| 2007-07-26 17:05:41 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH |
| | FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS, |
| | AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE |
| | SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING, |
| | UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS |
| | FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF |
| | THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD |
| | LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE |
| | DURING A DESIGN WIND EVENT SHALL BE USED.THE |
| | ENGINEER'S CALCULATIONS STATES "SEE ATTACYHED MOUNTING |
| | DETAILS . . . " BUT NOTHING WAS ATTACHED. |
| | |
| | 2.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED |
| | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS FS471.025. |
| | |
| | 3.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS TO |
| | BE ON EACH SHEET. |
| | |
| | 4.)CALCULATIONS ARE TO BE SIGNED, SEALED AND DATED ON |
| | EACH SHEET UNLESS AN INDEX SHEET (IN COMPLIANCE WITH |
| | FAC61G15-23) IS USED, FAC61G15-23.002. |
| | |