| 2007-10-30 13:45:09 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE IN |
| | NEED OF ADDRESSING ALONG WITH NEW COMMENT AS NEW |
| | INFORMATION IS ONLY NOW BEING SUBMITTED FOR REVIEW. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE KNOW AS PER FS 481.229, PLANS AND |
| | DOCUMENTS MAY NOT BE DONE BY A *DESIGNER* WHO IS NOT |
| | LICENSED UNDER FS 481 OR 471. |
| | PLEASE SEE THIS ALSO INCLUDES DESIGNS FOR ENERGY |
| | CALCULATIONS. |
| | PLEASE CONTACT THE BOARD OF ARCHITECTS PROSECUTING |
| | ATTORNEY MR. DAVID MINACCI FOR ANY QUESTIONS REGARDING |
| | THIS. |
| | BY REVISING A TITLE BLOCK DOES NOT ALLEVIATE OR CHANGE |
| | THE STATUTES WHICH IS IN EFFECT. |
| | |
| | 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED |
| | ENERGY CALCULATIONS AS REQUIRED PER 13-101.1.6 HOWEVER |
| | AS CALCULATIONS HAS NOW BEEN SUBMITTED AND THEY DO NOT |
| | CORRELATE WITH PLANS. |
| | PLEASE SEE THE LIGHTING ON PLANS NEEDS TO BE SPECIFIC |
| | AND THE ASSUMED ALLOWANCES FOR INTERIOR LIGHTING NEEDS |
| | TO BE FIGURED. |
| | PLEASE SEE THE CALCULATIONS ALSO DO NOT INCLUDE ANY |
| | EXTERIOR LIGHTING WHICH IS NOT POSSIBLE WHEN THE PLANS |
| | DO HAVE AND CONTAIN EXTERIOR LIGHTING. |
| | PLEASE SEE ONLY ONE COPY OF CALCULATIONS WERE SUBMITTED |
| | WHEN TWO SIGNED, DATED AND SEALED SETS ARE REQUIRED. |
| | PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED. |
| | PLEASE SEE NOTES ABOVE IN NOTE #1. |
| | |
| | 3) NOTE: PLEASE SEE PROVIDE THE SPECIFIC INFORMATION ON |
| | THE FIXTURES WHICH ARE BEING INSTALLED. PLANS MENTIONS |
| | THESE ARE TO BE SELECTED BY THE OWNER HOWEVER THESE IS |
| | REQUIRED AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE MENTIONED |
| | ELECTRICAL LIGHTING CONTROLS FOR INTERIOR LIGHTING. THE |
| | RESPONSE MENTIONS THIS WILL BE DONE HOWEVER COULD NOT |
| | LOCATE ANY CONTROL DEVICES. |
| | FBC 13-415.1.ABC.1.1, 13-415.1.ABC.1.2. |
| | |
| | ** PLEASE SEE ANY POSSIBLE CODES FROM OTHER REVIEWER(S) |
| | WHICH MAY BE REQUESTED. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |