| Plan Review Notes For Permit 07060415 |
| Permit Number |
07060415 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-15 13:37:50 | ***FAILED*** | | | | | | | | | 1)PLEASE INCLUDE MORE LEGIBLE SETBACK DIMENSIONS TO | | | PROPERTY LINES ON THE SURVEYS.NOTE:GENERATOR MUST | | | BE A MINIMUM OF 3.5' FROM SIDE PROPERTY LINE,AS PER | | | THE CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT | | | REGULATIONS, SECTION 94-305(B)(4) : | | | | | | (4)MECHANICAL EQUIPMENT.MECHANICAL EQUIPMENT MAY | | | NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK... | | | | | | (THE REQUIRED SIDE SETBACK FOR THE RESIDENCE IS 7.5' | | | ... THEREFORE YOU MAY ENCROACH 4' INTO THAT ... LEAVING | | | YOU WITH A SIDE SETBACK OF 3.5' TO THE GENERATOR'S | | | EDGE. | | | | | | | | | CHRIS HOOPS | | | ZONING TECHNICIAN | | | 561-805-6720 |
|