Plan Review Notes
Plan Review Notes For Permit 07060316
Permit Number 07060316
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-17 16:45:34BUILDING PLAN REVIEW
 PERMIT: 07060316
 ADD: 525 OKEECHOBEE BLVD
 CONT: TERRY"S ELECTRICAL
 TEL: (561)689-4182
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLEASE PROVIDE A SITE PLAN WHERE THESE GENERATORS
 WILL BE INSTALLED. I BELIEVE FROM THE BASE BUILDING
 PLAN THAT THERE IS AN EASEMENT AND THAT THESE
 GENERATORS WILL ACTUALLY BE PLACED
 ON THE SAME LOT AS THE "B" BLOCK PARKING GARAGE ALONG
 WITH THE NEW ELEVATOR TOWER. PLEASE SUBMIT SITE PLAN IF
 CORRECTIONS NEED TO BE MADE TO THE PERMIT APPLICATION
 ADDRESS AND PCN PLEASE DO SO. PLEASE NOTE THE CORRECT
 ADDRESS TO THE SITE PLAN HEADER !
  
 4) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY 3)-
 WIND EXPOSURE
  
 5) ) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE
 PROVIDE SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS
 WITH THE INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE
 OF FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION. SECOND, PROVIDE
 INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH,
 IF WIREMESH, FIBER MESH OR IF STEEL REBAR WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]