Plan Review Notes
Plan Review Notes For Permit 07060316
Permit Number 07060316
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-26 18:13:38 
  
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT AS STATED ON PREVIOUS PHONE
 CALLS, THIS SEPARATE PERMIT WAS REQUIRED AS THE
 GENERATORS WERE LOCATED ON A DIFFERENT PARCEL AND LEGAL
 PROPERTY.
 PLEASE SEE HOWEVER THE PERMIT WAS APPLIED FOR UNDER THE
 SAME ADDRESS OF THE OFFICE TOWER WHICH IS INCORRECT.
 PLEASE OBTAIN THE CORRECT PARCEL AND ADJUST PLANS WHICH
 ARE TO BE SUBMITTED.
 AS ONLY A LEGAL EASEMENT WAS ISSUED, THIS IS STILL
 LOCATED ON A SEPARATE PCN.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE NO SITE/SURVEY PLANS WERE SUBMITTED
 FOR LOCATION UNDER THIS LEGAL RECORDED PERMIT.
 REVIEW FOR CLEARANCES, LOCATIONS ETC CAN NOT BE DONE AT
 THIS TIME.
 110.26.
 FBC 106.1.2
  
 3) NOTE: PLEASE SUBMIT THE ELECTRICAL PLANS FOR THE
 GENERATOR AND ITS LOCATION ALONG WITH THE REVISED
 ELECTRICAL RISER FOR THE BASE OFFICE BUILDING IN WHICH
 IT FEEDS.
 PLEASE SEE THE NOTES UNDER THE BASE BUILDING ON THE
 LAST SUBMITTED REVISED ELECTRICAL AS THE PLANS NEED TO
 REFLECT CHANGES AND CORRECTIONS FOR THE INCREASED
 UNITS.
 PLEASE ALSO SEE NOTES WITH RESPECT TO THE MODIFICATIONS
 OF THE GENERATOR. IF THIS UNIT IS STILL GOING TO BE
 BI-FUEL AND ANY MODIFICATIONS TO THIS UNIT MAY VERY
 WELL VOID ANY OF THE CERTIFICATIONS OF THE GENERATOR.
 PLEASE KNOW AS THESE ARE PART OF LEGALLY REQUIRED AND
 EMERGENCY LIFE SAFETY SYSTEMS IN THE OFFICE BUILDING
 ANY MODIFICATIONS TO CERTIFIED OR LISTED EQUIPMENT IS
 NOT PERMITTED.
 110.3, 215.5, 90.7, 700, 701 ETC.
 REVISE SERVICE.
  
 4) NOTE: PLEASE BE SURE ALL MANUFACTURES SPECS/CUT
 SHEETS ARE SUBMITTED. PLEASE SEE COMMENTS FROM OTHER
 TRADES FOR FUEL TANKS ETC.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL CONTRACTOR DID NOT
 SIGN ON THE ELECTRICAL LINE FOR THE GEN-ELEC PERMIT.
 PLEASE DO SO.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]