2008-08-27 13:26:25 
  
  
 PROVISO
  
 NFPA-37-4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND
 THEIR WEATHERPROOF HOUSINGS IF PROVIDED, THAT ARE
 INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 1.5 M (5
 FT) FROM OPENINGS IN WALLS AND AT LEAST 1.5 M (5 FT)
 FROM STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 SEPARATION SHALL NOT BE REQUIRED WHERE THE FOLLOWING
 CONDITIONS EXIST:
 (1) THE ADJACENT WALL OF THE STRUCTURE HAS A FIRE
 RESISTANCE RATING OF AT LEAST 1 HOUR.
 (2) THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  