Plan Review Notes
Plan Review Notes For Permit 07060415
Permit Number 07060415
Review Stop Z
Sequence Number 3
Notes
Date Text
2008-08-27 10:31:23PLANNING AND ZONING: **** PASSED WITH PROVISO ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO THE IBIS RESIDENTIAL PLANNED DEVELOPMENT
 (RPD) REGULATIONS, THE REQUIRED SIDE SETBACK FOR A ZERO
 LOT LINE (ZLL) RESIDENCE IS EIGHT (8) FEET; AND
 PURSUANT TO THE ZONING CODE, SECTION 94-305(B)(4),
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR (4)
 FEET INTO A SETBACK.
  
 THEREFORE, THE GENERATOR?S EDGE SHALL BE A MINIMUM OF
 FOUR (4) FEET FROM THE SIDE PROPERTY LINE.THE PLANS
 SHOW THE GENERATOR AT 42 INCHES FROM THE PROPERTY LINE,
 WHICH IS NOT COMPLYING.IF YOU RESUBMIT FOR OTHER
 FAILED DISCIPLINES, REVISE DRAWINGS ACCORDINGLY TO MEET
 THE REQUIREMENTS.OTHERWISE, ASSURE AT INSTALLATION
 THAT THE LOCATION OF THE GENERATOR WILL MEET SIDE
 SETBACK/INCLUDING ENCROACHMENT REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]