| 2007-06-25 08:03:37 | |
| | |
| | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CURRENT CODES |
| | ADOPTED BY THE STATE ARE ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (IF APPLICABLE). |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK |
| | SHALL INCLUDE: ALL LABOR, MATERIALS, EQUIPMENT, AND |
| | WIRING, DESIGN COST ETC. THIS IS EVEN IF ANY OF THESE |
| | ITEMS ARE OWNER SUPPLIED. PLEASE SEE THE VALUE AS |
| | STATED ON PERMIT APPLICATION IS EXTREMELY LOW. A VALUE |
| | MAY BE ASSESSED BY THIS OFFICE USING GUIDES ADOPTED |
| | INTO THE FBC 108.3 |
| | |
| | 3) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH |
| | ARE NOT SHOWN ON SYMBOL LEGEND AND DEVICES CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE |
| | INSTALLED FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE |
| | METHOD OF INSTALLATION OF THESE CABLES. |
| | PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS |
| | MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC. |
| | PLEASE SEE CHAPTER 8 NEC. |
| | |
| | 5) NOTE: PLEASE SEE THE CAMERA WHICH IS BEING SHOWN ON |
| | THE SEPARATE PROPERTY (ELEVATOR TOWER) IS NOT PERMITTED |
| | AS SYSTEMS CROSSING OVER THE PROPERTY LINE. |
| | |
| | 6) NOTE: PLEASE PROVIDE INFORMATION FOR ACCESS AND |
| | EGRESS CONTROLS AND FAIL-SAFE OPERATIONS SO THAT IN THE |
| | EVENT OF A POWER FAILURE EGRESS IN NOT IMPEDED IN ANY |
| | FASHION. |
| | PLEASE ALSOSEE NOTES FROM THE FIRE MARSHAL'S OFFICE |
| | WITH RESPECT TO LOCKING ARRANGEMENTS AND FURTHER |
| | DETAILS ON PLANS FOR CARD ACCESS, PUSH BUTTONEGRESS |
| | ETC WHICH WILL AFFECT THESE PLANS. |
| | PLEASE SEE NFPA-101CHAPTER 7:PLEASE SEE 7.2.1.5, |
| | 7.2.1.6., 7.2.1.9 ONLY TO MENTION A FEW. |
| | |
| | 7) NOTE: PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE |
| | BASE BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER |
| | OF RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED |
| | BY THE BASE BUILDING DESIGNER OF RECORD. |
| | FS 471 |
| | |
| | 8) NOTE: PLEASE SUBMIT THREE SETS OF COMPLETE PLANS AND |
| | SPECS AS THIS IS A THRESHOLD PROJECT. |
| | FBC106.1 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-25 07:05:21 | RECEIVED 6/22 |