Plan Review Notes
Plan Review Notes For Permit 07060380
Permit Number 07060380
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-19 22:35:16BUILDING PLAN REVIEW
 PERMIT: 07060380
 ADD: 2112 N JOG RD
 CONT: ALTEK STEEL
 TEL: (561)662-8352
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.EVEN SHELL BUILDINGS!
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H )SQ. FT. FOOTPRINT
  
 4)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERMORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER.THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 5)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED
 $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 6) SHEET 5.1 INDICATES ROOF DRAINS BUT THERE ARE NO
 SECONDARY OREMERGENCY OVERFLOWS, ALSO PLAN INDICATES
 DOWN SPOUT BUT ON SHEET 4.1 THERE IS NO DOWNSPOUT OR
 RAIN LEADERS SHOWN.
 1503.4.1 GUTTERS.
 GUTTERS AND LEADERS PLACED ON THE OUTSIDE OF BUILDINGS,
 OTHER THAN GROUP R-3 AS APPLICABLE IN SECTION 101.2 ,
 PRIVATE GARAGES AND BUILDINGS OF TYPE V CONSTRUCTION,
 SHALL BE OF NONCOMBUSTIBLE MATERIAL OR A MINIMUM OF
 SCHEDULE 40 PLASTIC PIPE.
  
 1503.4.3 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 7) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL
 BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS
 SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C.
 ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A
 METHOD A CALCULATION MAY BE RESUBMITTED. MINIMUM WALL
 AND ROOF INSULATIONS,ETC.
  
 8) DISCREPANCY BETWEEN THE LIFE SAFETY PLAN AND SHEET
 3.1, MISSING THE REAR DOORS?
  
 9) SHEET 2.1 IT APPEARS THIS BUILDING IS TO BE FILLED
 CELL MASONARY THE END WALLS AND THE REAR WALLS APPEAR
 TO MISSING THE REQUIRED FILLED CELLS?
  
 10) SHEET 2.1 PROVIDES A BEAM SCHEDULE AND SHEET A6.1
 PROVIDES BEAM DETAILS, MISSING A BEAM LAYOUT SHEET?
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE
 PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE WWW.FLORIDABUILDING.ORG
  
 12) NOTE MIAMI DADE REPORTS THAT DO NOT REFER UNDER
 SUB-HEADING # 3 CALCULATIONS TO BEING TESTED OR IN
 COMPLIANCE WITH THE 2004 FBC NEED TO BE REVIEWED BY AN
 ENGINEER,
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 THE OLDER NOA'S WERE TESTED WITH THE 1.33 STEEL FACTORS
 FOR THE FASTENERS WHICH IS NOT ALLOWED UNDER THE 2004
 FBC.
  
 13) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) YKK STOREFRONT, NEEDS FLORIDA COVERSHEET, SEE OLDER
 REPORT WILL NEED VARIFICATION OF FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. B)
 YKK 20 D NARROW STILE OUTSWING DOOR, OLDER REPORT WILL
 NEED VARIFICATION OF THE FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. C)
 MISSING THE REAR DOORS, HOLLOW METAL DOORS
 D) STORM SHUTTERS SEE COMMENTS BELOW FOR STORM
 SHUTTERS
 E) FOOFING ASSEMBLIES
 E1) MODIFIED, MISSING FLORIDA REPORT, SUBSYSTEMS TO BE
 USED IS NOT HIGHLIGHTED, SEE LIMITATION 7 OR 9! E2)
 MONIER TILE, MISSING FLORIDA COVER SHEET, INDICATE ON
 SHEET 4 OR 5 WHICH TYPE OF FASTENING SYSTEM TO BE
 USED.
  
 14) STORM SHUTTERS: PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING. FBC 1606.1.4.FL BLD
 CODE 2004 SECTION 103.6, 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES:
 1(B) A COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TOPALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]