| 2007-08-01 18:53:09 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED TO PROVIDE TWOSIGNED AND SEALED SETS OF |
| | PLANS. ONLY ONE SUBMITTED. |
| | |
| | 2-A) NOTES ON RIGH HAND SIDE STATE THAT "THIS DESIGN |
| | COMPLIES WITH ASCE 7-01". THERE IS NOT ASCE 7 01. |
| | CORRECT ASCE 7 TO BE USED IS ASCE 7-02. |
| | REVISE INFORMATION AS REQUIRED. |
| | |
| | B) IMPORTANCE FACTOR OF I=.77 IS INCORRECT. SEE ASCE |
| | 7-02 AND REVISE AS REQUIRED. |
| | |
| | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 4- REVISE ALL PLANS AND SURVEY TO INCLUDE REVISED |
| | ADDRESS.CORRECT ADDRESS TO BE USED FOR THIS PROJECT |
| | IS 2203 MERCER AVE AS REVISED BY OUR ADDRESSING |
| | DEPARTMENT. |
| | |
| | 5- UPDATE OWNER INFORMATION WITH PERMITCLERK. PROVIDE |
| | REQUIRED PROOF OF OWNERSHIP. |
| | |
| | 6- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. 1802.2 |
| | FBC 2004 AND NOTES ON ENGINEERED DRAWINGS. |
| | |
| | 7-A) ENGINEERED DRAWINGS TO PROVIDE COMPLETE ENGINEER |
| | INFORMATION AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA |
| | ADMINISTRATIVE CODE. READ THIS SECTION AND PROVIDE ALL |
| | REQUIRED INFORMATION TO AVOID FUTURE DENIALS. |
| | B) ENGINEERED DRAWINGS TO PROVIDE THE ENGINEERING |
| | FIRM CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY |
| | SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 8- ENGINEERED DRAWINGS ONLY SHOW THE SIGN FRAMEWORK. |
| | DRAWINGS ARE MISSING: |
| | A) COMPLETE SPECS INCLUDING ATTACHMENT OF SIGN |
| | ITSELF TO SHOW COMPLIANCE WITH WIND LOADS OF ASCE |
| | 7-02. |
| | |
| | |
| | B) GUARDRAIL ATTACHMENT TO SHOW COMPLIANCE WITH SEC. |
| | 1607.7 FBC 2004. |
| | |
| | C) PLANS TO SHOW LOCATION OF GUARDRAILS. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |