| Plan Review Notes For Permit 07060364 |
| Permit Number |
07060364 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-08-21 12:02:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)TWO COLLATED SETS REQUIRED FOR PERMIT ISSUANCE. | | | ONLY ONE INSTALLATION SCHEDULE WAS SUBMITTED.DUE TO | | | WORK LOAD, I AM UNABLE TO MAKE PHOTOCOPIES AND COLLATE | | | PERMIT PACKAGES. | | | | | | 2.)SEE SHEET 11.A 2 1/2" EDGE DISTANCE REQUIRES A | | | FACTOR OF .66. | | | | | | 3.)THE SHUTTER MOUNTING TYPE SHOULD BE SPECIFIC TO | | | THE DETAIL YOU ARE USING, FOR INSTANCE, WALL MOUNT 1 | | | THROUGH 4, CELING 5, FLOOR MOUNT 6 THROUGH 8. | | | | | | 4.)YOU HAVE SPECIFIED "COPLE BLOCK".DOES THIS MEAN | | | CONCRETE BLOCK?ANCHORING FOR WALL MOUNT 1 WAS CIRCLED | | | ON THE PRODUCT APPROVAL, BUT THIS REQUIRES A CONCRETE | | | SUBSTRATE. | | | | | | 5.)WALL MOUNT 1 AND WALL MOUNT 3 INFORMATION WAS | | | CIRCLED ON THE PRODUCT APPROVAL.WALL MOUNT 3 REQUIRES | | | 4" ANCHOR SPACING DUE TO THE .66 FACTOR, BUT ALL ANCHOR | | | SPACING IS SPECIFIED AS 6" ON THE INSTALLATION | | | SCHEDULE. | | | | | | 6.)ANCHOR SPACING FOR 8' SPANS CIRCLED, BUT OPENING | | | #6 EXCEEDS 8'. | | | |
|