| Date |
Text |
| 2007-08-14 12:52:16 | |
| | *** DENIED 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW COMMENT. |
| | |
| | |
| | 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. |
| | PLEASE BE SURE THE FOLLOWING CURRENT CODES ADOPTED BY |
| | THE STATE ARE ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (IF APPLICABLE). |
| | |
| | 2) NOTE:OWES FEES FOR VALUE BEING INCREASED BY |
| | CONTRACTOR. |
| | FBC 108.3 |
| | |
| | |
| | 3) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| | REVIEW. NO DETAILS FOR LISTED PENETRATIONS PROVIDED |
| | ALONG WITH CABLING INFORMATION. |
| | FBC |
| | PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE INSTALLED |
| | FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE METHOD OF |
| | INSTALLATION OF THESE CABLES. |
| | PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS |
| | MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC. |
| | PLEASE SEE CHAPTER 8 NEC. |
| | |
| | 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| | REVIEW. |
| | PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE BASE |
| | BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER OF |
| | RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED BY |
| | THE BASE BUILDING DESIGNER OF RECORD. |
| | FS 471 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |