| 2007-11-17 13:51:36 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. ENERGY CALCULATIONS: |
| | A) PROJECT SUMMARY STATES THIS IS A NEW FINISHED |
| | BUILDING, BUT PLANS INDICATES THIS IS A SHELL BUILDING. |
| | PLEASE COORDINATE PLANS AND CALCULATIONS. |
| | B) ENERGY CALCULATIONS ARE TO BE CERTIFIED BY THE |
| | OWNER, PROJECT ARCHITECT (REGISTERED IN THE STATE OF |
| | FLORIDA), OR OTHER OFFICIALLY DESIGNATED AGENT ALLOWED |
| | IN SECTION 103.2 IN ACCORDANCE WITH FBC 13-103.1 |
| | C)MANUAL J INCLUDED WITH ENERGY CALCULATIONS INDICATE |
| | BARE CONCRETE BLOCK WALLS WITH INSULATION VALUE OF |
| | R-11. WHAT IS THE BASIS FOR THIS VALUE? MANUAL J ALSO |
| | INDICATES A METAL DECK ROOF WITH 3 INCHES OF INSULATION |
| | WITH A VALUE OF R-19. WHAT IS THE BASIS FOR THIS |
| | VALUE? |
| | D) THE VALUES USED IN THE MANUAL J AND THE ENERGY |
| | CALCULATIONS SHALL BE SHOWN ON PLANS, IN SUFFICIENT |
| | DETAIL, INCLUDING ALL PERTINENT DATA AND FEATURES OF |
| | THE BUILDING AND THE EQUIPMENT AND SYSTEMS AS HEREIN |
| | GOVERNED INCLUDING, BUT NOT LIMITED TO: DESIGN |
| | CRITERIA, EXTERIOR ENVELOPE COMPONENT MATERIALS, |
| | U-VALUES OF THE ENVELOPE SYSTEMS, R-VALUES OF |
| | INSULATING MATERIALS, SIZE AND TYPE OF APPARATUS AND |
| | EQUIPMENT, EQUIPMENT AND SYSTEMS CONTROLS AND OTHER |
| | PERTINENT DATA TO INDICATE CONFORMANCE WITH THE |
| | REQUIREMENTS OF THIS CODE. FBC 13-103.2 |
| | |
| | 2. SEE PLUMBING CODE FOR MINIMUM FACILITIES REQUIRED. |
| | |
| | 3. MANUAL J SHOWS 300 CFM OF VENTILATION AIR FOR EACH |
| | SYSTEM. WHAT IS THE BASIS FOR THIS NUMBER? PREVIOUS |
| | REVIEW REQUESTED OUTSIDE AIR CALCULATIONS BASED ON |
| | FBC,M TABLE 403.3. NONE WERE PROVIDED. OUTSIDE AIR |
| | CALCULATIONS SHALL BE BASED ON OCCUPANCY |
| | CLASSIFICATION, OCCUPANT LOAD AND CFM/PERSON AS |
| | REQUIRED BY TABLE 403.3. SHOE THE MINIMUM REQUIRED |
| | OUTSIDE AIR RATE FOR THIS SPACE AND SHOW CORRELATION |
| | WITH MANUAL J FOR PROPER SYSTEM SIZING. |
| | |
| | NEW COMMENT: WALL LOUVERS HAVE BEEN ADDED TO THE |
| | DRAWINGS. LOUVERS ARE GOVERNED BY FAC RULE 9B-72 AND AS |
| | SUCH, PRODUCT APPROVAL IS REQUIRED. SUBMIT TWO COPIES |
| | OF THE PRODUCT APPROVAL FOR THE SPECIFIC BRAND OF |
| | LOUVER TO BE USED. FOR MORE INFORMATION ON THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM PLEASE VISIT: |
| | WWW.FLORIDABUILDING.ORG |
| | |