| 2007-09-28 10:17:43 | BUILDING PLAN REVIEW |
| | PERMIT: 07060491 |
| | ADD: 1554 PBL BLVD. |
| | CONT: GREAT DANE PETROLEUM CONTRACTORS |
| | TEL: (954)792-1334 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE |
| | SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE |
| | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| | REQUIRES WITHOUT LOAD REDUCTION. SECOND, PROVIDE |
| | INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH, |
| | IF WIRE-MESH, FIBER MESHES OR IF STEEL REBAR WILL BE |
| | USED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | ***FBC 1805.2 FOOTINGS ARE REQUIRED TO EXTEND BELOW THE |
| | GROUND SURFACE A MINIMUM OF 12 INCHES.** |
| | |
| | 3)2004 FL. BLD CODE 1603.1.4 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE |
| | CONSTRUCTION DRAWINGS, |
| | 1) - BASIC WIND SPEED, MPH |
| | 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY |
| | 3) - WIND EXPOSURE |
| | 4) - INTERNAL PRESSURE COEFFICIENT, |
| | 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF. |
| | ***THE STRUCTURE AND GENERATOR WILL BE USED DURING |
| | EMERGENCY SITUATIONS. THEREFORE, THE STRUCTURE SHALL BE |
| | A CATEGORY IV WITH A WIND FACTOR OF 1.15. SEE FBC TABLE |
| | 1604.5. |
| | |