| Plan Review Notes For Permit 07060380 |
| Permit Number |
07060380 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-13 11:18:20 | --------------DENIED------------------ | | | | | | FBC 2004 CODE FAMILY W/ 2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO MECHANICAL INFORMATION WAS PROVIDED ASIDE FROM | | | THE ROOF PLAN SHOWS 3 RTU'S.PLEASE SEE THE MINIMUM | | | PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS AS | | | REQUIRED BY FBC 106.3.5. | | | | | | 2. FLOOR PLAN SHOWS PROVISIONS FOR TWO TOILET ROOMS. | | | PLEASE SHOW PROVISIONS FOR MECHANICAL EHAUST PER FBC,M | | | TABLE 403.3. | | | | | | 3. PLEASE SHOW OUTDOOR AIR CALCULATINS INCLUDING | | | OCCUPANCY CLASIFICATIONS, OCCUPANT LOAD AND OUTDOOR AIR | | | REQUIRED PER FBC, M 403.3. | | | | | | NOTE: ADDITIONAL COMMENTS ARE POSSIBLE BASED ON NEW | | | INFORMATION WHICH MAY BE PROVIDED FOR NEXT REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|