Plan Review Notes
Plan Review Notes For Permit 07060440
Permit Number 07060440
Review Stop B
Sequence Number 3
Notes
Date Text
2007-11-14 16:50:57BUILDING REVIEW THIRD CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2006 REVISIONS.
  
 1- TIFFIN METAL PRODUCT DRAWING NO 140480S4SE:
 A) ONLY ONE COPY WAS SUBMITTED. NEED TO PROVIDE TWO
 COPIES AS REQUIRED BY SEC. 106.1 CITY AMENDMENTS TO FBC
 2004.
  
 B) ENGINEER CAN'T USE A RUBBER STAMP SIGNATURE. NEED
 TO PROVIDE ORIGINAL SIGNATURE. IN ADDITION ENGINEER TO
 REVIEW SEC. 61G15-23.002(2)OF FLORIDA ADMINISTRATIVE
 CODE AND PROVIDE ALL HIS INFORMATION AS REQUIRED.
  
 2-DRAWINGS AND CALCULATIONS PERFORMED BY EFFECTIVE
 ENGINEERING SOLUTIONS, LTD:
 A) DRAWING 1 OF 1 NEEDS TO CLEARLY PROVIDE THE NAME
 OF THE ENGINEER SIGNING AND SEALING THE DRAWINGAS
 REQUIRED BY SEC. 61G15-23.002(2) OF FLORIDA
 ADMINISTRATIVE CODE.
  
 B) CALCULATIONS NEED TO PROVIDE THE NAME OF THE
 ENGINEER ON EACH SHEET AND SIGN AND SEAL EACH SHEET AS
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 C) SHEET 2 OF 28 OF ENGINEER CALCULATIONS NEED TO
 REVISE THE FLORIDA BUILDING CODE EDITION REFERENCED.
 CORRECT FLORIDA BUILDING CODE IS 2004, NOT 2003.
  
 3- PROVIDE 2 COPIES OF SURVEYS AND TWO COPIES OF
 LANDSCAPE PLANS AS REQUIRED BY SEC. 106.1 CITY
 AMENDMENTS TO FBC 2004. ONLY ONE COPY SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712