UNITS |
| | I) NUMBER OF FLOORS |
| | J) SQ. FT. LIV SPACE/ FL |
| | K) SQ. FT. FOOTPRINT |
| | |
| | 4) SHEET S-1 NOTE# 19 INDICATES THERE SHALL BE A |
| | SPECIAL INSPECTOR FOR THE REINFORCED MASONARY SHALL BE |
| | PROVIDED. ALSO, PLEASE ARRANGE WITH HAROLD PISKURA |
| | (INSPECTION SERVICES MANAGER - TEL: 561 805 6711), A |
| | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, |
| | CONTRACTOR AND ENGINEER. |
| | |
| | 5) FBC 1802.2.1 QUESTIONABLE SOILS, WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 6) ) 109.3.10* IMPACT OF CONSTRUCTION. |
| | ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERMORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS |
| | SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| | BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| | DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY |
| | SHALL NOT ADVERSELY IMPACT HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 7)109.3.10.1 HURRICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 8)BOTH C1 & C2 BOTH INDICATE THIS JOBSITE LOCATION TO |
| | BE ON NORTH DIXIE HWY, PLEASE CORRECT. |
| | |
| | 9)SHEET A-2 INDICATES A MECHANICAL EQUIPMENT STAND |
| | WITH A NOTE SEE M-2 FOR DETAIL, MISSING SHEET M-2. |
| | |
| | 10) SHEET A-2 ALSO INDICATES THE USE OF AN ATTACHED |
| | LADDER PLEASE PROVIDE MANUFACTURERS SPECS. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE |
| | STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 12)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | |
| | A) STOREFRONT- NOTE THE STOREFRONT REPORT NOA |
| | 04-0331.02 SECTION (3) CALCULATIONS HAS NOT BEEN |
| | VERIFIED UNDER THE 2004 FBC. THE ANCHOR CALCULATIONS |
| | WERE UNDER THE 2001 FBC WHEN FASTENERS WERE STILL |
| | TAKING THE 1 1/3 INCREASE PLEASE VERIFY THAT THE ANCHOR |
| | CALCULATION WILL COMPLY WITH THE 2004 FBC. 1606.3.1.1 |
| | LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR MORE LOADS IN |
| | COMBINATION WITH DEAD LOAD ARE INVESTIGATED IN LOAD |
| | COMBINATIONS OF 1605.3.1.1 THE COMBINED PLIED BY 0.75 |
| | PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS FROM THE LOAD |
| | COMBINATION OF THE DEAD LOAD PLUS THE LOAD PRODUCING |
| | THE LARGEST EFFECTS. INCREAS IN ALLOWABLE STRESS |
| | SPECIFIED IN THE MATERIALS SECTIONS OF THIS CODE OR A |
| | REFRENCED STANDARD SHALL NOT BE USED WITH THESE LOAD |
| | COMBINATIONS EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER 23. |
| | |
| | B) DH-350 ALUMINUM OUTSWING DOOR & TRANSOM REQUIRES |
| | FLORIDA COVER SHEET. |
| | |
| | C) EXTERIOR METAL CORE DOOR |
| | |
| | D) PRE-ENGINEERED A/C STANDS |
| | |
| | E) GLASS BLOCK |
| | |
| | F) TRUSS ANCHORS OR BUCKETS |
| | |
| | G) ROOFING ASSEMBLIES |
| | |
| | 13) SHEET A-9 DETAIL# 5 INDICATES 2'X8' WOOD JOIST @ |
| | 2'-0" O. C. BUT THERE IS NO INFORMATION HOW THEY WILL |
| | BE SECURED IN PLACE? |
| | 106.1.2* ADITIONAL INFORMATION REQUIRED. |
| | |
| | 14) SHEET A-2 STORAGE ROOM# 2THE DOOR ON THE RIGHT |
| | SIDE IS MISSING THE REQUIRED 18" SEE : |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 15)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |