Plan Review Notes
Plan Review Notes For Permit 07060440
Permit Number 07060440
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-01 18:53:09BUILDING REVIEW CHECKLIST:
 1- NEED TO PROVIDE TWOSIGNED AND SEALED SETS OF
 PLANS. ONLY ONE SUBMITTED.
  
 2-A) NOTES ON RIGH HAND SIDE STATE THAT "THIS DESIGN
 COMPLIES WITH ASCE 7-01". THERE IS NOT ASCE 7 01.
 CORRECT ASCE 7 TO BE USED IS ASCE 7-02.
 REVISE INFORMATION AS REQUIRED.
  
 B) IMPORTANCE FACTOR OF I=.77 IS INCORRECT. SEE ASCE
 7-02 AND REVISE AS REQUIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 4- REVISE ALL PLANS AND SURVEY TO INCLUDE REVISED
 ADDRESS.CORRECT ADDRESS TO BE USED FOR THIS PROJECT
 IS 2203 MERCER AVE AS REVISED BY OUR ADDRESSING
 DEPARTMENT.
  
 5- UPDATE OWNER INFORMATION WITH PERMITCLERK. PROVIDE
 REQUIRED PROOF OF OWNERSHIP.
  
 6- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. 1802.2
 FBC 2004 AND NOTES ON ENGINEERED DRAWINGS.
  
 7-A) ENGINEERED DRAWINGS TO PROVIDE COMPLETE ENGINEER
 INFORMATION AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE. READ THIS SECTION AND PROVIDE ALL
 REQUIRED INFORMATION TO AVOID FUTURE DENIALS.
 B) ENGINEERED DRAWINGS TO PROVIDE THE ENGINEERING
 FIRM CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY
 SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 8- ENGINEERED DRAWINGS ONLY SHOW THE SIGN FRAMEWORK.
 DRAWINGS ARE MISSING:
 A) COMPLETE SPECS INCLUDING ATTACHMENT OF SIGN
 ITSELF TO SHOW COMPLIANCE WITH WIND LOADS OF ASCE
 7-02.
  
  
 B) GUARDRAIL ATTACHMENT TO SHOW COMPLIANCE WITH SEC.
 1607.7 FBC 2004.
  
 C) PLANS TO SHOW LOCATION OF GUARDRAILS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712