2007-07-26 23:38:09*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 110.
  
 3.PROVIDE A SITE PLAN SHOWING PROPER SETBACKS TO
 PROPERTY LINES, BUILDING OPENINGS OF AT LEAST 10 FEET
 DISTANCE, AND ANY MEANS OF EGRESS IN REGARDS TO FUEL
 EXHAUSTING.
  
 4.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA
 704 LABELS WILL BE REQUIRED.
  
 5.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 6.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 7.THE INSTALLATION AND/OR SCOPE OF WORK SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF.
  
 8.HOW WILL THE ABOVE GROUND FUEL TANK BE PROTECTED
 FROM VEHICULAR/COLLISION DAMAGE?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW