| Date |
Text |
| 2007-06-26 18:13:38 | |
| | |
| | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THAT AS STATED ON PREVIOUS PHONE |
| | CALLS, THIS SEPARATE PERMIT WAS REQUIRED AS THE |
| | GENERATORS WERE LOCATED ON A DIFFERENT PARCEL AND LEGAL |
| | PROPERTY. |
| | PLEASE SEE HOWEVER THE PERMIT WAS APPLIED FOR UNDER THE |
| | SAME ADDRESS OF THE OFFICE TOWER WHICH IS INCORRECT. |
| | PLEASE OBTAIN THE CORRECT PARCEL AND ADJUST PLANS WHICH |
| | ARE TO BE SUBMITTED. |
| | AS ONLY A LEGAL EASEMENT WAS ISSUED, THIS IS STILL |
| | LOCATED ON A SEPARATE PCN. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE NO SITE/SURVEY PLANS WERE SUBMITTED |
| | FOR LOCATION UNDER THIS LEGAL RECORDED PERMIT. |
| | REVIEW FOR CLEARANCES, LOCATIONS ETC CAN NOT BE DONE AT |
| | THIS TIME. |
| | 110.26. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SUBMIT THE ELECTRICAL PLANS FOR THE |
| | GENERATOR AND ITS LOCATION ALONG WITH THE REVISED |
| | ELECTRICAL RISER FOR THE BASE OFFICE BUILDING IN WHICH |
| | IT FEEDS. |
| | PLEASE SEE THE NOTES UNDER THE BASE BUILDING ON THE |
| | LAST SUBMITTED REVISED ELECTRICAL AS THE PLANS NEED TO |
| | REFLECT CHANGES AND CORRECTIONS FOR THE INCREASED |
| | UNITS. |
| | PLEASE ALSO SEE NOTES WITH RESPECT TO THE MODIFICATIONS |
| | OF THE GENERATOR. IF THIS UNIT IS STILL GOING TO BE |
| | BI-FUEL AND ANY MODIFICATIONS TO THIS UNIT MAY VERY |
| | WELL VOID ANY OF THE CERTIFICATIONS OF THE GENERATOR. |
| | PLEASE KNOW AS THESE ARE PART OF LEGALLY REQUIRED AND |
| | EMERGENCY LIFE SAFETY SYSTEMS IN THE OFFICE BUILDING |
| | ANY MODIFICATIONS TO CERTIFIED OR LISTED EQUIPMENT IS |
| | NOT PERMITTED. |
| | 110.3, 215.5, 90.7, 700, 701 ETC. |
| | REVISE SERVICE. |
| | |
| | 4) NOTE: PLEASE BE SURE ALL MANUFACTURES SPECS/CUT |
| | SHEETS ARE SUBMITTED. PLEASE SEE COMMENTS FROM OTHER |
| | TRADES FOR FUEL TANKS ETC. |
| | |
| | 5) NOTE: PLEASE SEE THE ELECTRICAL CONTRACTOR DID NOT |
| | SIGN ON THE ELECTRICAL LINE FOR THE GEN-ELEC PERMIT. |
| | PLEASE DO SO. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |