Plan Review Notes
Plan Review Notes For Permit 07060364
Permit Number 07060364
Review Stop B
Sequence Number 3
Notes
Date Text
2007-08-21 12:02:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)TWO COLLATED SETS REQUIRED FOR PERMIT ISSUANCE.
 ONLY ONE INSTALLATION SCHEDULE WAS SUBMITTED.DUE TO
 WORK LOAD, I AM UNABLE TO MAKE PHOTOCOPIES AND COLLATE
 PERMIT PACKAGES.
  
 2.)SEE SHEET 11.A 2 1/2" EDGE DISTANCE REQUIRES A
 FACTOR OF .66.
  
 3.)THE SHUTTER MOUNTING TYPE SHOULD BE SPECIFIC TO
 THE DETAIL YOU ARE USING, FOR INSTANCE, WALL MOUNT 1
 THROUGH 4, CELING 5, FLOOR MOUNT 6 THROUGH 8.
  
 4.)YOU HAVE SPECIFIED "COPLE BLOCK".DOES THIS MEAN
 CONCRETE BLOCK?ANCHORING FOR WALL MOUNT 1 WAS CIRCLED
 ON THE PRODUCT APPROVAL, BUT THIS REQUIRES A CONCRETE
 SUBSTRATE.
  
 5.)WALL MOUNT 1 AND WALL MOUNT 3 INFORMATION WAS
 CIRCLED ON THE PRODUCT APPROVAL.WALL MOUNT 3 REQUIRES
 4" ANCHOR SPACING DUE TO THE .66 FACTOR, BUT ALL ANCHOR
 SPACING IS SPECIFIED AS 6" ON THE INSTALLATION
 SCHEDULE.
  
 6.)ANCHOR SPACING FOR 8' SPANS CIRCLED, BUT OPENING
 #6 EXCEEDS 8'.
  