| Plan Review Notes For Permit 07060316 |
| Permit Number |
07060316 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-26 23:38:09 | *****DENIED***** | | | | | | | | | 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY | | | POWER SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 110. | | | | | | 3.PROVIDE A SITE PLAN SHOWING PROPER SETBACKS TO | | | PROPERTY LINES, BUILDING OPENINGS OF AT LEAST 10 FEET | | | DISTANCE, AND ANY MEANS OF EGRESS IN REGARDS TO FUEL | | | EXHAUSTING. | | | | | | 4.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE | | | INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA | | | 704 LABELS WILL BE REQUIRED. | | | | | | 5.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | | GENERATOR. | | | | | | 6.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 7.THE INSTALLATION AND/OR SCOPE OF WORK SHALL NOT | | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | | SAID PROPERTY OR THE VICINITY THEREOF. | | | | | | 8.HOW WILL THE ABOVE GROUND FUEL TANK BE PROTECTED | | | FROM VEHICULAR/COLLISION DAMAGE? | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW |
|