2007-07-13 11:18:20--------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO MECHANICAL INFORMATION WAS PROVIDED ASIDE FROM
 THE ROOF PLAN SHOWS 3 RTU'S.PLEASE SEE THE MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS AS
 REQUIRED BY FBC 106.3.5.
  
 2. FLOOR PLAN SHOWS PROVISIONS FOR TWO TOILET ROOMS.
 PLEASE SHOW PROVISIONS FOR MECHANICAL EHAUST PER FBC,M
 TABLE 403.3.
  
 3. PLEASE SHOW OUTDOOR AIR CALCULATINS INCLUDING
 OCCUPANCY CLASIFICATIONS, OCCUPANT LOAD AND OUTDOOR AIR
 REQUIRED PER FBC, M 403.3.
  
 NOTE: ADDITIONAL COMMENTS ARE POSSIBLE BASED ON NEW
 INFORMATION WHICH MAY BE PROVIDED FOR NEXT REVIEW.
  