| 2007-06-26 18:48:47 | |
| | |
| | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE |
| | STATED ON ARCHITECTURAL SHEETS ALSO. MOST ARE ALREADY |
| | STATED ON THE E-1 SHEET. |
| | PLEASE SEE PLANS MENTIONS THE *PALM BEACH COUNTY |
| | AMENDMENTS* AND THIS PROJECT IS LOCATED IN THE CITY OF |
| | WEST PALM BEACH. |
| | PLEASE ADJUST. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE ANY POSSIBLE CODES FROM OTHER REVIEWER(S) |
| | WHICH MAY BE REQUESTED. |
| | |
| | 2) NOTE: PLEASE KNOW THAT THE SPACE EVEN AS A SHELL |
| | WILL BE REQUIRED TO CONTAIN INTERIOR LIGHTING FOR |
| | INGRESS/EGRESS IN SPACE. THESE MAY BE CONTROLLED BY OS |
| | DEVICES OR MANUAL SWITCHES AS ENTRANCE/EXIT LOCATIONS. |
| | |
| | PLEASE SEE THIS WILL ALSO BE REQUIRED BY THE FIRE |
| | MARSHAL'S OFFICE. |
| | NFPA-101 7.8. THE EMERGENCY BATTERY BACK UP LIGHTS |
| | SHOWN ON PLANS ARE OK FOR LOSS OF POWER. |
| | |
| | 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUIRED |
| | FOR NEW BUILDINGS. |
| | PLEASE SEE METHOD FOR SHELL SPACES. 13-415.1.AB.1.1, |
| | 13-415.2 |
| | |
| | 4) NOTE: PLEASE LABEL MAINS PER 230.2E : EXAMPLE, MAIN |
| | 1OF3, MAIN 2 OF 3 ETC. |
| | |
| | 5) NOTE:PLEASE SEE THAT NOW THAT AN ADDRESS HAS BEEN |
| | ASSIGNED. PLEASE BE SURE TO REVISE THE TITLE BLOCKS FOR |
| | NEW ADDRESS WHICH WAS ASSIGNED AS 2112 N. JOG RD. ** |
| | PLEASE BE SURE TO ALSO REVISE THE PERMIT APPLICATION. A |
| | NEW PERMIT APPLICATION WILL BE ATTACHED TO NOTES FOR |
| | CONVENIENCE AS THERE ARE SEVERAL ITEMS ON PERMIT |
| | APPLICATION WHICH ARE NOT VISIBLE. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |