| Plan Review Notes For Permit 07060316 |
| Permit Number |
07060316 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-29 18:48:58 | FAILED | | | | | | 1) MINOR AMENDMENT APPROVAL REQUIRED FOR GENERATOR | | | LOCATION.THIS IS IN CITYPLACE RETAIL SERVICE AREA. | | | | | | 2) WHERE WILL THE DUMPSTERS/COMPACTORS FOR CITYPLACE BE | | | RELOCATED TOO?THESE NEED TO BE SHOWN ON THE PLANS. | | | | | | 3) THE TURNING RADIUS/TURN AROUND FOR THE GARBAGE | | | TRUCKS AND 18-WHEELERS DELIVERING TO CITYPLACE RETAIL | | | SHALL BE SHOWN ON THE PLANS.THE GENERATORS ARE TAKING | | | UP A SIGNIFICANT PORTION OF THE SERVICE AREA. | | | | | | 4) CITYPLACE RETAIL STAMP IS REQUIRED ON THE PLANS. | | | | | | 5) WHAT IS THE RELOCATION PLAN FOR THE MANHOLE.IS | | | THIS A CITY WATER MAIN? IF SO, THEN THE WPB UTILITIES | | | SHALL SIGN-OFF ON THE RELOCATION/BURYING OF THE | | | MANHOLE. | | | | | | 6) HOW TALL IS THE GENERATOR?CLEARLY STATE THE | | | MAXIMUM HEIGHT.THE NUMBERS IN THE SCHEMATICS ARE | | | DIFFICULT TO READ. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|