Plan Review Notes
Plan Review Notes For Permit 07060486
Permit Number 07060486
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-25 08:03:37 
  
 *** UNSAT ***
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CURRENT CODES
 ADOPTED BY THE STATE ARE ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE).
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK
 SHALL INCLUDE: ALL LABOR, MATERIALS, EQUIPMENT, AND
 WIRING, DESIGN COST ETC. THIS IS EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. PLEASE SEE THE VALUE AS
 STATED ON PERMIT APPLICATION IS EXTREMELY LOW. A VALUE
 MAY BE ASSESSED BY THIS OFFICE USING GUIDES ADOPTED
 INTO THE FBC 108.3
  
 3) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH
 ARE NOT SHOWN ON SYMBOL LEGEND AND DEVICES CAN NOT BE
 REVIEWED AT THIS TIME.
 FBC 106.1.2
  
 4) NOTE: PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE
 INSTALLED FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE
 METHOD OF INSTALLATION OF THESE CABLES.
 PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS
 MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC.
 PLEASE SEE CHAPTER 8 NEC.
  
 5) NOTE: PLEASE SEE THE CAMERA WHICH IS BEING SHOWN ON
 THE SEPARATE PROPERTY (ELEVATOR TOWER) IS NOT PERMITTED
 AS SYSTEMS CROSSING OVER THE PROPERTY LINE.
  
 6) NOTE: PLEASE PROVIDE INFORMATION FOR ACCESS AND
 EGRESS CONTROLS AND FAIL-SAFE OPERATIONS SO THAT IN THE
 EVENT OF A POWER FAILURE EGRESS IN NOT IMPEDED IN ANY
 FASHION.
 PLEASE ALSOSEE NOTES FROM THE FIRE MARSHAL'S OFFICE
 WITH RESPECT TO LOCKING ARRANGEMENTS AND FURTHER
 DETAILS ON PLANS FOR CARD ACCESS, PUSH BUTTONEGRESS
 ETC WHICH WILL AFFECT THESE PLANS.
 PLEASE SEE NFPA-101CHAPTER 7:PLEASE SEE 7.2.1.5,
 7.2.1.6., 7.2.1.9 ONLY TO MENTION A FEW.
  
 7) NOTE: PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE
 BASE BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER
 OF RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED
 BY THE BASE BUILDING DESIGNER OF RECORD.
 FS 471
  
 8) NOTE: PLEASE SUBMIT THREE SETS OF COMPLETE PLANS AND
 SPECS AS THIS IS A THRESHOLD PROJECT.
 FBC106.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]