| 2007-07-14 13:38:49 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | ******SHELL ONLY****** |
| | |
| | 1.SHT 3.1 ALTHOUGH THIS IS A SHELL ONLY, NO |
| | PROVISIONS ARE INDICATED FOR THE REQUIRED DRINKING |
| | FOUNTAIN. SECTION 403.1. PLEASE BE ADVISED THAT A |
| | DRINKING FOUNTAIN IS REQUIRED. |
| | |
| | 2. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE OF |
| | THE BUILDING. SECTION 608.13.2. PLEASE INDICATE ON |
| | PLANS. |
| | |
| | 3. SHT 4.1 WEST ELEVATION DOES NOT SHOW DOWNSPOUTS |
| | INDICATED ON SHT 5.1 ROOF PLAN. PLEASE CORRELATE |
| | INFORMATION FROM ELEVATION AND ROOF PLAN. SECTION |
| | 106.1.1. |
| | |
| | 4. SHT 5.1 SECONDARY ROOF DRAINS OR SCUPPERS SHALL BE |
| | PROVIDED WHERE THE ROOF PERIMETER CONSTURCTION EXTENDS |
| | ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE |
| | ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY |
| | REASON/ SECTION 1107.1 PLEASE INDICATE THE LOCATION OF |
| | THE SECONDARY ROOF DRAINS/SCUPPERS.--SEPARATE |
| | SYSTEMS ARE REQUIRED PER SECTION 1107.2. |
| | |
| | 5. SHT 5.1 THREE RTU'S ON THE ROOF. PLEASE INDICATE IF |
| | THERE WILL BE CONDENSATE DRAINING FROM THESE UNITS. IF |
| | SO PLEASE INDICATE METHOD OF DRAINING FROM THE ROOF. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |