| 2007-07-11 19:01:12 | BUILDING PLAN REVIEW |
| | PERMIT: 07060491 |
| | ADD: 1554 PBL BLVD. |
| | CONT: GREAT DANE PETROLEUM CONTRACTORS |
| | TEL: (954)792-1334 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)GENERATOR SLAB & ANCHOR REQUIREMENT |
| | PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| | PLUS PROVIDE PLANS WITH THE INFORMATION |
| | DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE |
| | THE DEVICE REQUIRES WITHOUT LOAD |
| | REDUCTION. |
| | SECOND, PROVIDE INFORMATION ON THE |
| | SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| | WIREMESH, FIBER MESH OR IF STEEL REBAR |
| | WILL BE USED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 3)2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO |
| | INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | SITE WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST AND DESIGN FEES EXCLUDING LAND VALUE. OUR |
| | VALUATION REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND |
| | MEANS COST ANALYSIS SERVICES PER 108.3 FBC* |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |