2007-11-05 14:02:49BUILDING PLAN REVIEW
 PERMIT: 07060380
 ADD: 2112 N JOG RD
 CONT: ALTEK STEEL
 TEL: (561)662-8352
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 2ND REQUEST, 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 A) COMPLIED.
 B) COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. NOTE SHEET 3.1 INDICATES THIS BUILDING IS
 DESIGNED TO A TYPE IIAFIRE SPRINKLERED BUILDING. IWHEN
 THE DESIGNER DESIGNS A BUILDING TO A MORE RESTRICTIVE
 TYPE OF CONSTRUCTION THAN REQUIRED
 BY CODE, ALL PORTIONS MUST MEET THIS STANDARD.
 PLEASE SEE TABLE 601 FOOTNOTE (C)(2)(I) REQUIRES THE
 TRUSSES, GIRDERS AND ROOF SHEATHING TO BE FIRE
 RETARDANT TREATED WOOD.
 D) COMPLIED.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.PLANS INDICATE
 A FIRE SPRINKLER SYSTEM IS IN THE DESIGN BUT NO FIRE
 SPRINKLER PLANS WERE SUBMITTED. 106.3.5.1.1(5)
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H )SQ. FT. FOOTPRINT
  
 4)BUILDING PROVISO; 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERMORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER.THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 5)BUILDING PROVISO:109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED
 $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 6) COMPLIED.
  
 7) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL
 BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS
 SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C.
 ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A
 METHOD A CALCULATION MAY BE RESUBMITTED. MINIMUM WALL
 AND ROOF INSULATIONS,ETC.
  
 8) COMPLIED.
  
 9) SHEET 2.1 IT APPEARS THIS BUILDING IS TO BE FILLED
 CELL MASONARY THE END WALLS AND THE REAR WALLS APPEAR
 TO MISSING THE REQUIRED FILLED CELLS?
  
 10) SHEET 2.1 PROVIDES A BEAM SCHEDULE AND SHEET A6.1
 PROVIDES BEAM DETAILS, MISSING A BEAM LAYOUT SHEET?
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE
 PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE WWW.FLORIDABUILDING.ORG
  
 12) NOTE MIAMI DADE REPORTS THAT DO NOT REFER UNDER
 SUB-HEADING # 3 CALCULATIONS TO BEING TESTED OR IN
 COMPLIANCE WITH THE 2004 FBC NEED TO BE REVIEWED BY AN
 ENGINEER,
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 THE OLDER NOA'S WERE TESTED WITH THE 1.33 STEEL FACTORS
 FOR THE FASTENERS WHICH IS NOT ALLOWED UNDER THE 2004
 FBC.
  
 13) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) YKK STOREFRONT, NEEDS FLORIDA COVERSHEET, SEE OLDER
 REPORT WILL NEED VARIFICATION OF FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. B)
 YKK 20 D NARROW STILE OUTSWING DOOR, OLDER REPORT WILL
 NEED VARIFICATION OF THE FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. C)
 MISSING THE REAR DOORS, HOLLOW METAL DOORS
 D) STORM SHUTTERS SEE COMMENTS BELOW FOR STORM
 SHUTTERS
 E) ROOFING ASSEMBLIES
 E1) MODIFIED, MISSING FLORIDA REPORT, SUBSYSTEMS TO BE
 USED IS NOT HIGHLIGHTED, SEE LIMITATION 7 OR 9!
 E2) MONIER TILE, MISSING FLORIDA COVER SHEET, INDICATE
 ON SHEET 4 OR 5 WHICH TYPE OF FASTENING SYSTEM TO BE
 USED.
 F) TRUSS ANCHORS
 G) WALL LOUVERS
  
 14) STORM SHUTTERS: PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING. FBC 1606.1.4.FL BLD
 CODE 2004 SECTION 103.6, 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES:
 1(B) A COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TOPALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]