| 2007-06-28 16:28:49 | |
| | |
| | *** UNSAT *** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND |
| | ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A |
| | MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70(SHOWS A 2000 EDITION?) |
| | |
| | ** PLEASE SEE COMMENTS FROM FIRE AND OTHER TRADES FOR |
| | OTHER CODES REFERENCED. |
| | |
| | 2) NOTE: PLEASE SEE THE PERMIT APPLICATION AS SUBMITTED |
| | NEEDS TO CONTAIN THE SIGNATURES OF THE QUALIFIER OR |
| | AUTHORIZED AGENT FOR THE ELECTRICAL CONTRACTOR. PLEASE |
| | SEE THESE ALL APPEAR TO BE THE SAME SIGNATURE FROM THE |
| | SAME PERSON. |
| | PLEASE SEE THE NOTARY STATEMENT NEEDS TO BE FILLED OUT |
| | CORRECTLY. PLEASE SUBMIT SIGNATURE VERIFICATION LETTERS |
| | ORIGINAL AND NOTARIZED CORRECTLY UNDER FS 117.05. |
| | ** PLEASE KNOW THE PERMIT APPLICATION AS SUBMITTED WILL |
| | BE RETAINED BY THIS OFFICE. |
| | |
| | 3) NOTE: PLEASE SEE THE VALUE AS STATED ON APPLICATION |
| | IS EXTREMELY LOW. PLEASE KNOW THE VALUE IS REQUIRED TO |
| | BE FOR ALL LABOR, EQUIPMENT, CONSTRUCTION, MATERIALS, |
| | DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. FBC 108.3 |
| | ** PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE |
| | IF AN APPROPRIATE VALUE IS NOT ADJUSTED. |
| | |
| | 4) NOTE: PLEASE KNOW THE EXISTING MTS AS STATED ON |
| | PLANS MUST COMPLY WITH NEC 702.6. PLEASE KNOW THAT |
| | THERE IS KEYED INTERLOCK EQUIPMENT WHICH DOES NOT MEET |
| | THE NEC FOR INADVERTENT CONNECTION. |
| | PLEASE KNOW MANY OF THESE DEVICES CONTAIN MULTIPLE KEYS |
| | WHICH PERMIT THE DEVICES FROM BOTH POWER SOURCES BEING |
| | TURNED ON AT THE SAME TIME. |
| | PLEASE SUBMIT SPECS FOR EQUIPMENT TO BE SURE TO SUBMIT |
| | THE SPECS FOR THE MTS TO VERIFY THIS IS NOT EQUIPMENT |
| | AS STATED. |
| | |
| | 5) NOTE: PLEASE SEE RISER WHICH INDICATES ONLY ONE SET |
| | OF CONDUCTORS RATED FOR 310AMPS FROM THE GENERATOR WHEN |
| | THE BREAKER ON THE GENERATOR IS 600AMPS. |
| | PLEASE SEE 240.4, 310.16 AND 445.13 |
| | |
| | 6) NOTE: PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS |
| | NEED TO INDICATE THE OVER CURRENT PROTECTION OF THE |
| | BREAKER TO COORDINATION WITH THE RISER. PLEASE ALSO BE |
| | SURE THE SPECS/CUT SHEETS ALSO INDICATE THE MINIMUM |
| | CLEARANCES FOR THE GENERATOR UNIT FROM ALL EQUIPMENT, |
| | VENTS ETC. |
| | PLEASE SEE THIS UNIT BEING DIESEL WILL REQUIRED A |
| | MINIMUM OF 10FT FROM ANY OPENINGS INTO THE STRUCTURE. |
| | PLEASE SEE MECHANICAL REVIEW FOR THIS. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-28 15:25:02 | PLANS REMOVED FROM INCOMING AND IN ELEC FOR REVIEW. |
| | PLANS ROUTED BACK TO INCOMING ONCE REVIEW IS DONE. |