| Date |
Text |
| 2007-09-16 11:20:43 | 2007-09-16 11:20:43 |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT AN ORIGINAL LETTER FROM AN |
| | OFFICER OF THE COMPANY WHICH WOULD BE FROM EXXON?S |
| | CORPORATE DIVISION WHICH STATES THE ENERGIZING, |
| | DE-ENERGIZING AND START UP OF THIS UNIT WILL ONLY BE |
| | PERFORMED BY QUALIFIED PERSONNEL. THE LETTER AS |
| | SUBMITTED FROM EXXON?S PROJECT MANAGER IS NOT AS NEEDED |
| | FROM THIS DEPARTMENT |
| | 702.6 EXCEPTION. |
| | THIS LETTER IS TO BE NOTARIZED AND ORIGINAL WHICH WILL |
| | BE PLACED IN FILE FOR ANY FUTURE REFERENCE. |
| | THIS LETTER NEEDED HAS BEEN CONFIRMED WITH THE |
| | BUILDING OFFICIAL AND ASSISTANT BUILDING OFFICIAL |
| | THROUGH CITY LAW DEPARTMENT. |
| | |
| | * KEYED INTERLOCKS WITH MULTIPLE KEYS AVAILABLE AND |
| | INSTALLED WILL NOT PREVENT INADVERTENT CONNECTION OF |
| | THE UTILITY AND EMERGENCY BACK UP SOURCE OF POWER AT |
| | THE SAME TIME* |
| | |
| | 2) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WHICH MAY |
| | BE FORTHCOMING FOR THE STRUCTURAL DESIGN OF FOOTING FOR |
| | THE NEW WALL. |
| | THIS IS OF CONCERN AS THE FOOTER FOR THE 9FT PLUS WALL |
| | IS BEING SHOWN AS 8 INCHES BY 8 INCHES AS A THICKENED |
| | EDGE SLAB. |
| | |
| | 3) NOTE: PLEASE SEE THE MAINS AND MEANS OF DISCONNECT |
| | FOR THE SERVICE AND GENERATOR ARE NOW BEING SHOWN |
| | INSIDE A BLOCK WALL ENCLOSURE. |
| | HOW WILL THE FIRE DEPARTMENT OR EMERGENCY PERSONNEL |
| | HAVE ACCESS TO THIS EQUIPMENT? |
| | PLEASE SEE 110.26 FOR THE CLEAR AND UNOBSTRUCTED PATH |
| | REQUIRED FOR THIS AREA. THE CLEARANCE IS BEING SHOWN AS |
| | 6FT TO THE WALL; PLEASE PROVIDE A MORE DETAILED LAYOUT |
| | FOR CLEAR SPACE, ACCESS, AND MEETING 110.26. |
| | THIS WILL BE FORWARDED TO THE FIRE MARSHAL ALSO. IT MAY |
| | BE A KNOX BOX WHICH WILL BE REQUIRED. |
| | 230.70, 230.71, 230.76, 230.79 ETC. |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |