| Plan Review Notes For Permit 07060380 |
| Permit Number |
07060380 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-07 17:35:52 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 02.ALL FIRE LINES/FIRE HYDRANT(S) TO BE INSTALLED AND | | | IN WORKING CONDITION BEFORE, DURING, AND AFTER BUILDING | | | CONSTRUCTION.SHOW THE LOCATION OF THE NEAREST FIRE | | | HYDRANT(S) TO THE PROPOSED STRUCTURE | | | | | | 09.THE PROJECT DATA ON SHEET 3.1 STATES THAT THERE | | | ARE FOUR (4) EXITS, WHEREAS THE LIFE SAFETY SUMMARY ON | | | SHEET 7.1 LISTS TWO (2) EXIT DOORS.PLEASE INCLUDE THE | | | ACTUAL NUMBER OF EXITS IN THE PROJECT DATA (SHEET 3.1) | | | AND LIFE SAFETY SUMMARY (SHEET 7.1) AS ILLUSTRATED ON | | | SHEET 7.1 | | | | | | 10.IT IS STATED THAT THE BUILDING WILL BE | | | SPRINKLERED.IN THE EVENT OF A FIRE, HOW AND WHERE | | | WILL WATER BE INTRODUCED INTO THE BUILDING?S | | | | | | 11.AS IT RELATES TO THIS SPRINKLERED BUILDING, HOW | | | WILL NOTIFICATION FOR EMERGENCY RESPONSE BE | | | ACCOMPLISHED IN THE ACTIVATION OF THE SPRINKLER | | | SYSTEM? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE(ON THE PLAN) EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|