Plan Review Notes
Plan Review Notes For Permit 07060486
Permit Number 07060486
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-14 12:52:16 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW COMMENT.
  
  
 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW.
 PLEASE BE SURE THE FOLLOWING CURRENT CODES ADOPTED BY
 THE STATE ARE ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE).
  
 2) NOTE:OWES FEES FOR VALUE BEING INCREASED BY
 CONTRACTOR.
 FBC 108.3
  
  
 3) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW. NO DETAILS FOR LISTED PENETRATIONS PROVIDED
 ALONG WITH CABLING INFORMATION.
 FBC
 PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE INSTALLED
 FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE METHOD OF
 INSTALLATION OF THESE CABLES.
 PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS
 MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC.
 PLEASE SEE CHAPTER 8 NEC.
  
 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
 PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE BASE
 BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER OF
 RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED BY
 THE BASE BUILDING DESIGNER OF RECORD.
 FS 471
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]