| 2007-12-14 14:04:30 | BUILDING REVISION CHECKLIST: |
| | |
| | 1- DRAWINGS NEED TO BE SIGNED, SEALED AND DATED BY THE |
| | ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTE AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE |
| | CODE. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVEIN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS PRIOR |
| | TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 3- REVISE STORM SHUTTERS INSTALLATION SCHEDULE: |
| | A) FOUR COLUMNREFERS TO THE SHUTTERS MOUNTING |
| | CONDITIONS. EG: WALL MOUNTED, BUILT OUT MOUNTED, ETC, |
| | NOT THE ANCHOR TYPE TO BE USED. REVISE AS REQUIRED. |
| | |
| | B) SHUTTER SPAN SHOWNDOESN'T RELATETO WINDOW |
| | HEIGHT SHOWN ON COLUMN #2. REVISE AS REQUIRED. |
| | ***NOTE: ALSO, KEEP IN CONSIDERATION THE EDGE DISTANCE |
| | REQUIRED. SEE SHUTTERS DRAWINGS TO SEE HOW THE PANEL |
| | SPAN IS MEASURED AND REVISE AS REQUIRED. |
| | |
| | C) CLARIFY WHICH ANCHOR TYPE IS GOING TO BE USED |
| | PANEL MATE PLUS OR TAPCON.INSTALLATION SCHEDULE SHOWS |
| | ONE ANCHOR ON COLUMN4 AND ANOTHER ANCHORON COLUMN |
| | #10. REVISE AS REQUIRED. |
| | |
| | D) REVISE MINIMUM EDGE DISTANCE REQUIRED. SEE STORM |
| | SHUTTERS DRAWINGS AND REVISE AS REQUIRED. |
| | |
| | 4- CLEARLY MARK ON STORM SHUTTER DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE |
| | USED TO VERIFY IF INFORMATION SHOWN ON INSTALLATION |
| | SCHEDULE MATCHES. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 5- UPDATE TOTAL VALUATION TO INCLUDE ALL SCOPE OF WORK |
| | TO BE PERFORMED, INCLUDING THE CHANGE OUT OF ALL |
| | WINDOWS. INITIAL PERMIT APPLICATION CALLED FOR WINDOW |
| | REPLACEMENT OF A COUPLE OF WINDOWS ONLY,NOT ALL THE |
| | WINDOWS. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- ENGINEER OF RECORD TO CERTIFY THAT ALLEXISTING |
| | WINDOWS ARESINGLE HUNG WINDOWS AND THAT THEY WILL BE |
| | REPLACEDFOR SAME TYPE OF WINDOW.AND,REPLACEMENT |
| | OF WINDOWS DON'TMAKE THE BUILDING LESS SAFER THAT IT |
| | WAS BEFORE AS REQUIRED BY SEC. 501.2 OF 2004 EXISTING |
| | BUILDING CODE. |
| | |