| Plan Review Notes For Permit 07060415 |
| Permit Number |
07060415 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-08-27 13:26:25 | | | | | | | | | | PROVISO | | | | | | NFPA-37-4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND | | | THEIR WEATHERPROOF HOUSINGS IF PROVIDED, THAT ARE | | | INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 1.5 M (5 | | | FT) FROM OPENINGS IN WALLS AND AT LEAST 1.5 M (5 FT) | | | FROM STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM | | | SEPARATION SHALL NOT BE REQUIRED WHERE THE FOLLOWING | | | CONDITIONS EXIST: | | | (1) THE ADJACENT WALL OF THE STRUCTURE HAS A FIRE | | | RESISTANCE RATING OF AT LEAST 1 HOUR. | | | (2) THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NONCOMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED | | | THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE | | | COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|