Plan Review Notes For Permit 07060380
Permit Number 07060380
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-14 13:38:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ******SHELL ONLY******
  
 1.SHT 3.1 ALTHOUGH THIS IS A SHELL ONLY, NO
 PROVISIONS ARE INDICATED FOR THE REQUIRED DRINKING
 FOUNTAIN. SECTION 403.1. PLEASE BE ADVISED THAT A
 DRINKING FOUNTAIN IS REQUIRED.
  
 2. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE OF
 THE BUILDING. SECTION 608.13.2. PLEASE INDICATE ON
 PLANS.
  
 3. SHT 4.1 WEST ELEVATION DOES NOT SHOW DOWNSPOUTS
 INDICATED ON SHT 5.1 ROOF PLAN. PLEASE CORRELATE
 INFORMATION FROM ELEVATION AND ROOF PLAN. SECTION
 106.1.1.
  
 4. SHT 5.1 SECONDARY ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTURCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON/ SECTION 1107.1 PLEASE INDICATE THE LOCATION OF
 THE SECONDARY ROOF DRAINS/SCUPPERS.--SEPARATE
 SYSTEMS ARE REQUIRED PER SECTION 1107.2.
  
 5. SHT 5.1 THREE RTU'S ON THE ROOF. PLEASE INDICATE IF
 THERE WILL BE CONDENSATE DRAINING FROM THESE UNITS. IF
 SO PLEASE INDICATE METHOD OF DRAINING FROM THE ROOF.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  